EO PURIFICATION UNIT

Cause and Effect Diagram


Petrochemical
TAPCO Industries Design & MARUN Petrochemical
Polar Refrigeration
PIDEC Doc. No.: VD-1233-330-DIG-001 Rev.: 01 Engineering Co. Company (MPC)
GmbH PROJ. NO. :1233 PROJ. NO. :1226

PROJECT REQ. NO. : 1233-DE-00-RE-REQ-330

ITEM NO. : 20-PK-9010

TOTAL Sheets : 12

General Comments: □ No Comment To Vendor


- Any priority & latency / delay□forComment
actuating an effects to be specified
as marked, manufacturing may proceed To Vendor
by a note. (e.g. Oil pumps may □ stop
Majorwith a time
Comment delay
as marked, after tripping
manufacturing is on hold forthe
the next rev
compressor, ...) To Vendor

- All interlocks related to brine□skid to be added to this document (eg.


Rejected, new document with the same rev. no. To Vendor
□ Used as for information To Vendor
Interlock for Auto start / stop of the standby oil & brine pumps, Pump
protection and etc.) Name :
Signature :
Req. No.: Seq. No.:

Date:
PIDEC review & comments does not absolve the vendor of the responsibility
for the correct design, manufacturing and operation of the equipment

DE EXT A

Eng. Phase Purpose Of Distribution (POD) Purpose Of Issue (POI)

01 29/04/22 Issued for Approval SvK IS IS SK

00 25/11/21 Issued for Approval SvK IS IS SK


Rev Date Description Prepared by Checked by Approved by Authorized by

This document with all its rights is the property of MPC and must be held in confidence. No disclosure,
reproduction or other use of the document in whole or parts is to be made without the prior consent of MPC
Sub-Vendor: Vendor: EO PURIFICATION UNIT EP Contractor: Owner/Purchaser:

Cause and Effect Diagram


Petrochemical
TAPCO Industries Design & MARUN Petrochemical
Polar Refrigeration Engineering Co. Company (PMC)
GmbH PROJ. NO. :1233
PIDEC Doc. No.: VD-1233-330-DIG-001 Rev.: 01 PROJ. NO. : 1226

Change Index During Formal Issues


Internal
Sheet First Second Third Fourth Fifth Sixth
Issue Reason of Latest Change
No. Issue Issue Issue Issue Issue Issue
Rev. 0A Rev.00 Rev.01 Rev.02 Rev.03 Rev.04 Rev.05
1 X X
2 X X
3 X X
4 X X
5 X X
6 X X
7 X X
8 X X
9 X X
10 X X
11 X X
12 X X

This document with all its rights is the property of MPC and must be held in confidence. No disclosure,
reproduction or other use of the document in whole or parts is to be made without the prior consent of MPC
Sub-Vendor: Vendor: EP Contractor: Owner/Purchaser:
EO PURIFICATION UNIT

Cause and Effect Diagram


Petrochemical
Polar Refrigeration TAPCO Industries MARUN Petrochemical
GmbH Design & Company (MPC)
PIDEC Doc. No.: VD-1233-330-DIG-001 Rev.: 01 Engineering Co. PROJ. NO. : 1226
PROJ. NO. : 1233

Index Page

Cause and Effect Diagram

1. Cause and Effect Diagram 4

This document with all its rights is the property of MPC and must be held in confidence. No disclosure,
reproduction or other use of the document in whole or parts is to be made without the prior consent of MPC
Vendor: EPCC Contractor: EO PURIFICATION UNIT Owner:

Cause and Effect Diagram

Job No.:19-016-OG-IRN Project No.: 1226 Doc. No.: VD-1233-330-DIG-001 Rev.: 01

IS-960101 (REFRIGERATION UNIT EMERGENCY STOP)


EFFECT NO.
NO. ACTUATED BY P&ID NO. NOTE CAUSE EFFECT ACTUATES ON P&ID NO. NOTE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 20-HS-96010 1 HAND SWITCH IN PLANT'S DCS X X X X X X X X X X X X X X X X X X X X X X 1 Compressor main motor OFF 20-PU-9010-CM-1A 1 3

