Equipment Data Sheet

CENTRIFUGAL PUMPS 1 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-021
Proposal Curve No Sheet 1 of 3
Item Description Firewater Diesel Engine Driven Pumps No. of Units 2 (Tag No. P2954 & P2955)

Revision A B
Issue IDC Implementation Issue
Date 3/14/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client

LIQUID Water
VISCOSITY cSt @ 5oC 1 S G @ 5oC 1 SP. HEAT (kJ/kg deg C) N/A
PROCESS
DATA

REID VAPOUR PRESSURE psia MIN NORMAL Negligible MAX


PUMPING TEMP. °C MIN + 10 NORMAL + 20 MAX + 30
H2S CONCENTRATION ppm MIN N/A NORMAL N/A MAX N/A
CHLORIDES ppm N/A CORROSIVE / EROSIVE AGENT N/A
LIQUIDS Type TOXIC FLAMMABLE OTHER N/A

CAPACITY (NOTE 1) m3/hr MIN 0 RATED 908 MAX 1362


MINIMUM CONTINUOUS FLOW THERMAL m3/hr
STABLE m3/hr
SUCTION PRESSURE BARG RATED -0.08 MAXIMUM +1.94
DISCHARGE PRESS. BARG 11.23 DIFFERENTIAL PRESS. BARG + 11.0
DIFFERENTIAL HEAD m 115.25 NPSH REQUIRED - RATED CAP m H2O STA
DRIVER

MAX HEAD-RATED IMPELLER m STA SUCTION SPECIFIC SPEED STA


MAX POWER-RATED IMPLLER. kW STA MAX SOUND PRESS. LEVEL 85 dBA
POWER REQUIRED kW STA SPEED rev/min STA ROTATION : NOTE 2
PUMPS TO OPERATE AS ENGINE - REQ'D FLUID COUPLING - N/A GEAR BOX N/A
DUTY AND STANDBY ENGINE BY Pump Supplierr FLUID COUPLING BY N/A
ENGINE MOUNTED BY Pump Supplierr FLUID COUPLING MOUNTED BY N/A
DATA SHEETS ENGINE N/A FLUID COUPLING N/A
IMPELLER CASING CASING SPLIT
TYPE CLOSED, RADIAL FLOW SINGLE VOLUTE AXIAL ü
DIAMETER mm STA DOUBLE VOLUTE RADIAL
BETWEEN BEARINGS Alternative VERTICAL DOUBLE CASING
OVERHUNG ü MOUNTNG CENTRELINE VERTICAL FOOT MOUNTING
NEAR CENTRELINE IN LINE SUMP PLATE
MECHANICAL SEALS BEARINGS SLEEVE ROLLER BALL
CONSTRUCTION

API SEAL CODE N/A RADIAL BEARINGS STA


TYPE Gland Packing THRUST BEARINGS STA
SupplierR STA LUBRICATION FORCED RING
COUPLING MAKE STA COUPLING GUARD YES NO
MODEL
RATING

CONNECTIONS (NOTE 2) SIZE ANSI FLANGE POSITION OTHER CONNECTIONS


RATING FACE NO. SIZE TYPE
SUCTION 16" 150 RAISED SIDE VENT STA Valved and

DISCHARGE 12" 150 RAISED SIDE DRAIN STA Flanged to

Edge of B'plate

INSTRUMENTATION (NOTE 3) PRESSURE GAUGE TYPE TEMPERATURE GAUGE TYPE


TEMP & PRESSURE LOCATION THERMOWELLS TYPE
PRESSURE SWITCH TYPE LOCATION(S)
LOCATION ACCELEROMETER
VIBRATION MOUNTING PROVISION ONLY MOUNTING ONLY NON CONTACT

9755-DAT-ME-021
Equipment Data Sheet
CENTRIFUGAL PUMPS 2 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-021
Proposal Curve No Sheet 2 of 3
Item Description Firewater Diesel Engine Driven Pumps No. of Units 2 (Tag No. P2954 & P2955)

Material Classification Supplierrs Std BEARING HOUSING STA


BARREL/CASING STA WEAR RINGS STA
MATERIALS

SHAFT STA SHAFT SLEEVE STA


IMPELLER STA BASE PLATE Fabricated Steel
DIFFUSERS GASKETS Non Asbestos

TYPE NOTE 4
SupplierR STA TYPE STA
DRIVER

DRIVER

REMARKS

VERTICAL PUMPS UP DOWN SEPARATE MOUNTING PLATE


PUMP THRUST N DRIVER ALIGNMENT SCREWS
AT MIN FLOW N PIT OR SUMP DEPTH m
AT DESIGN FLOW N PUMP LENGTH m
VERTICAL PUMPS

AT RUNOUT N MIN SUBMERGENCE REQD. m


MAX THRUST N COLUMN PIPE FLANGED THREADED
FLOW RATE m3/hr LINE SHAFT OPEN ENCLOSED
GUIDE BUSHINGS BOWL LINE SHAFT
GUIDE BUSHINGS LUBRICATION WATER OIL GREASE PUMPAGE

REMARKS

SURFACE PREPARATION AND PAINTING NOTE 5


SURFACE PREPARATION

PUMP ENGINE BASEPLATE OTHER


SupplierRS STANDARD
& PAINTING

SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS

WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT

WEIGHT OF ENGINE kg STA


REMARKS WEIGHT OF BASEPLATE kg STA

CODES AND STANDARDS


CODES AND STANDARDS

CASING IMPELLER SHAFT OTHER


MATL. CERTIFICATION REQ'D: ü ü ü
NOZZLE WELD INSPECTION. MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CASTING INSPECTION MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CHARPY TESTS REQUIRED ITEMS
APPLICABLE CODES
REMARKS

