You are on page 1of 6

Self-Excited Induction Generator Based Generation

System Regulation Using Synchronous Generator as


Reactive Power Compensator
2022 14th Seminar on Power Electronics and Control (SEPOC) | 978-1-6654-7089-6/22/$31.00 ©2022 IEEE | DOI: 10.1109/SEPOC54972.2022.9976454

Raul E. Pivetta, Igor Luiz Dal Forno, Felipe Bovolini Grigoletto


Lucas G. Scherer, Robinson F. de Camargo Energy Processing and Control Laboratory - LAPEC
Power Electronics and Control Research Group - GEPOC Federal University of Pampa - UNIPAMPA
Federal University of Santa Maria - UFSM Alegrete, Brazil
Santa Maria, Brazil
raul-pivetta@hotmail.com

Abstract—This article presents the modeling, simulation and amplitude and frequency of the generated voltages varies
experimental results of a microgrid formed by the parallel with the load applied to the machine terminals. Thus, the
operation of the Self-Excited Induction Generator (SEIG) and stability of the generation system is strictly dependent on
the Field-wound Synchronous Generator (SG), where the SG
acts as a reactive compensator. In the generation system, the the balance of active and reactive power at the generator
SEIG is kept supplying rated power, driven through a primary terminals [3], [4]. This condition makes the SEIG need reactive
source of constant power. The SG, on the other hand, is driven by power compensation techniques for effective regulation of the
a constant speed source. A Electronic Load Controller (ELC) is generated voltages [5].
used to consume the surplus active power generated by the SEIG
In opposition, the SG can control the generated reactive
that is not used by the consumer unit in order to regulate system’s
frequency. When the connected load is greater than the SEIG’s power and, consequently, the amplitude of the generated
rated power, the SG acts by supplying active power to supply voltage by ajusting the field excitation [9]. Thus, in isolated
the demand, the ELC is turned off and the frequency control is systems, the SG is used as a grid former [6]–[8].
performed by the speed control of the SG’s primary machine. Thus, the use of SG and SEIG in parallel presents comple-
The reactive power in the microgrid is controlled by the SG
static excitation system. This system, based on a Buck converter mentary characteristics between each other. This association
powered by an external DC source, acts to control the voltage at becomes interesting mainly in the repowering of SG based
the Common Connection Point (CCP) of the system by adjusting generation plants, where the inclusion of SEIG can increase
the SG field voltage. Experimental results shows the performance total installed power and improve system’s reliability [10]. The
and reliability of the system against load connections from no- main advantage is that the costs associated with the inclusion
load to rated power.
Index Terms— microgrids, self-excited induction generator,
of the induction generator are lower when compared to the
synchronous generator, power processing costs related to the SG [11]. Moreover, the parallel connection
of a SG and a SEIG is simpler than that of two SG, since
I. I NTRODUCTION it does not require advanced synchronization techniques [12].
When the two generators operate in parallel, they can share the
A microgrid (MG) is characterized by the interconnection of same primary source when there is surplus primary resource
different forms of energy generation to feed an isolated load or or combine two different primary sources, such as water, wind,
distribution network in order to obtain greater efficiency and biomass or even non-renewable thermoelectric source [13].
flexibility of energy resources in the place where it is installed Thus, this paper proposes the connection of a SG in parallel
[1]. Due to this possibility of connecting different forms of to a SEIG, using a static excitation system based on a Buck
energy, currently, MGs are considered as decentralized and converter powered by an independent source for the SG in
promising electrical energy systems, enabling the interconnec- order to control the generated voltage’s amplitude. The use of
tion of different renewable sources through interfaces made an independent source to power the excitation system allows
up of power electronics [2]. The microgrid under study in the interconnection of a different energy resource to the MG.
the present article is composed by a Self-excited Induction
Generator (SEIG) and a Wound Field Synchronous Generator II. S YSTEM D ESCRIPTION
(SG) operating in parallel to feed AC loads.
The use of SEIG in isolated systems is already consoli- Fig. 1 shows the proposed microgeneration system. The
dated. This type of generator has advantages such as low SEIG primary mover is considered a constant power supplier,
cost, greater robustness, reduced need for maintenance and characterizing, for example, a hydroelectric turbine driven by
application flexibility. However, in isolated applications, the constant flow. The SG, on the other hand, is driven by a