2 2 Oil pump motor 1 OFF 20-PK-9010-PM-1A 1 3

3 3 Oil pump motor 2 OFF 20-PK-9010-PM-2A 1 3

4 4 Turn off oil heater 20-PK-9010-EH-1A 1

5 5 De-Energize Capacity Control Solenoid Valve SV-960101A.1 1

6 6 De-Energize Capacity Control Solenoid Valve SV-960101A.2 1

7 7 De-Energize Capacity Control Solenoid Valve SV-960101A.3 1


Tag No. to be recked & corrected (SDY-960101A);
8 the informed tag8no.De-Energize
is related toCapacity
solenoid Control
valve ofSolenoid Valve SV-960101A.4 1
cooling water supply to the condenser)
9 9 De-Energize By-Pass Solenoid Valve PY-960101A 1

10 10 Compressor main motor OFF 20-PU-9010-CM-1B 2 3

11 11 Oil pump motor 1 OFF 20-PK-9010-PM-1B 2 3

12 12 Oil pump motor 2 OFF 20-PK-9010-PM-2B 2 3

13 13 Turn off oil heater 20-PK-9010-EH-1B 2

14 14 De-Energize Capacity Control Solenoid Valve SV-960101B.1 2

15 15 De-Energize Capacity Control Solenoid Valve SV-960101B.2 2

16 16 De-Energize Capacity Control Solenoid Valve SV-960101B.3 2

17 Tag No. to be recked & correctedCapacity


17 De-Energize (SDY-960101B);
Control Solenoid Valve SV-960101B.4 2
the informed tag no. is related to solenoid valve of
cooling water supply to the condenser)
18 18 De-Energize By-Pass Solenoid Valve PY-960101B 2
Tag No. is not available
19 on the PIDs.
19 Close solenoid valve LY-960101-1 3 2

Hint to Instrument team:


20 20 Close solenoid valve LY-960102-1
Does it require any reset switch
3 2
to open the valve in case the
21 21 Brine Pump Motor OFF 20-PK-9010-PM-3A
interlock become healthy? 4 3

22 22 Brine Pump Motor OFF 20-PK-9010-PM-3B 4 3

23 23
Vendor to check if it is required to de-energize the SV-960102
(already has been considered according to the PID)
24 24

Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified. 2) ''Close'' means de-energize for these valves. 3) OFF means as long as the fault is existing, START is restircted.
Vendor: EPCC Contractor: EO PURIFICATION UNIT Owner:

Cause and Effect Diagram

Job No.:19-016-OG-IRN Project No.: 1226 Doc. No.: VD-1233-330-DIG-001 Rev.: 01

IS-960101A (COMPRESSOR SKID A EMERGENCY STOP)


EFFECT NO.
NO. ACTUATED BY P&ID NO. NOTE CAUSE EFFECT ACTUATES ON P&ID NO. NOTE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 HS-960141A 1 ESD Push Button stop compressor skid A X X X X X X X X X X X X 1 Compressor main motor OFF 20-PU-9010-CM-1A 1 2
To be shown in the PID also
2 PALL-960113 3 Too Low Suction Pressure X X X X X X X X X X X X 2 Oil pump motor 1 OFF 20-PK-9010-PM-1A 1 2

3 TALL-960129 3 Too Low Brine Temperature X X X X X X X X X X X X 3 Oil pump motor 2 OFF Notes are related to 20-PK-9010-PM-2A 1 2
causes not the effects

4 LAHH-960101 3 3 Too high level in 20-PK-9010-V-2 X X X X X X X X X X X X 4 Turn off oil heater 20-PK-9010-EH-1A 1 3

5 PAHH-960105A 1 3 Too High Discharge Pressure X X X X X X X X X X X X 5 De-Energize Capacity Control Solenoid Valve SV-960101A.1 1 3

6 PDAHH-960101A 1 3 Too High Oil Differential Pressure X X X X X X X X X X X X 6 De-Energize Capacity Control Solenoid Valve SV-960101A.2 1 3

7 PDALL-960101A 1 3 Too Low Oil Differential Pressure X X X X X X X X X X X X 7 De-Energize Capacity Control Solenoid Valve SV-960101A.3 1 3

8 VAHH-960101A 1 Too High Vibration on Compressor X X X X X X X X X X X X Tag No. to be recked & corrected
8 De-Energize (SDY-960101A);
Capacity Control Solenoid Valve SV-960101A.4 1
the informed tag no. is related to solenoid valve of
cooling water supply to the condenser)
9 VAHH-960102A 1 Too High Vibration on Compressor X X X X X X X X X X X X 9 De-Energize By-Pass Solenoid Valve PY-´960101A 1