9755-DAT-ME-021
Equipment Data Sheet
CENTRIFUGAL PUMPS 3 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-021
Proposal Curve No Sheet 3 of 3
Item Description Firewater Diesel Engine Driven Pumps No. of Units 2 (Tag No. P2954 & P2955)

QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA

PERFORMANCE CURVE APPR. DATE COMMENTS

SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE

HYDROTEST ü
PERFORMANCE ü
NPSH ü
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST

TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER Engine operation and
control panel operation

VENDOR TO SUBMIT TEST DATE COMMENTS


PROCEDURES

ENVIRONMENTAL & SITE DATA


ENVIRONMENTAL & SITE DATA

LOCATION INDOOR OUTDOOR UNDER ROOF PARTIAL SIDES


GRADE MEZZANINE HEATED UNHEATED
WINTERISATION REQUIRED NO TROPICALISATION REQUIRED YES
ELECTRICAL AREA ZONE NOTE 4 GAS GROUP NOTE 4 TEMPERATURE CLASS NOTE 4
CLASSIFICATION

SITE DATA ELEVATION - 0 m ATMOSPHERE - Tropical


AMBIENT TEMPERATURE deg C MINIMUM 10 NORMAL 30 MAXIMUM 50
RELATIVE HUMIDITY % MINIMUM NORMAL MAXIMUM 100

Note 1 The pumps shown on this Data Sheet will be used as the main diesel engine driven pumps to supply a firewater system.
The maximum flow will be 150% of the rated flow in accordance with the requirements of NFPA 20. The pump shall be capable
of operating at zero flow for a period of 2 hours. The driver shall be rated accordingly.
Note 2 The rotation shall be to suit the application. The suction flange shall be on the right side and the discharge flange shall be
NOTES

on the left side when viewed from the driver end.


Note 3 In accordance with NFPA 20.
Note 4 In accordance with NFPA 20.
Note 5 Pumpsets to be prepared and painted in accordance with project specification 9755-SPC-CP-007.
Note 6 Tests on one pump of each type to be witnessed by the Purchaser.
Note 7 STA = Supplier to add details.
REMARKS

9755-DAT-ME-021
Equipment Data Sheet
CENTRIFUGAL PUMPS 1 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-020
Proposal Curve No Sheet 1 of 3
Item Description Firewater Electrically Driven Pump No. of Units 1 (Tag No. P2953)

Revision A B
Issue IDC Implementation Issue
Date 3/14/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client

LIQUID Water
VISCOSITY cSt @ 5oC 1 S G @ 5oC 1 SP. HEAT (kJ/kg deg C) N/A
PROCESS
DATA

REID VAPOUR PRESSURE psia MIN NORMAL Negligible MAX


PUMPING TEMP. °C MIN + 10 NORMAL + 20 MAX + 30
H2S CONCENTRATION ppm MIN N/A NORMAL N/A MAX N/A
CHLORIDES ppm N/A CORROSIVE / EROSIVE AGENT N/A
LIQUIDS Type TOXIC FLAMMABLE OTHER N/A

CAPACITY (NOTE 1) m3/hr MIN 0 RATED 908 MAX 1362


MINIMUM CONTINUOUS FLOW THERMAL m3/hr
STABLE m3/hr
SUCTION PRESSURE BARG RATED -0.08 MAXIMUM +1.94
DISCHARGE PRESS. BARG 11.23 DIFFERENTIAL PRESS. BARG 11.31
DIFFERENTIAL HEAD m 115.25 NPSH REQUIRED - RATED CAP m H2O STA
DRIVER

MAX HEAD-RATED IMPELLER m STA SUCTION SPECIFIC SPEED STA


MAX POWER-RATED IMPLLER. kW STA MAX SOUND PRESS. LEVEL 85 dBA
POWER REQUIRED kW STA SPEED rev/min STA ROTATION : NOTE 2
PUMPS TO OPERATE AS ELEC. MOTOR - REQ'D FLUID COUPLING - N/A GEAR BOX N/A
DUTY ONLY ELEC MOTOR BY Pump Supplier FLUID COUPLING BY N/A
MOTOR MOUNTED BY Pump Supplier FLUID COUPLING MOUNTED BY N/A
DATA SHEETS ELEC MOTOR 9755-DAT-EL-001 FLUID COUPLING N/A
IMPELLER CASING CASING SPLIT
TYPE CLOSED, RADIAL FLOW SINGLE VOLUTE AXIAL ü
DIAMETER mm STA DOUBLE VOLUTE RADIAL
BETWEEN BEARINGS Alternative VERTICAL DOUBLE CASING
OVERHUNG ü MOUNTNG CENTRELINE VERTICAL FOOT MOUNTING
NEAR CENTRELINE IN LINE SUMP PLATE
MECHANICAL SEALS BEARINGS SLEEVE ROLLER BALL
CONSTRUCTION

API SEAL CODE N/A RADIAL BEARINGS STA


TYPE Gland Packing THRUST BEARINGS STA
Supplier STA LUBRICATION FORCED RING
COUPLING MAKE STA COUPLING GUARD YES NO
MODEL
RATING

CONNECTIONS (NOTE 2) SIZE ANSI FLANGE POSITION OTHER CONNECTIONS


RATING FACE NO. SIZE TYPE
SUCTION 16" 150 RAISED SIDE VENT STA Valved and

DISCHARGE 12" 150 RAISED SIDE DRAIN STA Flanged to

Edge of B'plate

INSTRUMENTATION (NOTE 3) PRESSURE GAUGE TYPE TEMPERATURE GAUGE TYPE


TEMP & PRESSURE LOCATION THERMOWELLS TYPE
PRESSURE SWITCH TYPE LOCATION(S)
LOCATION ACCELEROMETER
VIBRATION MOUNTING PROVISION ONLY MOUNTING ONLY NON CONTACT

