EO PURIFICATION UNIT
TOTAL Sheets : 12
Date:
PIDEC review & comments does not absolve the vendor of the responsibility
for the correct design, manufacturing and operation of the equipment
DE EXT A
This document with all its rights is the property of MPC and must be held in confidence. No disclosure,
reproduction or other use of the document in whole or parts is to be made without the prior consent of MPC
Sub-Vendor: Vendor: EO PURIFICATION UNIT EP Contractor: Owner/Purchaser:
This document with all its rights is the property of MPC and must be held in confidence. No disclosure,
reproduction or other use of the document in whole or parts is to be made without the prior consent of MPC
Sub-Vendor: Vendor: EP Contractor: Owner/Purchaser:
EO PURIFICATION UNIT
Index Page
This document with all its rights is the property of MPC and must be held in confidence. No disclosure,
reproduction or other use of the document in whole or parts is to be made without the prior consent of MPC
Vendor: EPCC Contractor: EO PURIFICATION UNIT Owner:
1 20-HS-96010 1 HAND SWITCH IN PLANT'S DCS X X X X X X X X X X X X X X X X X X X X X X 1 Compressor main motor OFF 20-PU-9010-CM-1A 1 3
23 23
Vendor to check if it is required to de-energize the SV-960102
(already has been considered according to the PID)
24 24
Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified. 2) ''Close'' means de-energize for these valves. 3) OFF means as long as the fault is existing, START is restircted.
Vendor: EPCC Contractor: EO PURIFICATION UNIT Owner:
1 HS-960141A 1 ESD Push Button stop compressor skid A X X X X X X X X X X X X 1 Compressor main motor OFF 20-PU-9010-CM-1A 1 2
To be shown in the PID also
2 PALL-960113 3 Too Low Suction Pressure X X X X X X X X X X X X 2 Oil pump motor 1 OFF 20-PK-9010-PM-1A 1 2
3 TALL-960129 3 Too Low Brine Temperature X X X X X X X X X X X X 3 Oil pump motor 2 OFF Notes are related to 20-PK-9010-PM-2A 1 2
causes not the effects
4 LAHH-960101 3 3 Too high level in 20-PK-9010-V-2 X X X X X X X X X X X X 4 Turn off oil heater 20-PK-9010-EH-1A 1 3
5 PAHH-960105A 1 3 Too High Discharge Pressure X X X X X X X X X X X X 5 De-Energize Capacity Control Solenoid Valve SV-960101A.1 1 3
6 PDAHH-960101A 1 3 Too High Oil Differential Pressure X X X X X X X X X X X X 6 De-Energize Capacity Control Solenoid Valve SV-960101A.2 1 3
7 PDALL-960101A 1 3 Too Low Oil Differential Pressure X X X X X X X X X X X X 7 De-Energize Capacity Control Solenoid Valve SV-960101A.3 1 3
8 VAHH-960101A 1 Too High Vibration on Compressor X X X X X X X X X X X X Tag No. to be recked & corrected
8 De-Energize (SDY-960101A);
Capacity Control Solenoid Valve SV-960101A.4 1
the informed tag no. is related to solenoid valve of
cooling water supply to the condenser)
9 VAHH-960102A 1 Too High Vibration on Compressor X X X X X X X X X X X X 9 De-Energize By-Pass Solenoid Valve PY-´960101A 1
10 GALL-960101A 1 Too Low Axial Distance of Rotor X X X X X X X X X X X X 10 De-Energize Solenoid Valve SV-960102 3
18 18
19 19
20 20
21 21
22 22
23 23
24 24
Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified. 2) OFF means as long as the fault is existing, START is restircted. 3) Voting 2oo3.
Vendor: EPCC Contractor: EO PURIFICATION UNIT Owner:
1 HS-960141B 2 ESD Push Button stop compressor skid A X X X X X X X X X X X X 1 Compressor main motor OFF 20-PU-9010-CM-1B 2 2
3 TALL-960129 3 Too Low Brine Temperature X X X X X X X X X X X X 3 Oil pump motor 2 OFF 20-PK-9010-PM-2B 2 2
4 LAHH-960101 3 Too high level in 20-PK-9010-V-2 X X X X X X X X X X X X 4 Turn off oil heater 20-PK-9010-EH-1B 2 3
5 PAHH-960105B 2 Too High Discharge Pressure X X X X X X X X X X X X 5 De-Energize Capacity Control Solenoid Valve SV-960101B.1 2 3
6 PDAHH-960101B 2 Too High Oil Differential Pressure X X X X X X X X X X X X 6 De-Energize Capacity Control Solenoid Valve SV-960101B.2 2 3
7 PDALL-960101B 2 Too Low Oil Differential Pressure X X X X X X X X X X X X 7 De-Energize Capacity Control Solenoid Valve SV-960101B.3 2 3
8 VAHH-960101B 2 Too High Vibration on Compressor X X X X X X X X X X X X 8 De-Energize Capacity Control Solenoid Valve SV-960101B.4 2
9 VAHH-960102B 2 Too High Vibration on Compressor X X X X X X X X X X X X 9 De-Energize By-Pass Solenoid Valve PY-´960101B 2
10 GALL-960101B 2 Too Low Axial Distance of Rotor X X X X X X X X X X X X 10 De-Energize Solenoid Valve SV-960102 3
18 18
19 19
20 20
21 21
22 22
23 23
24 24
Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified. 2) OFF means as long as the fault is existing, START is restircted. 3) Voting 2oo3.
