INSPECTION REPORT
Technical Procedure Referred :
TI - PT - E - 004
TI 030
Issue Nr : RP - E - 001 - 220101 Date: 01/01/2022 Page 1 / 5

Certification Body: "TECH-INSPECT" SH.P.K. Client:


Address: Rr. Shyqyri Brari Nd. 2/1 Address: KORCE
Quality Manager: Sention Zotaj Contact Person:
Mob: +355 672016333 Mob:
Email: sention.zotaj@techinspect.al VAT Number:

This report indicates :

EXPLOSIVE ATMOSPHERES
Electrical Installations Inspection
Intended for :

Ex d – Explosion Proof

This report consists in 5 pages

Date of Inspection Site Location :

01/01/2022 KORCE

Inspector: Technical Director

Brian Lazaj Franc Lami


OMI 16
"TECH-INSPECT" Sh.p.k
INSPECTION REPORT
Technical Procedure Referred :
TI - PT - E - 004
TI 030
Issue Nr : RP - E - 001 - 220101 Date: 01/01/2022 Page 2 / 5
Reference to :
IEC 60079-17:2013
IEC 60079-14:2013 Inspection Sheet

Apparatus Type :

Manufacturer :

Serial No :

Model No: :

IP Class :

Area Classification Equipment Certification

Classification Drawing: Protection Technique:

Zone: Gas:

Gas/Dust Group: Gas/Dust Group:

Temperature Class: Temperature Class:


Environmental Condition :
Certification Scheme:

Certificate Number:

Cable Entry Components(Glands/Reducers/Adapters)

Type Qty Manufacturer Model Certificate Number

Inspection Type Initial/Construction Periodic/Maintenance

Detailed Close Visual Continous


Inspection Level
OMI 16
"TECH-INSPECT" Sh.p.k
INSPECTION REPORT
Technical Procedure Referred :
TI - PT - E - 004
TI 030
Issue Nr : RP - E - 001 - 220101 Date: 01/01/2022 Page 3 / 5

A GENERAL (ALL EQUIPMENT) D C V Comments


Equipment is appropriatete to the EPL / Zone
A1 requirements of the location
A2 Equipment group is correct
Equipment temperature class is correct ( only for
A3
gas)
Degree of Protection (IP) of equipment is
A5 appropriate for the level of
protection/group/conductivity
A6 Equipment circuit identification is correct
A7 Equipment circuit identification is avaiable
Enclosure , glass parts and glass-to-metal sealing
A8 gaskets and/or compounds are satisfactory
There is no damage or unauthorised
A9 modifications

A10 There is no evidence of unauthorised modifications

Bolts,cable entry devices(direct and indirect)and


A11 blanking elements are of the correct type and are
complete and tight
A11.1 -physical check
A11.2 -visual check
A12 Threaded coverson on enclosures are of the
correct type, are tight and secured
A12.1 -physical check
A12.2 -visual check
Joint surfaces are clean and undamaged and
A13 gaskets , if any , are satisfactory and positioned
correctly
A14 Condition of enclosure gaskets is satisfactory
There is no evidence of ingress of water or dust in
A15 the enclosure in accordance with the IP rating
Dimensions of flanged joint gaps are:
' - within the limits in accordance with
manufacturer’s documentation
A16 '- within maximum values permitted by relevant
construction standard at time of installation or

Breathing operation is satisfactory– ( type “nR”


A24
only)
A25 Breathing and draining devices are satisfactory
EQUIPMENT SPECIFIC (LIGHTING)
A27 HID lamps are not indicating EOL effects
A28 Lamp type, rating, pin configuration and position
are correct
EQUIPMENT SPECIFIC (MOTORS)

Motor fans have sufficient clearance to the


A29 enclosure and/or covers, cooling systems are
X
undamaged, motor foundations have no
indentations or cracks
A30 The ventilation airflow is not impeded
Insulation resistance (IR) of the motor windings is
A31 satisfactory
OMI 16
"TECH-INSPECT" Sh.p.k
INSPECTION REPORT
Technical Procedure Referred :
TI - PT - E - 004
TI 030
Issue Nr : RP - E - 001 - 220101 Date: 01/01/2022 Page 4 / 5

B INSTALLATION - GENERAL D C V Comments


B1 Type of cable is appropriate
The cables are adequately supported is no obvious
B2 damage to cables
Sealing of trunking, ducts, pipes and/or conduits is
B3
satisfactory
B4 Stopping boxes and cable boxes are correctly
filled
B5 Integrity of conduit system and interface with
mixed system maintained

Earthing connections, including any supplementary


earthing bonding connections are satisfactory (for
B6 example connections are tight and conductor are X
of sufficient cross-section)

B6.1 -physical check


B6.1 -visual check

There is no evident damage or degradation


B7 that indicates that the fault loop impedance
(TN systems) or earthing resistance (IT
systems) is not satisfactory

B8 Automatic electrical protective devices are


set correctly (auto-reset not possible)
B9 Automatic electrical protective devices
operate within permitted limits
B10 Specific conditions of use (if applicable) are
complied with
B11 Cables not in use are correctly terminated
Obstructions adjacent to flameproof flanged
B12 joints are in accordance with IEC 60079-14
Variable voltage/frequency installation
B13 complies with documentation
INSTALLATION - HEATING SYSTEM
Temperature sensors function according to
B14 manufacturer's documents
Safety cut off devices function according to
B15 manufacturer's documents
B16 The setting of the safety cut off is sealed
B17 Reset of a heating system safety cut off X
possible with tool only
B18 Auto-reset is not possible
B19 Reset of a safety cut off under fault
conditions is prevented
B20 Safety cut off independent from control
system
Level switch is installed and correctly set, if
B21 required
Flow switch is installed and correctly set, if
B22 required

C ENVIRONMENT D C V Comments
Equipment is adequately protected against
C1 corrosion, weather, vibration and other
adverse factors
C2 No undue accumulation of dust and dirt
OMI 16
"TECH-INSPECT" Sh.p.k
INSPECTION REPORT
Technical Procedure Referred :
TI - PT - E - 004
TI 030
Issue Nr : RP - E - 001 - 220101 Date: 01/01/2022 Page 5 / 5

Device has been verified against the original design i.e.Datasheet or EX Register

Device certificate sited:


Special conditions (if applicable) complied with:

Device certificate sited:


Special conditions (if applicable) complied with:

Other certificates sited (list, if any)

Photo / Defects observed

Inspector Details
Name :

Company (Tech Inspect or


Contractor Company):

EX Competency Certificate No.:


Singanure Date