9755-DAT-ME-020
Equipment Data Sheet
CENTRIFUGAL PUMPS 2 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-020
Proposal Curve No Sheet 2 of 3
Item Description Firewater Electrically Driven Pump No. of Units 1 (Tag No. P2953)

Material Classification Suppliers Std BEARING HOUSING STA


BARREL/CASING STA WEAR RINGS STA
MATERIALS

SHAFT STA SHAFT SLEEVE STA


IMPELLER STA BASE PLATE Fabricated Steel
DIFFUSERS GASKETS Non Asbestos

TYPE NOTE 4
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 4 PHASE HERTZ ENCLOSURE NOTE 4
kW RATING STA VERTICAL HORIZONTAL
DRIVER

SPEED rev / min STA EFFICIENCY %


MINIMUM STARTING VOLTAGE INSULATION NOTE 4
DRIVER

FULL LOAD AMPS LOCKED ROTOR AMPS


STARTING METHOD TEMP. RISE deg C
BEARINGS STA LUBRICATION STA
VERTICAL SHAFT SOLID HOLLOW
VERTICAL THRUST UPWARD DOWNWARD
REMARKS

VERTICAL PUMPS UP DOWN SEPARATE MOUNTING PLATE


PUMP THRUST N DRIVER ALIGNMENT SCREWS
AT MIN FLOW N PIT OR SUMP DEPTH m
AT DESIGN FLOW N PUMP LENGTH m
VERTICAL PUMPS

AT RUNOUT N MIN SUBMERGENCE REQD. m


MAX THRUST N COLUMN PIPE FLANGED THREADED
FLOW RATE m3/hr LINE SHAFT OPEN ENCLOSED
GUIDE BUSHINGS BOWL LINE SHAFT
GUIDE BUSHINGS LUBRICATION WATER OIL GREASE PUMPAGE

REMARKS

SURFACE PREPARATION AND PAINTING NOTE 5


SURFACE PREPARATION

PUMP MOTOR BASE PLATE OTHER


SupplierS STANDARD
& PAINTING

SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS

WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT

WEIGHT OF MOTOR kg STA


REMARKS WEIGHT OF BASEPLATE kg STA

CODES AND STANDARDS


CODES AND STANDARDS

CASING IMPELLER SHAFT OTHER


MATL. CERTIFICATION REQ'D: ü ü ü
NOZZLE WELD INSPECTION. MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CASTING INSPECTION MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CHARPY TESTS REQUIRED ITEMS
APPLICABLE CODES
REMARKS

9755-DAT-ME-020
Equipment Data Sheet
CENTRIFUGAL PUMPS 3 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-020
Proposal Curve No Sheet 3 of 3
Item Description Firewater Electrically Driven Pump No. of Units 1 (Tag No. P2953)

QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA

PERFORMANCE CURVE APPR. DATE COMMENTS

SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE

HYDROTEST ü
PERFORMANCE ü
NPSH ü
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST

TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER

VENDOR TO SUBMIT TEST DATE COMMENTS


PROCEDURES

ENVIRONMENTAL & SITE DATA


ENVIRONMENTAL & SITE DATA

LOCATION INDOOR OUTDOOR UNDER ROOF PARTIAL SIDES


GRADE MEZZANINE HEATED UNHEATED
WINTERISATION REQUIRED NO TROPICALISATION REQUIRED YES
ELECTRICAL AREA ZONE NOTE 4 GAS GROUP NOTE 4 TEMPERATURE CLASS NOTE 4
CLASSIFICATION

SITE DATA ELEVATION - 0 m ATMOSPHERE - Tropical


AMBIENT TEMPERATURE deg C MINIMUM 10 NORMAL 30 MAXIMUM 50
RELATIVE HUMIDITY % MINIMUM NORMAL MAXIMUM 100

Note 1 The pump shown on this Data Sheet will be used as the electrically driven pump to supply a firewater system. The maximum flow
will be 150% of the rated flow in accordance with the requirements of NFPA 20. The pump shall be capable of operating
at zero flow for a period of 2 hours. The driver shall be rated accordingly.
Note 2 The rotation shall be to suit the application. The suction flange shall be on the right side and the discharge flange shall
NOTES

be on the left side when viewed from the driver end.


Note 3 In accordance with NFPA 20.
Note 4 See Data Sheet 9755-DAT-EL-001
Note 5 Pumpsets to be prepared and painted in accordance with project specification 9755-SPC-CP-007.
Note 6 Tests on one pump of each type to be witnessed by the Purchaser.
Note 7 STA = Supplier to add details.
REMARKS

9755-DAT-ME-020
Equipment Data Sheet
CENTRIFUGAL PUMPS 1 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-019
Proposal Curve No Sheet 1 of 3
Item Description Firewater Jockey Pump No. of Units 1 (Tag No. P2952)

Revision A B
Issue IDC Implementation Issue
Date 3/14/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client

LIQUID Water
VISCOSITY cSt @ 5oC 1 S G @ 5oC 1 SP. HEAT (kJ/kg deg C) N/A
PROCESS
DATA

REID VAPOUR PRESSURE psia MIN NORMAL Negligible MAX


PUMPING TEMP. °C MIN + 10 NORMAL + 20 MAX + 30
H2S CONCENTRATION ppm MIN N/A NORMAL N/A MAX N/A
CHLORIDES ppm N/A CORROSIVE / EROSIVE AGENT N/A
LIQUIDS Type TOXIC FLAMMABLE OTHER N/A

