TEST REPORT

Client Read Foundation


Ref No Nil
Project Read Foundation School Jhunja
Test Compressive Strengths

Specimen Bricks

Testing Date 30/5/2023

Compressive
S.No Mark Area Breaking Load Strength

Mpa(Psi)

1 267 24530 334.6 13.6(1972)

2 267 24420 321.9 13.1(1899)

3 267 24080 316.1 13.1(1923)

Average 13.27()

Note: Results pertain to samples submitted only

Tested by Checked by Verified by


MIRPUR UNIVERSITY OF SCIENCE & TECHNOLOGY (MUST), MIRPUR
AZAD JAMMU & KASHMIR
Department of Civil Engineering
Ph & Fax: +92-5827-961047

Ref. No. Dated:

TEST REPORT

Client Read Foundation


Ref No Nil
Project Read Foundation School Jhunja
Test Compressive Strengths

Specimen Bricks

Testing Date 30/5/2023

Compressive
S.No Mark Area Breaking Load Strength

Mpa(Psi)

1 267 24530 334.6 13.6(1972)

2 267 24420 321.9 13.1(1899)

3 267 24080 316.1 13.1(1899)

Average 13.27(1923)

Note: Results pertain to samples submitted only

Tested by Checked by Verified by


MIRPUR UNIVERSITY OF SCIENCE & TECHNOLOGY (MUST), MIRPUR
AZAD JAMMU & KASHMIR
Department of Civil Engineering
Ph & Fax: +92-5827-961047

Ref. No. Dated:

TEST REPORT

Client Read Foundation


Ref No Nil
Project Read Foundation School Jhunja
Test Compressive Strengths

Specimen Bricks

Testing Date 30/5/2023

Compressive
S.No Mark Area Breaking Load Strength

Mpa(Psi)

1 S 24310 350.7 14.4(2088)

2 S 24420 330.2 13.5(1958)

3 s 24300 338.3 13.9(2016)

Average 13.93(2021)

Note: Results pertain to samples submitted only

Tested by Checked by Verified by


MIRPUR UNIVERSITY OF SCIENCE & TECHNOLOGY (MUST), MIRPUR
AZAD JAMMU & KASHMIR
Department of Civil Engineering
Ph & Fax: +92-5827-961047

Ref. No. Dated:

TEST REPORT

Client Read Foundation


Ref No Nil
Project Read Foundation Girls College Bhimber
Test Compressive Strengths

Specimen Bricks

Testing Date 30/5/2023

Compressive
S.No Mark Area Breaking Load Strength

Mpa(Psi)

1 S 23650 299.5 12.6(1827)

2 S 24640 295.1 12.0(1740)

3 S 24090 285.4 11.8(1711)

Average 112.13(1759)

Note: Results pertain to samples submitted only

Tested by Checked by Verified by


MIRPUR UNIVERSITY OF SCIENCE & TECHNOLOGY (MUST), MIRPUR
AZAD JAMMU & KASHMIR
Department of Civil Engineering
Ph & Fax: +92-5827-961047

Ref. No. Dated:

TEST REPORT

Client Read Foundation


Ref No Nil
Project Read Foundation School Jhunja
Test Compressive Strengths

Specimen Bricks

Testing Date 30/5/2023

Compressive
S.No Mark Area Breaking Load Strength

Mpa(Psi)

1 267 24530 334.6 13.6(1972)

2 267 24420 321.9 13.1(1899)

3 267 24080 316.1 13.1(1923)

Average 13.27()

Note: Results pertain to samples submitted only

Tested by Checked by Verified by


MIRPUR UNIVERSITY OF SCIENCE & TECHNOLOGY (MUST), MIRPUR
AZAD JAMMU & KASHMIR
Department of Civil Engineering
Ph & Fax: +92-5827-961047

Ref. No. Dated:

TEST REPORT

Client Read Foundation


Ref No Nil
Project Read Foundation Girls College Bhimber
Test Compressive Strengths

Specimen Bricks

Testing Date 30/5/2023

Compressive
S.No Mark Area Breaking Load Strength

Mpa(Psi)

1 A 22890 250 10.9(1580.5)

2 A 23000 248.3 10.7(1552)

3 A 22900 245.2 10.7(1552)

Average 10.76(1562)

Note: Results pertain to samples submitted only

Tested by Checked by Verified by


MIRPUR UNIVERSITY OF SCIENCE & TECHNOLOGY (MUST), MIRPUR
AZAD JAMMU & KASHMIR
Department of Civil Engineering
Ph & Fax: +92-5827-961047