Authorized licensed use limited to: UNIVERSIDAD POLITECNICA SALESIANA. Downloaded on May 02,2023 at 02:13:41 UTC from IEEE Xplore. Restrictions apply.
machine of constant speed and variable power, such as a connected, causing the terminal voltage to increase. At that
controlled thermoelectric or biofuel system. moment, the excitation system decreases the voltage vf d to a
value below vf d−no−load and the SG starts to consume the
excess reagents. Finally, the reactive power of the load is
zeroed and vf d takes on the value of vf d−no−load and the
system returns to the condition of the first instant.

ELC active SG active IG active Load active


power
PIG nom

power
PIG nom

power
PIG nom

power
PIG nom

Frequency
fnom
Fig. 1. Proposed System.
Time
Due to the greater robustness, the SEIG is kept operating at
its rated power. Thus, a capacitor bank is designed to supply Fig. 2. Microgrid active power regulation.
the reactive power demanded by the load in the rated condition
of the SEIG. The SG acts by compensating the reactive power
IG reactive Load reactive

1 2 3 4
demanded by the loads to keep the amplitude of the generated
power

voltage constant. It is also capable of providing active power


when the load demand is greater than the SEIG capacity.
Since SIEG is kept supplying rated power by it’s unregu-
lated primary mover, surplus active power must be consumed
power

to keep system’s frequency constant. Thus, a Electronic Load


QCexc
Controller (ELC) is employed to regulates the system’s fre-
quency, consuming this excess power to ensure the correct
SG reactive

balance between generated and consumed active power. Fig. 2


power

demonstrate the active power regulation dynamics. During the


entire operation, SEIG is kept supplying rated power, PIGnom .
As load power increases, the ELC decreases the consumed
voltage

vfd-no-load
field

power, to the point where it is completely zeroed, when load


power is greater than or equal to SEIG capacity (PIGnom ).
From that point on, SG also starts to provide active power
voltage

and SG primer mover takes over the frequency control.


CCP

VTnom
Reactive power regulation is performed through the control
of the SG excitation, where a Buck converter powered by an
Time
external DC bus adjusts the generator’s field voltage, varying
the amount of generated reactive power. 3 exemplify the Fig. 3. Microgrid reactive power regulation.
reactive power regulation. Fig. 3 can be divided into 4 instants.
Initially, the load connected to the system does not consume III. S YSTEM M ODELING
reactive power and, consequently, the SG generates only a In this section, the SG, Buck converter and ELC model are
portion of reactives to maintain rated terminal voltage, with a exposed. It is noteworthy that it is not necessary to model the
field voltage (vf d ) equal to vf d−no−load . In the second instant, SEIG, as there is no control over it.
an inductive load is connected. In this way, the terminal
voltage tends to drop, but the excitation system increases vf d , A. SG and Buck converter modeling
increasing the generated reactive power and regulating the grid In [14] is presented the modeling and design of a SG
voltage amplitude. At the third instant, a capacitive load is terminal voltage control system using a static excitation system