CAPACITY (NOTE 1) m3/hr MIN 0 RATED 15 MAX


MINIMUM CONTINUOUS FLOW THERMAL m3/hr
STABLE m3/hr
DESIGN

SUCTION PRESSURE BARG RATED +0.02 MAXIMUM +1.94


DISCHARGE PRESS. BARG 11.13 DIFFERENTIAL PRESS. BARG 11.11
DIFFERENTIAL HEAD m 113.20 NPSH REQUIRED - RATED CAP m H2O STA
MAX HEAD-RATED IMPELLER m STA SUCTION SPECIFIC SPEED STA
MAX POWER-RATED IMPLLER. kW STA MAX SOUND PRESS. LEVEL 85 dBA
POWER REQUIRED kW STA SPEED rev/min STA ROTATION : NOTE 2
PUMPS TO OPERATE AS ELEC. MOTOR - REQ'D FLUID COUPLING - N/A GEAR BOX N/A
DUTY ONLY ELEC MOTOR BY Pump Supplier FLUID COUPLING BY N/A
MOTOR MOUNTED BY Pump Supplier FLUID COUPLING MOUNTED BY N/A
DATA SHEETS ELEC MOTOR 9755-DAT-EL-002 FLUID COUPLING N/A
IMPELLER CASING CASING SPLIT
TYPE CLOSED, RADIAL FLOW SINGLE VOLUTE AXIAL ü
DIAMETER mm STA DOUBLE VOLUTE RADIAL
BETWEEN BEARINGS Alternative VERTICAL DOUBLE CASING
OVERHUNG ü MOUNTNG CENTRELINE VERTICAL FOOT MOUNTING
NEAR CENTRELINE IN LINE SUMP PLATE
MECHANICAL SEALS BEARINGS SLEEVE ROLLER BALL
CONSTRUCTION

API SEAL CODE N/A RADIAL BEARINGS STA


TYPE Gland Packing THRUST BEARINGS STA
Supplier STA LUBRICATION FORCED RING
COUPLING MAKE STA COUPLING GUARD YES NO
MODEL
RATING

CONNECTIONS (NOTE 2) SIZE ANSI FLANGE POSITION OTHER CONNECTIONS


RATING FACE NO. SIZE TYPE
SUCTION 2" (STA) 150 RAISED END VENT STA Valved and

DISCHARGE 1.5" (STA) 150 RAISED TOP DRAIN STA Flanged to

Edge of B'plate

INSTRUMENTATION (NOTE 3) PRESSURE GAUGE TYPE TEMPERATURE GAUGE TYPE


TEMP & PRESSURE LOCATION THERMOWELLS TYPE
PRESSURE SWITCH TYPE LOCATION(S)
LOCATION ACCELEROMETER
VIBRATION MOUNTING PROVISION ONLY MOUNTING ONLY NON CONTACT

9755-DAT-ME-019
Equipment Data Sheet
CENTRIFUGAL PUMPS 2 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-019
Proposal Curve No Sheet 2 of 3
Item Description Firewater Jockey Pump No. of Units 1 (Tag No. P2952)

Material Classification Suppliers Std BEARING HOUSING STA


BARREL/CASING STA WEAR RINGS STA
MATERIALS

SHAFT STA SHAFT SLEEVE STA


IMPELLER STA BASE PLATE Fabricated Steel
DIFFUSERS GASKETS Non Asbestos

TYPE NOTE 4
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 4 PHASE HERTZ ENCLOSURE NOTE 4
kW RATING STA VERTICAL HORIZONTAL
DRIVER

SPEED rev / min STA EFFICIENCY %


MINIMUM STARTING VOLTAGE INSULATION NOTE 4
DRIVER

FULL LOAD AMPS LOCKED ROTOR AMPS


STARTING METHOD TEMP. RISE deg C
BEARINGS STA LUBRICATION STA
VERTICAL SHAFT SOLID HOLLOW
VERTICAL THRUST UPWARD DOWNWARD
REMARKS

VERTICAL PUMPS UP DOWN SEPARATE MOUNTING PLATE


PUMP THRUST N DRIVER ALIGNMENT SCREWS
AT MIN FLOW N PIT OR SUMP DEPTH m
AT DESIGN FLOW N PUMP LENGTH m
VERTICAL PUMPS

AT RUNOUT N MIN SUBMERGENCE REQD. m


MAX THRUST N COLUMN PIPE FLANGED THREADED
FLOW RATE m3/hr LINE SHAFT OPEN ENCLOSED
GUIDE BUSHINGS BOWL LINE SHAFT
GUIDE BUSHINGS LUBRICATION WATER OIL GREASE PUMPAGE

REMARKS

SURFACE PREPARATION AND PAINTING NOTE 5


SURFACE PREPARATION

PUMP MOTOR BASE PLATE OTHER


SupplierS STANDARD
& PAINTING

SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS

WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT

WEIGHT OF MOTOR kg STA


REMARKS WEIGHT OF BASEPLATE kg STA

CODES AND STANDARDS


CODES AND STANDARDS

CASING IMPELLER SHAFT OTHER


MATL. CERTIFICATION REQ'D: ü ü ü
NOZZLE WELD INSPECTION. MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CASTING INSPECTION MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CHARPY TESTS REQUIRED ITEMS
APPLICABLE CODES
REMARKS

9755-DAT-ME-019
Equipment Data Sheet
CENTRIFUGAL PUMPS 3 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-019
Proposal Curve No Sheet 3 of 3
Item Description Firewater Jockey Pump No. of Units 1 (Tag No. P2952)

QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA

PERFORMANCE CURVE APPR. DATE COMMENTS

SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE

HYDROTEST ü
PERFORMANCE ü
NPSH ü
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST

TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER

VENDOR TO SUBMIT TEST DATE COMMENTS


PROCEDURES

ENVIRONMENTAL & SITE DATA


ENVIRONMENTAL & SITE DATA

LOCATION INDOOR OUTDOOR UNDER ROOF PARTIAL SIDES


GRADE MEZZANINE HEATED UNHEATED
WINTERISATION REQUIRED NO TROPICALISATION REQUIRED YES
ELECTRICAL AREA ZONE NOTE 4 GAS GROUP NOTE 4 TEMPERATURE CLASS NOTE 4
CLASSIFICATION

