ABB REF 615

Example of a tripping logic with a downstream blocking signal combined with a pulse timer.

FUNCTION LIST
UPSTEAM_OC_BLOCKING
Blocking signal from the ABB615 downstream. It is an output signal that depends on the
overcurrent protection from the downstream relay.
PHLPTOC
Three-phase non directional overcurrent protection, low stage.

PHIPTOC
Three-phase non directional overcurrent protection, instantaneous stage.
EFIPTOC
Non-directional earth fault protection, instantaneous stage.
NSPTOC

Negative-sequence overcurrent protection.


T1PTTR1
Three-phase thermal protection for feeders, cables and distribution transformers.
ARCSARC
Arc protection

CBRCBRF1_TRRET
Circuit breaker failure protection function has two operating outputs:
TREET: operate output used for retripping its own breaker.
TRBU: output used to give a backup trip to the breaker feeding upstream.
PTGAPC

Pulse timer function block PTGAPC contains eight independent timers.


The function has a settable pulse length. Once the input is activated, the output is set for a
specific duration using the Pulse delay time setting.
PTGAPC
UPSTEAM_OC_BLOCKING IN1 Q1
IN2 Q2
IN3 Q3
IN4 Q4
IN5 Q5
IN6 Q6
IN7 Q7
IN8 Q8
TRPPTRC1
OR6 OR6 BLOCK TRIP TRPPTRC1_TRIP
PHLPTOC1_OPERATE B1 B1
PHIPTOC1_OPERATE B2 O B2 O OPERATE CL-LKOUT
EFIPTOC1_OPERATE B3 B3
RST_LKOUT
NSPTOC1_OPERATE B4 B4
T1PTTR1_OPERATE B5 B5
B6 B6
EXTERNAL_TRIP
OR6
ARCSARC1_OPERATE B1
ARCSARC2_OPERATE B2 O
CCBRBRF1_TRRET B3 TRIPPING LOGIC
B4
B5 ABB REF615
B6
REFERENCES
• “ABB Feeder Protection and Control REF615 – Application Manual”
• “ABB 615 Series – Technical Manual”