Authorized licensed use limited to: UNIVERSIDAD POLITECNICA SALESIANA. Downloaded on May 02,2023 at 02:13:41 UTC from IEEE Xplore. Restrictions apply.
controlled by a Buck converter powered by an external source, B. ELC modeling
where the models used in this paper are obtained and validated
The ELC topology is shown in Fig. 1. It can be considered
by simulation and experimental results.
as a power-draining resistor, that is, it does not insert dynamics
1) Transfer Functions: According to [15], SG excitation
model can be represented by a first-order function that relates
into the system. Therefore, the ELC model Gelc (s) is taken as
terminal voltage amplitude (modeled by the vd component
function that relates the estimated frequency variations, fe , to
of the phase voltages) to the field voltage vf d , given by (1).
′ ELC duty cycle, de , including the frequency estimation delay
Td0 is the direct-axis open-circuit transient time constant (also
of 0.1 seconds. The ELC model, given by (3), is obtained
called the field circuit time constant, as it is related to the
through experimental data.
parameters of this winding) and KG is a gain that depends
on the field voltage required to generate the nominal no-load
∆fe (s) 12
terminal voltage. The parameters presented in (1) correspond Gelc (s) = = (3)
to the SG of the experimental bench. When a power invariant ∆de (s) 0.1s + 1
dq0 transformation is applied to the generator phase voltages, IV. C ONTROL SYSTEM
the d component is equivalent to the RMS value of the line
voltages [14]. This substitution eliminates the delay caused by Fig. 5 shows the block diagram of the design control system.
calculating the RMS value [16]. As this is a balanced three-phase three-wire system, only two
line voltages are measured. From these, the equivalent phase
vd (s) KG 19.54121 voltages are obtained, used for applying the dq0 transforma-
G(s) = = ′ = (1)
vf d (s) Td0 s + 1 0.47619s + 1 tion. This reference system change requires knowledge of the
The non-ideal Buck converter with RL load topology is angular position of system voltages, the synchronism signal θ.
shown in Fig. 4. In this circuit, the converter’s load is the
SG field winding, modeled by a RL circuit, Rf d and Lf d .
The LC filter is used in the Buck converter output stage to Control system - DSP TMS320F28335
ensure lower output voltage ripple.
ωv
sin θ Frequency
identification fe

va Kalman
filter

θ
va vd
v ab abc
line-phase vb vq
v bc transformation vc v0
dq0
Fig. 4. Non-ideal Buck converter with RL load.

The parameters of the designed converter, as well as the Voltage loop


parameters of the SG, obtained experimentally, are presented controller
vdref ev uv vPWM_Buck
in Table 1. It is considered that the converter is powered by +
- Cv PWM
a 150 V bus. The high value of Lf d is due to high value of modulation
vd

Td0 .
Carrier 20 kHz
TABLE I
N ON - IDEAL B UCK C ONVERTER PARAMETERS Frequency loop
controller
Parameter Value fref ee ue vPWM_ELC
+
- Ce PWM
Input Voltage (Vin ) 150 V
modulation
Switching frequency (fs ) 20 kHz fe
Filter inductor (L) 4.55 mH
Filter capacitor (Cf ) 3.3 µF
Carrier 20 kHz
Field resistance (Rf d ) 31.94 Ω
Field inductance (Lf d ) 16 H
Capacitor parasitic resistance (rC ) 0.2 Ω
Fig. 5. Control System Block Diagram.
Inductor parasitic resistance (rL ) 0.263 Ω

Vf d (s) Cf Lf d Vs rC s2 + Vs (Cf Rf d rC + Lf d )s + Rf d Vs
Gvd (s) = =
D(s) Cf LLf d s3 + Cf (LRf d + LrC + Lf d rC + Lf d rL )s2 + (L + Lf d + Cf Rf d rC + Cf Rf d rL + Cf rC rL )s + (Rf d + rL )
(2)

