2 MVA
3 PHASE
0.85 PF
Lagging PF S(apparent power in 3P) = (1.732)(IL = IP)(VLL)
13.2 kV V=IZ
LL CONN
Z=V∠0/I∠-θ =V/I∠θ SUMMARY
SLOAD = 1.7 MW + 1.05357 MVAR 1=SIN^2+COS^2 Load VS VR PLOSS
ZLOAD = 87.12 ∠ 31.7883 OHMS Constant 2MVA
ZLOAD = 74.052 +J 45.8933 OHMS Power 0.85 PF 12.224 2.90% 31.27 kW
Lagging
Constant 87.48 12.19 2.61% 25.33 kW
Current ∠-31.79
Constant 87.12 12.1590 2.35% 20.37 kW
Impedance ∠31.79
Glenn John P. Gasapo EESIMS43Z E41 Assignment 3
VR= 11.88 kVLL @ 90% Nominal Value VR= 11.88 kVLL @ 90% Nominal Value
Constant Power Constant Current
VR = 12.224-11.88x 100%
11.88
VR = 2.90%
Glenn John P. Gasapo EESIMS43Z E41 Assignment 3