10 GALL-960101A 1 Too Low Axial Distance of Rotor X X X X X X X X X X X X 10 De-Energize Solenoid Valve SV-960102 3

11 GAHH-960101A 1 Too High Axial Distance of Rotor X X X X X X X X X X X X 11

12 TAHH-960101A 1 Too high compressor bearing temperature X X X X X X X X X X X X 12

13 TAHH-960102A 1 Too high compressor bearing temperature X X X X X X X X X X X X 13

14 TAHH-960103A 1 Too high compressor bearing temperature X X X X X X X X X X X X 14

15 TAHH-960104A 1 Too high compressor bearing temperature X X X X X X X X X X X X 15

16 TAHH-960107A 1 Too high oil temperature to compressor X X X X X X X X X X X X 16

17 TAHH-960106A 1 Too high discharge temperature X X X X X X X X X X X X 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified. 2) OFF means as long as the fault is existing, START is restircted. 3) Voting 2oo3.
Vendor: EPCC Contractor: EO PURIFICATION UNIT Owner:

Cause and Effect Diagram

Job No.:19-016-OG-IRN Project No.: 1226 Doc. No.: VD-1233-330-DIG-001 Rev.: 01

IS-960101B (COMPRESSOR SKID B EMERGENCY STOP)


EFFECT NO.
NO. ACTUATED BY P&ID NO. NOTE CAUSE EFFECT ACTUATES ON P&ID NO. NOTE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 HS-960141B 2 ESD Push Button stop compressor skid A X X X X X X X X X X X X 1 Compressor main motor OFF 20-PU-9010-CM-1B 2 2

2 PALL-960113 3 Too Low Suction Pressure X X X X X X X X Refer


X Xto our
X Xcomments for skid A 2 Oil pump motor 1 OFF 20-PK-9010-PM-1B 2 2

3 TALL-960129 3 Too Low Brine Temperature X X X X X X X X X X X X 3 Oil pump motor 2 OFF 20-PK-9010-PM-2B 2 2

4 LAHH-960101 3 Too high level in 20-PK-9010-V-2 X X X X X X X X X X X X 4 Turn off oil heater 20-PK-9010-EH-1B 2 3

5 PAHH-960105B 2 Too High Discharge Pressure X X X X X X X X X X X X 5 De-Energize Capacity Control Solenoid Valve SV-960101B.1 2 3

6 PDAHH-960101B 2 Too High Oil Differential Pressure X X X X X X X X X X X X 6 De-Energize Capacity Control Solenoid Valve SV-960101B.2 2 3

7 PDALL-960101B 2 Too Low Oil Differential Pressure X X X X X X X X X X X X 7 De-Energize Capacity Control Solenoid Valve SV-960101B.3 2 3

8 VAHH-960101B 2 Too High Vibration on Compressor X X X X X X X X X X X X 8 De-Energize Capacity Control Solenoid Valve SV-960101B.4 2

9 VAHH-960102B 2 Too High Vibration on Compressor X X X X X X X X X X X X 9 De-Energize By-Pass Solenoid Valve PY-´960101B 2

10 GALL-960101B 2 Too Low Axial Distance of Rotor X X X X X X X X X X X X 10 De-Energize Solenoid Valve SV-960102 3

11 GAHH-960101B 2 Too High Axial Distance of Rotor X X X X X X X X X X X X 11

12 TAHH-960101B 2 Too high compressor bearing temperature X X X X X X X X X X X X 12

13 TAHH-960102B 2 Too high compressor bearing temperature X X X X X X X X X X X X 13

14 TAHH-960103B 2 Too high compressor bearing temperature X X X X X X X X X X X X 14

15 TAHH-960104B 2 Too high compressor bearing temperature X X X X X X X X X X X X 15

16 TAHH-960107B 2 Too high oil temperature to compressor X X X X X X X X X X X X 16

17 TAHH-960106B 2 Too high discharge temperature X X X X X X X X X X X X 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified. 2) OFF means as long as the fault is existing, START is restircted. 3) Voting 2oo3.
Vendor: EPCC Contractor: EO PURIFICATION UNIT Owner:

Cause and Effect Diagram

Job No.:19-016-OG-IRN Project No.: 1226 Doc. No.: VD-1233-330-DIG-001 Rev.: 01

I-960106A (OIL HEATER TURN ON)


EFFECT NO.
NO. ACTUATED BY P&ID NO. NOTE
Based on relevant PID, CAUSE EFFECT ACTUATES ON P&ID NO. NOTE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
following item to be considered
1 TAL-960101A 1 Low oil temperature X 1 Turn on oil heater 20-PK-9010-EH-1A 1

2HS-960149A 1 X 2

3 3

Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified.

I-960107A (OIL HEATER TURN OFF)


EFFECT NO.
NO. ACTUATED BY P&ID NO. NOTE CAUSE EFFECT ACTUATES ON P&ID NO. NOTE
Based on relevant PID, following 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
items to be considered
1 LAL-960101A 1 Low level in 20-PK-9010-V-1A X X X 1 Turn off oil heater 20-PK-9010-EH-1A 1

TAH-960101A
2 1 High temperature of oil heater X 2 Oil pump motor 1 OFF 20-PK-9010-PM-1A 1 2

3HS-960150A 1 X 3 Oil pump motor 2 OFF 20-PK-9010-PM-2A 1 2


Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified.

I-960106B (OIL HEATER TURN ON)


EFFECT NO.
NO. ACTUATED BY P&ID NO. NOTE CAUSE EFFECT ACTUATES ON P&ID NO. NOTE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 TAL-960101B 2 Low oil temperature X 1 Turn on oil heater 20-PK-9010-EH-1B 2


Refer to our comments for skid A
2 2

3 3

Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified.

I-960107B (OIL HEATER TURN OFF)

EFFECT NO.
NO. ACTUATED BY P&ID NO. NOTE CAUSE EFFECT ACTUATES ON P&ID NO. NOTE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 LAL-960101B 2 Low level in 20-PK-9010-V-1B X X X 1 Turn off oil heater 20-PK-9010-EH-1B 2


Refer to our comments for skid A
2 2 Oil pump motor 1 OFF 20-PK-9010-PM-1B 2 2

3 3 Oil pump motor 2 OFF 20-PK-9010-PM-2B 2 2

Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified. 2) OFF means as long as the fault is existing, START is restircted.
Vendor: EPCC Contractor: EO PURIFICATION UNIT Owner:

Cause and Effect Diagram

Job No.:19-016-OG-IRN Project No.: 1226 Doc. No.: VD-1233-330-DIG-001 Rev.: 01

I-960109A (COMPRESSOR SKID A CAPACITY INCREASE)


EFFECT NO.
NO. ACTUATED BY P&ID NO. NOTE CAUSE EFFECT ACTUATES ON P&ID NO. NOTE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 TAH-960129 3 High Brine Temperature X X X X 1 Energize Capacity Control Solenoid Valve SV-960101A.1 1

2PAH-960113
PAH-960106 3 High suction pressure X X X X 2 De-Energize Capacity Control Solenoid Valve SV-960101A.2 1

Push Button to increase compressor skid A


3 HS-960142A 1 X X X X 3 De-Energize Capacity Control Solenoid Valve SV-960101A.3 1
capacity

4 4 Energize Capacity Control Solenoid Valve SV-960101A.4 1

Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified.

I-960110A (COMPRESSOR SKID A CAPACITY DECREASE)


EFFECT NO.
NO. ACTUATED BY P&ID NO. NOTE CAUSE EFFECT ACTUATES ON P&ID NO. NOTE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 TAL-960129 3 Low Brine Temperature X X X X 1 De-Energize Capacity Control Solenoid Valve SV-960101A.1 1

2PAH-960113
PAL-960106 3 Low suction pressure X X X X 2 Energize Capacity Control Solenoid Valve SV-960101A.2 1

Push Button to decrease compressor skid A


3 HS-960143A 1 X X X X 3 Energize Capacity Control Solenoid Valve SV-960101A.3 1
capacity

4 4 De-Energize Capacity Control Solenoid Valve SV-960101A.4 1

Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified.