Authorized licensed use limited to: UNIVERSIDAD POLITECNICA SALESIANA. Downloaded on May 02,2023 at 02:13:41 UTC from IEEE Xplore. Restrictions apply.
In [17], a method for estimating the states of linear systems way, a PI controller in the form of (5) is designed, with gains
corrupted by uncertainties and noise is presented, based on KP e = 0.08333 e KIe = 0.58333.
the use of the Kalman filter. The method consists of obtain the
KIe
fundamental component of the PCC voltages. From this signal, Ce (s) = KP e + (5)
the system frequency fe is estimated through the frequency s
identification algorithm, as shown in Fig. 5.
From the synchronization angle θ and the equivalent phase 420 vd

voltage (V)
Terminal
voltages, the dq0 transformation is applied. In this way, the 400 vdref
voltage amplitude vd and the system’s estimated frequency fe 380
are obtained and fed back to the control system. 360
340
A. Excitation system control 0,3

action u v
Control
Fig. 6 shows the block diagram of the excitation system 0,2
control, where a controller Cv (s) receives the voltage error 0,1
signal between the vd component reference value vdref (s) 0
and the CCP voltages actual vd (s) component. This controller 60

voltage (V)
generates the duty cycle of the buck converter, dv (s), which

Field
40
applies the field voltage required to regulate the value of vd (s).
20
0
4 4,5 5
Time (seconds)

Fig. 7. SG control validation.

Fig. 6. Excitation system control block diagram.

According to IEEE standard 421.2 [18], a excitation system


control must have a gain margin greater than 6 dB, Phase
Margin greater than 40° and overshoot below 15% to ensure
good voltage regulation. Thus, from these conditions, Cv (s)
is design as a PI type controller, given by (4), with gains KP v
= 0.00261 and KIv = 0.00564.
Fig. 8. ELC control block diagram.
KIv
Cv (s) = KP v + , (4) 1) ELC control validation: In order to partially validate
s
the frequency controller design, a simulation of the SEIG with
1) Excitation control validation: In order to validate the ELC is performed. The controller response is evaluated against
designed controller, a simulation of SG excitation system is variations in the reference frequency of the system. Fig. 9
performed. The designed controller is evaluated by varying shows the system frequency compared to the reference value
the voltage reference with the machine in the no-load condi- and the duty cycle of the ELC switch. It can be seen that the
tion, isolated from the system. Fig. 7 shows the voltage vd system follows the imposed reference value with a settling
compared to the reference value, the control action uv and the time of 0.5 seconds, that meets the criteria of this application.
field voltage vf d . The simulation result evidences the correct
performance of the control system, as vd follows the imposed
referente with a settling time of 0.3 seconds.

B. ELC control
Fig. 8 shows the block diagram of the ELC control system.
A Ce (s) controller receives the error between the reference
frequency and the estimated frequency of the system, generat-
ing the ELC duty cycle, which regulates the MG frequency by
varying the consumed active power. Since a positive frequency
error (fref > fe ) implies a decrease in the active power
consumed by the ELC (and consequently a decrease in the
duty cycle), the controller must have negative gain. Likewise, Fig. 9. ELC Control Validation.
negative errors (fref < fe ) imply an increase in de . In this