SITE DATA ELEVATION - 0 m ATMOSPHERE - Tropical


AMBIENT TEMPERATURE deg C MINIMUM 10 NORMAL 30 MAXIMUM 50
RELATIVE HUMIDITY % MINIMUM NORMAL MAXIMUM 100

Note 1 The pump shown on this Data Sheet will be used as a jockey pump to maintain the pressure in a wet fire hydrant system.
The pump flow will reduce to zero as the hydrant pressure builds up to its set pressure.
Note 2 The rotation shall be to suit the application. The suction flange shall be on the end and the discharge flange shall be on the top
when viewed from the driver end.
NOTES

Note 3 In accordance with NFPA 20.


Note 4 See Data Sheet 9755-DAT-EL-002
Note 5 Pumpsets to be prepared and painted in accordance with project specification 9755-SPC-CP-007.
Note 6 Tests on one pump of each type to be witnessed by the Purchaser.
Note 7 STA = Supplier to add details.

REMARKS

9755-DAT-ME-019
Equipment Data Sheet
ROTARY POSITIVE DISPLACEMENT PUMPS 1 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-018
Proposal Curve No Sheet 1 of 3
Item Description Recovered Fuel Transfer Pump (Road Offload Area) No. of Units 1 (Tag No. P3920)

Revision A B
Issue IDC Implementation Issue
Date 3/10/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client

LIQUID Jet A1
VISCOSITY cSt @ 5oC 2.2 S G @ 5oC 0.8 SP. HEAT (kJ/kg deg C) N/A
PROCESS
DATA

REID VAPOUR PRESSURE psia MIN NORMAL Negligible MAX


PUMPING TEMP. °C MIN + 10 NORMAL + 20 MAX + 30
H2S CONCENTRATION ppm MIN N/A NORMAL N/A MAX N/A
CHLORIDES ppm N/A CORROSIVE / EROSIVE AGENT N/A
LIQUIDS Type TOXIC ü FLAMMABLE ü OTHER N/A

CAPACITY (NOTE 1) m3/hr 10 NPSH REQUIRED - RATED CAP m H20 STA


SUCTION PRESSURE BARG +0 SUCTION SPECIFIC SPEED STA
DISCHARGE PRESS. BARG + 1.96 MAX SOUND PRESS. LEVEL dBA 85
DIFFERENTIAL PRESS BAR 1.96 DIFFERENTIAL HEAD m 25
DESIGN

POWER REQUIRED kW STA SPEED rev/min STA


PUMPS TO OPERATE AS ELEC. MOTOR Required GEAR BOX STA
DUTY ONLY ELEC MOTOR BY Pump Supplier ROTATION : CW from motor end
MOTOR MOUNTED BY Pump Supplier
DATA SHEETS ELEC MOTOR 9755-DAT-EL-004
PUMP TYPE CASING
SPUR GEAR MAXIMUM ALLOWABLE PRESSURE STA
SCREW RELIEF VALVE SET PRESSURE STA
VANE ü HYDRAULIC TEST PRESSURE STA
HELICAL GEAR
PROGRESSIVE CAVITY CASING SPLIT AXIAL
OTHER Sliding vane required RADIAL ü
MOUNTING
BETWEEN BEARINGS ü CENTRELINE VERTICAL FOOT MOUNTING
OVERHUNG NEAR CENTRELINE IN LINE SUMP PLATE
MECHANICAL SEALS BEARINGS SLEEVE ROLLER BALL
CONSTRUCTION

TYPE : SINGLE ü RADIAL BEARINGS STA


DUAL THRUST BEARINGS STA
DOUBLE LUBRICATION STA
Supplier STA
COUPLING MAKE Metastream or equal COUPLING GUARD YES NO
MODEL STA
RATING
CONNECTIONS SIZE ANSI FLANGE POSITION OTHER CONNECTIONS
RATING FACE NO. SIZE TYPE
SUCTION 3" 150 RAISED SIDE VENT STA Valved and

DISCHARGE 2" 150 RAISED TOP DRAIN STA Flanged to

BAL. DRUM N/A Edge of B'plate

INSTRUMENTATION (NOTE 2) PRESSURE GAUGE TYPE TEMPERATURE GAUGE TYPE


TEMP & PRESSURE LOCATION THERMOWELLS TYPE
PRESSURE SWITCH TYPE LOCATION(S)
LOCATION ACCELEROMETER
VIBRATION MOUNTING PROVISION ONLY MOUNTING ONLY NON CONTACT

9755-DAT-ME-018
Equipment Data Sheet
ROTARY POSITIVE DISPLACEMENT PUMPS 2 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-018
Proposal Curve No Sheet 2 of 3
Item Description Recovered Fuel Transfer Pump (Road Offload Area) No. of Units 1 (Tag No. P3920)

Supplier'S STANDARD ü
NOTE 3 BEARING HOUSING STA
MATERIALS

BARREL/CASING STA SHAFT SLEEVE STA


SHAFT STA BASE PLATE Fabricated Steel
ROTOR STA GASKETS Non Asbestos

TYPE NOTE 4
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 4 PHASE HERTZ ENCLOSURE NOTE 4
kW RATING STA VERTICAL HORIZONTAL
DRIVER

SPEED rev / min STA EFFICIENCY %


MINIMUM STARTING VOLTAGE INSULATION NOTE 4
DRIVER

FULL LOAD AMPS LOCKED ROTOR AMPS


STARTING METHOD TEMP. RISE deg C
BEARINGS STA LUBRICATION STA
VERTICAL SHAFT SOLID HOLLOW
VERTICAL THRUST UPWARD DOWNWARD
REMARKS