I-960109B (COMPRESSOR SKID B CAPACITY INCREASE)


EFFECT NO.
NO. ACTUATED BY P&ID NO. NOTE CAUSE EFFECT ACTUATES ON P&ID NO. NOTE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 TAH-960129 3 High Brine Temperature X X X X 1 Energize Capacity Control Solenoid Valve SV-960101B.1 2

PAH-960113
2 PAH-960106 3 High suction pressure X X X X 2 De-Energize Capacity Control Solenoid Valve SV-960101B.2 2

Push Button to increase compressor skid B


3 HS-960142B 2 X X X X 3 De-Energize Capacity Control Solenoid Valve SV-960101B.3 2
capacity

4 4 Energize Capacity Control Solenoid Valve SV-960101B.4 2


Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified.

I-960110B (COMPRESSOR SKID B CAPACITY DECREASE)


EFFECT NO.
NO. ACTUATED BY P&ID NO. NOTE CAUSE EFFECT ACTUATES ON P&ID NO. NOTE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 TAL-960129 3 Low Brine Temperature X X X X 1 De-Energize Capacity Control Solenoid Valve SV-960101B.1 2

2PAH-960113
PAL-960106 3 Low suction pressure X X X X 2 Energize Capacity Control Solenoid Valve SV-960101B.2 2

Push Button to decrease compressor skid B


3 HS-960143B 2 X X X X 3 Energize Capacity Control Solenoid Valve SV-960101B.3 2
capacity

4 4 De-Energize Capacity Control Solenoid Valve SV-960101B.4 2

Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified.
Vendor: EPCC Contractor: EO PURIFICATION UNIT Owner:

Cause and Effect Diagram

Job No.:19-016-OG-IRN Project No.: 1226 Doc. No.: VD-1233-330-DIG-001 Rev.: 01

I-960111A (COMPRESSOR SKID A NORMAL STOP)


EFFECT NO.
NO. ACTUATED BY P&ID NO. NOTE CAUSE EFFECT ACTUATES ON P&ID NO. NOTE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 HSL-960140A 1 Push Button to stop compressor skid A X X X X X X X X X 1 Stop compressor motor 20-PU-9010-CM-1A 1

2 2 Stop main oil pump motor 20-PK-9010-PM-1A 1

3 3 Stop main oil pump motor 20-PK-9010-PM-2A 1

4 4 Energized oil heater 20-PK-9010-EH-1A 1 3

5 5 De-Energize Capacity Control Solenoid Valve SV-960101A.1 1

6 6 Energize Capacity Control Solenoid Valve SV-960101A.2 1

7 7 Energize Capacity Control Solenoid Valve SV-960101A.3 1


Tag No. to be recked & corrected (SDY-960101A);
8 the informed tag8 no.De-Energize
is related to Capacity
solenoid Control
valve ofSolenoid Valve SV-960101A.4 1
cooling water supply to the condenser)
9 9 De-Energize By-Pass Solenoid Valve PY-´960101A 1

10 10
Vendor to check if it is required to de-energize the SV-960102
(already has been considered according to the PID)
11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified. 2) ''Close'' means de-energize, ''open'' means energize for these valves. 3) Effect 4: the heater will be energized, i.e. power supply to heater will be
enabled. However, the heater will only be turn ON when the oil temperature becomes lower than the set value of thermostat TSL-960101A.
Vendor: EPCC Contractor: EO PURIFICATION UNIT Owner:

Cause and Effect Diagram

Job No.:19-016-OG-IRN Project No.: 1226 Doc. No.: VD-1233-330-DIG-001 Rev.: 01

I-960111B (COMPRESSOR SKID B NORMAL STOP)


Refer to our comments for skid A
EFFECT NO.
NO. ACTUATED BY P&ID NO. NOTE CAUSE EFFECT ACTUATES ON P&ID NO. NOTE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 HSL-960140B 2 Push Bottun to stop compressor skid B X X X X 1 Stop compressor motor 20-PU-9010-CM-1B 2