Authorized licensed use limited to: UNIVERSIDAD POLITECNICA SALESIANA. Downloaded on May 02,2023 at 02:13:41 UTC from IEEE Xplore. Restrictions apply.
V. E XPERIMENTAL RESULTS Load 2 is disconnected. From the result, it can be seen that the
system is capable of maintaining the regulated voltage within
The results of the generation system are obtained in
the proper operating range according to the standard. From the
an experimental bench. The measurement signal acquisition
field voltage graph, it can be observed the excitation system’s
and processing of control signals is performed in a DSP
fast response to contain the voltage sags caused by the low PF
TMS320F28335. Fig. 10 shows the group of machines used
load. Likewise, the excitation system acts quickly to reduce the
on the bench. A 5 kVA, 380 V SG with 4 salient pole pairs,
field voltage during the load disconnection.
with a rated speed of 900 RPM, connected to three wires (no
The SG does not supply active power to the system while
neutral conductor available) is used. The GI used is a three-
the load power is less than the rated power of the SEIG. After
phase squirrel-cage rotor machine, 3.7 kW and 380 V. The GI
12 seconds, when the UC load exceeds 3.7 kW, the ELC is
is driven by an induction motor that provides constant power.
completely turned off and the SG starts to supply active power
The SG is driven by DC motor with regulated speed.
to the microgrid. Even when Load 2 is removed, at 18 seconds,
the ELC remains off, as the load power is still greater than
3.7 kW, so only the power delivered by the SG is reduced.
VI. C ONCLUSION
This work presented a microgrid formed by connecting two
generators, the SG and the SEIG, in parallel. The results
corroborate the concept of complementary operation between
the two generators, showing that the technologies can be
associated in order to obtain satisfactory results in terms of
reliability in generation systems.
The use of a SG static excitation system based on a Buck
converter powered by an external source was proposed and
validated since the system was able to maintain regulated
voltage amplitude against load variations from no-load to rated
power.
The results showed the correct performance of the ELC to
consume the SEIG surplus active power in order to control
bus frequency. When the load exceeds the SEIG limit, the
ELC is completely turned off and the SG’s primary mover
Fig. 10. Rotating machines used in the experimental bench.
takes control of the MG frequency. The correct coordination
between the two actuators controlling the same variable is the
The objective of the control system is to keep the voltage
result of an adequate control system.
amplitude within ±10% of the rated value of the RMS voltage,
Thus, the system complies with Brazilian National Electric
according to the brazilian National Electric Energy Agency
Energy Agency (ANEEL) standard both in steady-state and
(ANEEL) standards [19]. Dips or elevations that exceed this
transient conditions and, therefore, meets the objective of
range must last less than 3 seconds. In proposed microgrid,
providing electrical energy with quality and high reliability.
the voltage is controlled through vd , which is related to the
RMS value of the line voltages, as mentioned in Section III. ACKNOWLEDGMENT
Regarding frequency, the control system must keep the
This study was financed in part by the Coordenacção
frequency within the range of 59.9 Hz to 60.1 Hz. Variations
de Aperfeiçoamento de Pessoal de Nı́vel Superior - Brasil
above this range must be extinguished in less than 30 seconds,
(CAPES/PROEX) - Finance Code 001. The authors are grate-
as per [19].
ful to the National Institute of Technology and Develop-
To show the correct functioning of the system, a series of
ment in Distributed Generation (INCT-GD), CNPq process
load connections was made. Fig. 11 shows the behavior of the
n° 465640/2014-1, CAPES process n° 23038.000776/2017-54
system when the following loads are added over time:
and FAPERGS process n° 17/2551-0000517-1
• 6 seconds - Load 1: 1,6 kW, FP = 1;
• 9 seconds - Load 2: 2,2 kVA, FP = 0, 7 lagging; R EFERENCES
• 12 seconds - Load 3: 1, 9 kW, FP = 1; [1] ”IEEE Guide for Design, Operation, and Integration of Distributed
• 15 seconds - Load 4: 3 kVA, FP = 0, 99 lagging; Resource Island Systems with Electric Power Systems,” in IEEE Std
• 18 seconds - Load 2 disconnection. 1547.4, Jul. 2011.
[2] N. Hatziargyriou, H.Asano, R. Iravani, C. Marnay, ”MicroGrids,” Power
Fig. 11 shows the load power, the power supplied by the and Energy Magazine, IEEE, vol. 5, no. 4, pp. 78-94, Jul. 2007.
SG, the system frequency, the PCC voltage vd , the SG field [3] B. Singh, S. S. Murthy and S. Gupta, ”Analysis and design of
STATCOM-based voltage regulator for self-excited induction genera-
voltage and the ELC switch duty cycle. After the 15 second tors,” in IEEE Transactions on Energy Conversion, vol. 19, no. 4, pp.
instant, the system reaches 100% load, 8.7 kVA. In 18 seconds, 783-790, Dec. 2004.

Authorized licensed use limited to: UNIVERSIDAD POLITECNICA SALESIANA. Downloaded on May 02,2023 at 02:13:41 UTC from IEEE Xplore. Restrictions apply.
Fig. 11. Experimental result: system’s response to load variations.

