Form No: ETP-F-01 & Revision Date: 19.05.

2022
Revision No: 02

Meril Road, Salgaria, Pabna


Quality Assurance Department

ETP Raw and Treated water (Outlet) analysis report

Sample Location : STL & SFBL, ETP, Pabna plant


Type of Plant : Anaerobic, Anoxic & Aerobic Treatment
Test Frequency : Weekly
Sample Received date: 26.07.2022
Sample Received By : Kazi Abdul Malek
Date of testing : 26.07.2022
Lab Sample ID : QA-28/22

Sample Parameter Unit Result Remarks


pH - 6.17
Temperature °C 31.1
Raw Effluent Total Dissolved Solid (TDS) ppm 1486
(Homogeneous Tank) Electro – Conductivity (EC) µS/cm 2745
Dissolved Oxygen (DO) ppm 0.18
COD ppm 560

Sample Parameter Unit Standard Result Test Method Remarks


Color - Colorless Colorless
Odor - Absent Absent
Temperature °C NMT 40 33.0
pH at 26.4° C - 6 to 9 7.45 pH, USEPA electrode method

Treated Total Suspended Standard methods(2005), 2540D


Electro-
ppm NMT 150 115 & EPA(1983) method
Effluent Solid(TSS) 160.2(Residue, non-filterable) Conductivity
(Clarifier Total Dissolved ppm USEPA Direct Measurement found out of
NMT 2100 1333 limit.
Tank Solid (TDS) Method1, 2 ,Method 8160

outlet) Electro – µS/cm USEPA Direct Measurement


NMT 1200 2860 Method1, 2 ,Method 8160
Conductivity (EC)
Dissolved Oxygen Direct Measurement Method1  , 
ppm 4.5 to 8.0 6.25 Method-10360, LDO Probe
(DO)
Closed Reflux, Titrimetric 
COD ppm NMT 200 32 Method

BOD ( 5 days) ppm NMT 50 15 Ultimate


Note:
 Sludge Quantity (Biological Oxidation Tank) of ETP:   450 ml/lt.
 Water flow rate of the inlet water was 6.0 m³/hr. whereas the capacity of the ETP plant is 6 m³/hr.

Test performed By : Approved By :