2 2 Stop main oil pump motor 20-PK-9010-PM-1B 2

3 3 Stop main oil pump motor 20-PK-9010-PM-2B 2

4 4 Energized oil heater 20-PK-9010-EH-1B 2 3

5 5 De-Energize Capacity Control Solenoid Valve SV-960101B.1 1

6 6 Energize Capacity Control Solenoid Valve SV-960101B.2 1

7 7 Energize Capacity Control Solenoid Valve SV-960101B:3 1

8 8 De-Energize Capacity Control Solenoid Valve SV-960101B.4 1

De-Energize By-Pass Solenoid Valve PY-´960101B 1


9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified. 2) ''Close'' means de-energize, ''open'' means energize for these valves. 3) Effect 4: the heater will be energized, i.e. power supply to heater will be
enabled. However, the heater will only be turn ON when the oil temperature becomes lower than the set value of thermostat TSL-960101B.
Vendor: EPCC Contractor: EO PURIFICATION UNIT Owner:

Cause and Effect Diagram

Job No.:19-016-OG-IRN Project No.: 1226 Doc. No.: VD-1233-330-DIG-001 Rev.: 01

I-960113A (COMPRESSOR SKID A NORMAL / AUTO START)


EFFECT NO.
NO. ACTUATED BY P&ID NO. NOTE CAUSE EFFECT ACTUATES ON P&ID NO. NOTE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 TAH-960129 3 High Brine Circuit Temperature X X X X X X X X X 1 Start compressor motor 20-PU-9010-CM-1A 1

PAH-960113
2 PAH-960106 3 High suction pressure X X X X X X X X X 2 Start main oil pump motor 20-PK-9010-PM-1A 1

3 HSH-960139A 1 Push Botton LCP to start compressor skid A X X X X X X X X X 3 Start main oil pump motor 20-PK-9010-PM-2A 1 4

4 4 Energized oil heater 20-PK-9010-EH-1A 1 3

5 5 Energize Capacity Control Solenoid Valve SV-960101A.1 1

6 6 De-Energize Capacity Control Solenoid Valve SV-960101A.2 1

7 7 De-Energize Capacity Control Solenoid Valve SV-960101A.3 1


Tag No. to be recked & corrected (SDY-960101A);
8 the informed tag 8 Energize
no. is related Capacity Control
to solenoid valve Solenoid
of Valve SV-960101A.4 1
cooling water supply to the condenser)
9 9 Energize By-Pass Solenoid Valve PY-´960101A 1

10 10
Vendor to check if it is required to energize the SV-960102
11 (already has been considered according to the PID) 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified. 2) ''Close'' means de-energize, "open" means energize for these valves. 3) Effect 4: the heater will be energized, i.e. power supply to heater
will be enabled. However, the heater will only be turn ON if the oil temperature is lower than the set value of thermostat TSL-960101A. While the heater is ON, start of compressor is not allowed. 4) 20-PK-9010-PM-1A is not in operation.
Vendor: EPCC Contractor: EO PURIFICATION UNIT Owner:

Cause and Effect Diagram

Job No.:19-016-OG-IRN Project No.: 1226 Doc. No.: VD-1233-330-DIG-001 Rev.: 01

I-960113B (COMPRESSOR SKID B NORMAL / AUTO START)


Refer to our comments for skid A
EFFECT NO.
NO. ACTUATED BY P&ID NO. NOTE CAUSE EFFECT ACTUATES ON P&ID NO. NOTE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 TAH-960129 3 High Brine Circuit Temperature X X X X 1 Start compressor motor 20-PU-9010-CM-1B 2

2 PAH-960106 3 High suction pressure X X X X 2 Start main oil pump motor 20-PK-9010-PM-1B 2

3 HSH-960139B 2 Push Botton LCP to start compressor skid B X X X X 3 Start main oil pump motor 20-PK-9010-PM-2B 2 4

4 4 Energized oil heater 20-PK-9010-EH-1B 2 3

5 5 Energize Capacity Control Solenoid Valve SV-960101B.1 1

6 6 De-Energize Capacity Control Solenoid Valve SV-960101B.2 1

7 7 De-Energize Capacity Control Solenoid Valve SV-960101B.3 1

8 8 Energize Capacity Control Solenoid Valve SV-960101B.4 1

Energize By-Pass Solenoid Valve PY-´960101B 1


9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified. 2) ''Close'' means de-energize, "open" means energize for these valves. 3) Effect 4: the heater will be energized, i.e. power supply to heater
will be enabled. However, the heater will only be turn ON if the oil temperature is lower than the set value of thermostat TSL-960101B. While the heater is ON, start of compressor is not allowed. 4) 20-PK-9010-PM-1B is not in operation.