[4] G. Dyanamina and S. K. Kakodia, ”SEIG voltage regulation with electric system,” in 2017 IEEE 8th International Symposium on Power
STATCOM Regulator using Fuzzy logic controller,” 2021 International Electronics for Distributed Generation Systems (PEDG), 2017.
Conference on Sustainable Energy and Future Electric Transportation [13] C. Marinescu et. al., ”Controlling a stand-alone power system,” in
(SEFET), pp. 1-6, 2021. International Symposium on Power Electronics, Electrical Drives, Au-
[5] Y. K. Chauhan, S. K. Jain, B. Singh, ”A prospective on voltage tomation and Motion (SPEEDAM 2006), p. 525–530, 2006.
regulation of self-excited induction generators for industry applications,” [14] R. El. Pivetta, I. L. Dal Forno, L. G. Scherer, R. F. Camargo, F.
IEEE Transactions on Industry Applications, v. 46, n. 2, p. 720–730, B. Grigoletto, ”Modelagem e Controle de um Sistema de Excitaçãoo
2010. Estático de Gerador Sı́ncrono Utilizando Conversor Buck,” in Simpósio
[6] K. Kamiev, A. Parviainen and J. Pyrhönen, ”Hybrid excitation syn- Nacional de Sistemas Elétricos (SBSE 2022), 2022.
chronous generators for small hydropower plants,” 2016 XXII Inter- [15] I. Boldea, ”Synchronous Generators”. CRC Press, 2016.
national Conference on Electrical Machines (ICEM), pp. 2529-2535, [16] K.-M. Choo, C.-Y. Won, ”Analysis of Model-Based Tuning Method
2016. of PID Controller for Excitation Systems Considering Measurement
Delay,” in Energies 2020, 13, 939, 2020.
[7] J. Knudsen, J. D. Bendtsen, P. Andersen, K. K. Madsen and C. H. [17] R. Cardoso, R. F. de Camargo, H. Pinheiro, H. A. Grundling, ”Kalman
Sterregaard, ”Supervisory Control Implementation on Diesel-Driven filter based synchronization methods,” in 37th IEEE Power Electronics
Generator Sets,” in IEEE Transactions on Industrial Electronics, vol. Specialists Conference, p. 1–7, 2006.
65, no. 12, pp. 9698-9705, Dec. 2018. [18] IEEE, ”IEEE Guide for Identification, Testing, and Evaluation of the
[8] J. K. Nøland, S. Nuzzo, A. Tessarolo, E. F. Alves, ”Excitation system Dynamic Performance of Excitation Control Systems,” in IEEE Std
technologies for wound-field synchronous machines: Survey of solutions 421.2, 2014.
and evolving trends,” IEEE Access, 2019. [19] ANEEL. ”Procedimentos de distribuição de energia elétrica no sistema
[9] S. J. Chapman, ”Electric Machinery Fundamentals”. New York: elétrico nacional - PRODIST - Módulo 8 - Qualidade de energia
McGraw-Hill, 2012. elétrica”. 2022.
[10] A. S. Magalhães, et. al. ”Repowering of a synchronous generation plant
by induction generator,” in 2015 CHILEAN Conference on Electrical,
Electronics Engineering, Information and Communication Technologies
(CHILECON), p. 667–672, 2015.
[11] W. E. Vanço, et al., ”A proposal of expansion and implementation in
isolated generation systems using self-excited induction generator with
synchronous generator,” IEEE Access, 2019.
[12] V. Z. Silva, J. J. Rezek, R. D. L. Corrêa, ”Analysis of synchronous
and induction generators in parallel operation mode in an isolated

Authorized licensed use limited to: UNIVERSIDAD POLITECNICA SALESIANA. Downloaded on May 02,2023 at 02:13:41 UTC from IEEE Xplore. Restrictions apply.

You might also like