Vendor: EPCC Contractor: EO PURIFICATION UNIT Owner:
2HS-960149A 1 X 2
3 3
Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified.
TAH-960101A
2 1 High temperature of oil heater X 2 Oil pump motor 1 OFF 20-PK-9010-PM-1A 1 2
3 3
Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified.
EFFECT NO.
NO. ACTUATED BY P&ID NO. NOTE CAUSE EFFECT ACTUATES ON P&ID NO. NOTE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified. 2) OFF means as long as the fault is existing, START is restircted.
Vendor: EPCC Contractor: EO PURIFICATION UNIT Owner:
1 TAH-960129 3 High Brine Temperature X X X X 1 Energize Capacity Control Solenoid Valve SV-960101A.1 1
2PAH-960113
PAH-960106 3 High suction pressure X X X X 2 De-Energize Capacity Control Solenoid Valve SV-960101A.2 1
Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified.
1 TAL-960129 3 Low Brine Temperature X X X X 1 De-Energize Capacity Control Solenoid Valve SV-960101A.1 1
2PAH-960113
PAL-960106 3 Low suction pressure X X X X 2 Energize Capacity Control Solenoid Valve SV-960101A.2 1
Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified.
1 TAH-960129 3 High Brine Temperature X X X X 1 Energize Capacity Control Solenoid Valve SV-960101B.1 2
PAH-960113
2 PAH-960106 3 High suction pressure X X X X 2 De-Energize Capacity Control Solenoid Valve SV-960101B.2 2
1 TAL-960129 3 Low Brine Temperature X X X X 1 De-Energize Capacity Control Solenoid Valve SV-960101B.1 2
2PAH-960113
PAL-960106 3 Low suction pressure X X X X 2 Energize Capacity Control Solenoid Valve SV-960101B.2 2
Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified.
Vendor: EPCC Contractor: EO PURIFICATION UNIT Owner:
1 HSL-960140A 1 Push Button to stop compressor skid A X X X X X X X X X 1 Stop compressor motor 20-PU-9010-CM-1A 1
10 10
Vendor to check if it is required to de-energize the SV-960102
(already has been considered according to the PID)
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified. 2) ''Close'' means de-energize, ''open'' means energize for these valves. 3) Effect 4: the heater will be energized, i.e. power supply to heater will be
enabled. However, the heater will only be turn ON when the oil temperature becomes lower than the set value of thermostat TSL-960101A.
Vendor: EPCC Contractor: EO PURIFICATION UNIT Owner:
1 HSL-960140B 2 Push Bottun to stop compressor skid B X X X X 1 Stop compressor motor 20-PU-9010-CM-1B 2
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified. 2) ''Close'' means de-energize, ''open'' means energize for these valves. 3) Effect 4: the heater will be energized, i.e. power supply to heater will be
enabled. However, the heater will only be turn ON when the oil temperature becomes lower than the set value of thermostat TSL-960101B.
Vendor: EPCC Contractor: EO PURIFICATION UNIT Owner:
PAH-960113
2 PAH-960106 3 High suction pressure X X X X X X X X X 2 Start main oil pump motor 20-PK-9010-PM-1A 1
3 HSH-960139A 1 Push Botton LCP to start compressor skid A X X X X X X X X X 3 Start main oil pump motor 20-PK-9010-PM-2A 1 4
10 10
Vendor to check if it is required to energize the SV-960102
11 (already has been considered according to the PID) 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified. 2) ''Close'' means de-energize, "open" means energize for these valves. 3) Effect 4: the heater will be energized, i.e. power supply to heater
will be enabled. However, the heater will only be turn ON if the oil temperature is lower than the set value of thermostat TSL-960101A. While the heater is ON, start of compressor is not allowed. 4) 20-PK-9010-PM-1A is not in operation.
Vendor: EPCC Contractor: EO PURIFICATION UNIT Owner:
2 PAH-960106 3 High suction pressure X X X X 2 Start main oil pump motor 20-PK-9010-PM-1B 2
3 HSH-960139B 2 Push Botton LCP to start compressor skid B X X X X 3 Start main oil pump motor 20-PK-9010-PM-2B 2 4
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
Notes: 1) This document has a reference to latest revision of P&ID No. VD-1233-330-PID-001. In columns "P&ID No." the page number of this P&ID is specified. 2) ''Close'' means de-energize, "open" means energize for these valves. 3) Effect 4: the heater will be energized, i.e. power supply to heater
will be enabled. However, the heater will only be turn ON if the oil temperature is lower than the set value of thermostat TSL-960101B. While the heater is ON, start of compressor is not allowed. 4) 20-PK-9010-PM-1B is not in operation.