VERTICAL PUMPS UP DOWN SEPARATE MOUNTING PLATE


PUMP THRUST N DRIVER ALIGNMENT SCREWS
AT MIN FLOW N PIT OR SUMP DEPTH m
AT DESIGN FLOW N PUMP LENGTH m
VERTICAL PUMPS

AT RUNOUT N MIN SUBMERGENCE REQD. m


MAX THRUST N COLUMN PIPE FLANGED THREADED
FLOW RATE m3/hr LINE SHAFT OPEN ENCLOSED
GUIDE BUSHINGS BOWL LINE SHAFT
GUIDE BUSHINGS LUBRICATION WATER OIL GREASE PUMPAGE

REMARKS

SURFACE PREPARATION AND PAINTING NOTE 5


SURFACE PREPARATION

PUMP MOTOR BASE PLATE OTHER


SupplierS STANDARD
& PAINTING

SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS

WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT

WEIGHT OF MOTOR kg STA


REMARKS WEIGHT OF BASEPLATE kg STA

CODES AND STANDARDS


CODES AND STANDARDS

CASING IMPELLER SHAFT OTHER


MATL. CERTIFICATION REQ'D: ü ü ü
NOZZLE WELD INSPECTION. MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CASTING INSPECTION MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CHARPY TESTS REQUIRED ITEMS
APPLICABLE CODES
REMARKS

9755-DAT-ME-018
Equipment Data Sheet
ROTARY POSITIVE DISPLACEMENT PUMPS 3 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-018
Proposal Curve No Sheet 3 of 3
Item Description Recovered Fuel Transfer Pump (Road Offload Area) No. of Units 1 (Tag No. P3920)

QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA

PERFORMANCE CURVE APPR. DATE COMMENTS

SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE

HYDROTEST ü
PERFORMANCE ü
NPSH ü
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST

TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER

VENDOR TO SUBMIT TEST DATE COMMENTS


PROCEDURES

ENVIRONMENTAL & SITE DATA


ENVIRONMENTAL & SITE DATA

LOCATION INDOOR OUTDOOR UNDER ROOF PARTIAL SIDES


GRADE MEZZANINE HEATED UNHEATED
WINTERISATION REQUIRED NO TROPICALISATION REQUIRED YES
ELECTRICAL AREA ZONE NOTE 4 GAS GROUP NOTE 4 TEMPERATURE CLASS NOTE 4
CLASSIFICATION

SITE DATA ELEVATION - 0 m ATMOSPHERE - Tropical


AMBIENT TEMPERATURE deg C MINIMUM 10 NORMAL 30 MAXIMUM 50
RELATIVE HUMIDITY % MINIMUM NORMAL MAXIMUM 100

Note 1 The pump shown on this Data Sheet will be used to transfer recovered JetA1 fuel from a horizontal separator tank to a horizontal
storage tank at the road offloading area. Add 1.7 bar to the discharge pressure (to allow for the internal relief valve) when sizing the
motor.
Note 2 See project design base memorandum and P&ID drawings for full details of pump monitoring and control instrumentation.
Note 3 Do not use zinc, copper, cadmium and their alloys for parts in contact with the fuel.
NOTES

Note 4 See Data Sheet 9755-DAT-EL-004


Note 5 Pumpsets to be prepared and painted in accordance with project specification 9755-SPC-CP-007.
Note 6 Tests on one pump of each type to be witnessed by the Purchaser.
Note 7 STA = Supplier to add details.

REMARKS

9755-DAT-ME-018
Equipment Data Sheet
ROTARY POSITIVE DISPLACEMENT PUMPS 1 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-017
Proposal Curve No Sheet 1 of 3
Item Description Transfer Pump (Road Offload Area) No. of Units 3 (Tag Nos. P3201, P3202 & P3203 )

Revision A B
Issue IDC Implementation Issue
Date 3/10/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client

LIQUID Jet A1
VISCOSITY cSt @ 5oC 2.2 S G @ 5oC 0.8 SP. HEAT (kJ/kg deg C) N/A
PROCESS
DATA

REID VAPOUR PRESSURE psia MIN NORMAL Negligible MAX


PUMPING TEMP. °C MIN + 10 NORMAL + 20 MAX + 30
H2S CONCENTRATION ppm MIN N/A NORMAL N/A MAX N/A
CHLORIDES ppm N/A CORROSIVE / EROSIVE AGENT N/A
LIQUIDS Type TOXIC ü FLAMMABLE ü OTHER N/A

CAPACITY (NOTE 1) m3/hr 250 NPSH REQUIRED - RATED CAP m H20 STA
SUCTION PRESSURE BARG - 0.11 SUCTION SPECIFIC SPEED STA
DISCHARGE PRESS. BARG + 6.95 MAX SOUND PRESS. LEVEL dBA 85
DIFFERENTIAL PRESS BAR 7.06 DIFFERENTIAL HEAD m 90
DESIGN

POWER REQUIRED kW STA SPEED rev/min STA


PUMPS TO OPERATE AS ELEC. MOTOR Required GEAR BOX STA
DUTY AND STANDBY ELEC MOTOR BY Pump Supplier ROTATION : CW from motor end
MOTOR MOUNTED BY Pump Supplier
DATA SHEETS ELEC MOTOR 9755-DAT-EL-003
PUMP TYPE CASING
SPUR GEAR MAXIMUM ALLOWABLE PRESSURE STA
SCREW RELIEF VALVE SET PRESSURE STA
VANE ü HYDRAULIC TEST PRESSURE STA
HELICAL GEAR
PROGRESSIVE CAVITY CASING SPLIT AXIAL
OTHER Sliding vane required RADIAL ü
MOUNTING
BETWEEN BEARINGS ü CENTRELINE VERTICAL FOOT MOUNTING
OVERHUNG NEAR CENTRELINE IN LINE SUMP PLATE
MECHANICAL SEALS NOTE 6 BEARINGS SLEEVE ROLLER BALL
CONSTRUCTION