Ref. No. Dated:

TEST REPORT

Client Read Foundation


Ref No Nil
Project Read Foundation School Chaur Chak Gujrat
Test Compressive Strengths

Specimen Bricks

Testing Date 30/5/2023

Compressive
S.No Mark Area Breaking Load Strength

Mpa(Psi)

1 CH 23760 234.3 9.8(1421)

2 CH 23970 240.2 10(1450)

3 CH 22880 251.5 10.9(1580)

Average 10.23(1483.7)

Note: Results pertain to samples submitted only

Tested by Checked by Verified by


MIRPUR UNIVERSITY OF SCIENCE & TECHNOLOGY (MUST), MIRPUR
AZAD JAMMU & KASHMIR
Department of Civil Engineering
Ph & Fax: +92-5827-961047

Ref. No. Dated:

TEST REPORT

Client Read Foundation


Ref No Nil
Project Read Foundation School Dobay
Test Compressive Strengths

Specimen Bricks

Testing Date 30/5/2023

Compressive
S.No Mark Area Breaking Load Strength

Mpa(Psi)

1 CH 24530 254.8 10.3(1493)

2 CH 24750 250.1 10.1(1464)

3 CH 24200 243.9 10.0(1450)

Average 10.13(1469)

Note: Results pertain to samples submitted only

Tested by Checked by Verified by


MIRPUR UNIVERSITY OF SCIENCE & TECHNOLOGY (MUST), MIRPUR
AZAD JAMMU & KASHMIR
Department of Civil Engineering
Ph & Fax: +92-5827-961047

Ref. No. Dated:

TEST REPORT

Client Read Foundation


Ref No Nil
Project Read Foundation Girls College Bhimber
Test Compressive Strengths

Specimen Bricks

Testing Date 30/5/2023

Compressive
S.No Mark Area Breaking Load Strength

Mpa(Psi)

1 CH 23650 253.1 10.7(1551)

2 CH 23870 245.4 10.2(1479)

3 CH 23650 249.2 10.5(1522)

Average 10.46(1517)

Note: Results pertain to samples submitted only

Tested by Checked by Verified by


MIRPUR UNIVERSITY OF SCIENCE & TECHNOLOGY (MUST), MIRPUR
AZAD JAMMU & KASHMIR
Department of Civil Engineering
Ph & Fax: +92-5827-961047

Ref. No. Dated:

TEST REPORT

Client Read Foundation


Ref No Nil
Project Read Foundation School Dheri Sahabzadian Kotli
Test Compressive Strengths

Specimen Bricks

Testing Date 30/5/2023

Compressive
S.No Mark Area Breaking Load Strength

Mpa(Psi)

1 CH 23540 262.5 11.1(1609)

2 CH 23760 255.8 10.7(1551)

3 CH 24200 260.2 10.7(1551)

Average 10.83(1570)

Note: Results pertain to samples submitted only

Tested by Checked by Verified by


MIRPUR UNIVERSITY OF SCIENCE & TECHNOLOGY (MUST), MIRPUR
AZAD JAMMU & KASHMIR
Department of Civil Engineering
Ph & Fax: +92-5827-961047

Ref. No. Dated:

TEST REPORT

Client Read Foundation


Ref No Nil
Project Read Foundation School Dheri Sahabzadian Kotli
Test Compressive Strengths

Specimen Bricks

Testing Date 30/5/2023

Compressive
S.No Mark Area Breaking Load Strength

Mpa(Psi)

1 CH 23540 262.5 11.1(1609)

2 CH 23760 255.8 10.7(1551)

3 CH 24200 260.2 10.7(1551)

Average 10.83(1570)

Note: Results pertain to samples submitted only

Tested by Checked by Verified by

MIRPUR UNIVERSITY OF SCIENCE & TECHNOLOGY (MUST), MIRPUR


AZAD JAMMU & KASHMIR
Department of Civil Engineering
Ph & Fax: +92-5827-961047

Ref. No. Dated:

TEST REPORT

Client Read Foundation


Ref No Nil
Project Read Foundation college Chadala
Test Compressive Strengths

Specimen Bricks

Testing Date 30/5/2023

Compressive
S.No Mark Area Breaking Load Strength

Mpa(Psi)

1 D1 22990 311.6 13.5(1958)

2 D1 21630 298.2 13.7(1987)

3 D1 22580 296.9 13.1(1899)

Average 13.43(1948)

Note: Results pertain to samples submitted only

Tested by Checked by Verified by