You are on page 1of 1

 

TECHNICAL BULLETIN
July 26, 2018

CONTROL UNIT V1.6 UPDATE

OVERVIEW:
AFEX has identified a condition which can cause the Control Unit to present a beeping tone without displaying any 
errors. In Configuration and Test modes this condition will appear as a flashing silence light. The condition does not affect 
the functionality of the system. 

A programming solution for this condition has been implemented with Control Unit software version 1.6, which will begin 
shipping immediately. 

PREVENTING/CLEARING THE CONDITION (V1.5 OR EARLIER):


After your installation is completed and the Control Unit has been configured, disconnect and reconnect the Control Unit 
harness to reboot the Control Unit, which will prevent the condition from occurring. 

If you are servicing an existing installation that presents a beeping tone or flashing silence light without an error message, 
disconnect and reconnect the Control Unit harness to reboot the Control Unit and the condition will clear. If it does not 
clear, please contact our office at (919) 781‐6610 for further assistance. 

 
PAGE 1 OF 1