TYPE : SINGLE ü RADIAL BEARINGS STA


DUAL THRUST BEARINGS STA
DOUBLE LUBRICATION STA
Supplier STA
COUPLING MAKE Metastream or equal COUPLING GUARD YES NO
MODEL STA
RATING
CONNECTIONS SIZE ANSI FLANGE POSITION OTHER CONNECTIONS
RATING FACE NO. SIZE TYPE
SUCTION 8" 150 RAISED SIDE VENT STA Valved and

DISCHARGE 8" 150 RAISED SIDE DRAIN STA Flanged to

BAL. DRUM N/A Edge of B'plate

INSTRUMENTATION (NOTE 2) PRESSURE GAUGE TYPE TEMPERATURE GAUGE TYPE


TEMP & PRESSURE LOCATION THERMOWELLS TYPE
PRESSURE SWITCH TYPE LOCATION(S)
LOCATION ACCELEROMETER
VIBRATION MOUNTING PROVISION ONLY MOUNTING ONLY NON CONTACT

9755-DAT-ME-017
Equipment Data Sheet
ROTARY POSITIVE DISPLACEMENT PUMPS 2 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-017
Proposal Curve No Sheet 2 of 3
Item Description Transfer Pump (Road Offload Area) No. of Units 3 (Tag Nos. P3201, P3202 & P3203 )

Supplier'S STANDARD ü
NOTE 3 BEARING HOUSING STA
MATERIALS

BARREL/CASING STA SHAFT SLEEVE STA


SHAFT STA BASE PLATE Fabricated Steel
ROTOR STA GASKETS Non Asbestos

TYPE NOTE 4
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 4 PHASE HERTZ ENCLOSURE NOTE 4
kW RATING NOTE 1 STA VERTICAL HORIZONTAL
DRIVER

SPEED rev / min STA EFFICIENCY %


MINIMUM STARTING VOLTAGE INSULATION NOTE 4
DRIVER

FULL LOAD AMPS LOCKED ROTOR AMPS


STARTING METHOD TEMP. RISE deg C
BEARINGS STA LUBRICATION STA
VERTICAL SHAFT SOLID HOLLOW
VERTICAL THRUST UPWARD DOWNWARD
REMARKS

VERTICAL PUMPS UP DOWN SEPARATE MOUNTING PLATE


PUMP THRUST N DRIVER ALIGNMENT SCREWS
AT MIN FLOW N PIT OR SUMP DEPTH m
AT DESIGN FLOW N PUMP LENGTH m
VERTICAL PUMPS

AT RUNOUT N MIN SUBMERGENCE REQD. m


MAX THRUST N COLUMN PIPE FLANGED THREADED
FLOW RATE m3/hr LINE SHAFT OPEN ENCLOSED
GUIDE BUSHINGS BOWL LINE SHAFT
GUIDE BUSHINGS LUBRICATION WATER OIL GREASE PUMPAGE

REMARKS

SURFACE PREPARATION AND PAINTING NOTE 5


SURFACE PREPARATION

PUMP MOTOR BASE PLATE OTHER


SupplierS STANDARD
& PAINTING

SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS

WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT

WEIGHT OF MOTOR kg STA


REMARKS WEIGHT OF BASEPLATE kg STA

CODES AND STANDARDS


CODES AND STANDARDS

CASING IMPELLER SHAFT OTHER


MATL. CERTIFICATION REQ'D: ü ü ü
NOZZLE WELD INSPECTION. MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CASTING INSPECTION MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CHARPY TESTS REQUIRED ITEMS
APPLICABLE CODES
REMARKS

9755-DAT-ME-017
Equipment Data Sheet
ROTARY POSITIVE DISPLACEMENT PUMPS 3 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-017
Proposal Curve No Sheet 3 of 3
Item Description Transfer Pump (Road Offload Area) No. of Units 3 (Tag Nos. P3201, P3202 & P3203 )

QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA

PERFORMANCE CURVE APPR. DATE COMMENTS

SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 7 OBSERVE

HYDROTEST ü
PERFORMANCE ü
NPSH ü
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST

TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER

VENDOR TO SUBMIT TEST DATE COMMENTS


PROCEDURES

ENVIRONMENTAL & SITE DATA


ENVIRONMENTAL & SITE DATA

LOCATION INDOOR OUTDOOR UNDER ROOF PARTIAL SIDES


GRADE MEZZANINE HEATED UNHEATED
WINTERISATION REQUIRED NO TROPICALISATION REQUIRED YES
ELECTRICAL AREA ZONE NOTE 4 GAS GROUP NOTE 4 TEMPERATURE CLASS NOTE 4
CLASSIFICATION

SITE DATA ELEVATION - 0 m ATMOSPHERE - Tropical


AMBIENT TEMPERATURE deg C MINIMUM 10 NORMAL 30 MAXIMUM 50
RELATIVE HUMIDITY % MINIMUM NORMAL MAXIMUM 100

Note 1 The pumps shown on this Data Sheet will be used to transfer JetA1 fuel from two horizontal storage tanks at the road offload area to
the main depot storage tanks. Add 1.7 bar to the discharge pressure (to allow for the internal relief valve) when sizing the motor. They
will be used independently or with two simultaneously in a parallel arrangement.
Note 2 See project design base memorandum and P&ID drawings for full details of pump monitoring and control instrumentation.
Note 3 Do not use zinc, copper, cadmium and their alloys for parts in contact with the fuel.
NOTES

Note 4 See Data Sheet 9755-DAT-EL-003


Note 5 Pumpsets to be prepared and painted in accordance with project specification 9755-SPC-CP-007.
Note 6 Pumps are to be equipped with seal leakage detection systems. EExd IIA T3 proximity switches required.
Note 7 Tests on one pump of each type to be witnessed by the Purchaser.
Note 8 STA = Supplier to add details.

REMARKS

9755-DAT-ME-017
Equipment Data Sheet
ROTARY POSITIVE DISPLACEMENT PUMPS 1 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-016
Proposal Curve No Sheet 1 of 3
Item Description Recovered Fuel Transfer Pump No. of Units 1 (Tag No. P2920)

Revision A B
Issue IDC Implementation Issue
Date 3/10/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client

LIQUID Jet A1
VISCOSITY cSt @ 5oC 2.2 S G @ 5oC 0.8 SP. HEAT (kJ/kg deg C) N/A
PROCESS
DATA

REID VAPOUR PRESSURE psia MIN NORMAL Negligible MAX


PUMPING TEMP. °C MIN + 10 NORMAL + 20 MAX + 30
H2S CONCENTRATION ppm MIN N/A NORMAL N/A MAX N/A
CHLORIDES ppm N/A CORROSIVE / EROSIVE AGENT N/A
LIQUIDS Type TOXIC ü FLAMMABLE ü OTHER N/A

CAPACITY (NOTE 1) m3/hr 10 NPSH REQUIRED - RATED CAP m H20 STA


SUCTION PRESSURE BARG + 0.04 SUCTION SPECIFIC SPEED STA
DISCHARGE PRESS. BARG + 3.18 MAX SOUND PRESS. LEVEL dBA 85
DIFFERENTIAL PRESS BAR 3.14 DIFFERENTIAL HEAD m 40
DESIGN

POWER REQUIRED kW STA SPEED rev/min STA


PUMPS TO OPERATE AS ELEC. MOTOR Required GEAR BOX STA
DUTY ONLY ELEC MOTOR BY Pump Supplier ROTATION : CW from motor end
MOTOR MOUNTED BY Pump Supplier
DATA SHEETS ELEC MOTOR 9755-DAT-EL-004
PUMP TYPE CASING
SPUR GEAR MAXIMUM ALLOWABLE PRESSURE STA
SCREW RELIEF VALVE SET PRESSURE STA
VANE ü HYDRAULIC TEST PRESSURE STA
HELICAL GEAR
PROGRESSIVE CAVITY CASING SPLIT AXIAL
OTHER Sliding vane required RADIAL ü
MOUNTING
BETWEEN BEARINGS ü CENTRELINE VERTICAL FOOT MOUNTING
OVERHUNG NEAR CENTRELINE IN LINE SUMP PLATE
MECHANICAL SEALS BEARINGS SLEEVE ROLLER BALL
CONSTRUCTION

TYPE : SINGLE ü RADIAL BEARINGS STA


DUAL THRUST BEARINGS STA
DOUBLE LUBRICATION STA
Supplier STA
COUPLING MAKE Metastream or equal COUPLING GUARD YES NO
MODEL STA
RATING
CONNECTIONS SIZE ANSI FLANGE POSITION OTHER CONNECTIONS
RATING FACE NO. SIZE TYPE
SUCTION 3" 150 RAISED SIDE VENT STA Valved and

DISCHARGE 2" 150 RAISED TOP DRAIN STA Flanged to

BAL. DRUM N/A Edge of B'plate

INSTRUMENTATION (NOTE 2) PRESSURE GAUGE TYPE TEMPERATURE GAUGE TYPE


TEMP & PRESSURE LOCATION THERMOWELLS TYPE
PRESSURE SWITCH TYPE LOCATION(S)
LOCATION ACCELEROMETER
VIBRATION MOUNTING PROVISION ONLY MOUNTING ONLY NON CONTACT

9755-DAT-ME-016
Equipment Data Sheet
ROTARY POSITIVE DISPLACEMENT PUMPS 2 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-016
Proposal Curve No Sheet 2 of 3
Item Description Recovered Fuel Transfer Pump No. of Units 1 (Tag No. P2920)

Supplier'S STANDARD ü
NOTE 3 BEARING HOUSING STA
MATERIALS

BARREL/CASING STA SHAFT SLEEVE STA


SHAFT STA BASE PLATE Fabricated Steel
ROTOR STA GASKETS Non Asbestos

TYPE NOTE 4
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 4 PHASE HERTZ ENCLOSURE NOTE 4
kW RATING NOTE 1 STA VERTICAL HORIZONTAL
DRIVER

SPEED rev / min STA EFFICIENCY %


MINIMUM STARTING VOLTAGE INSULATION NOTE 4
DRIVER

FULL LOAD AMPS LOCKED ROTOR AMPS


STARTING METHOD TEMP. RISE deg C
BEARINGS STA LUBRICATION STA
VERTICAL SHAFT SOLID HOLLOW
VERTICAL THRUST UPWARD DOWNWARD
REMARKS

VERTICAL PUMPS UP DOWN SEPARATE MOUNTING PLATE


PUMP THRUST N DRIVER ALIGNMENT SCREWS
AT MIN FLOW N PIT OR SUMP DEPTH m
AT DESIGN FLOW N PUMP LENGTH m
VERTICAL PUMPS

AT RUNOUT N MIN SUBMERGENCE REQD. m


MAX THRUST N COLUMN PIPE FLANGED THREADED
FLOW RATE m3/hr LINE SHAFT OPEN ENCLOSED
GUIDE BUSHINGS BOWL LINE SHAFT
GUIDE BUSHINGS LUBRICATION WATER OIL GREASE PUMPAGE

REMARKS

SURFACE PREPARATION AND PAINTING NOTE 5


SURFACE PREPARATION

PUMP MOTOR BASE PLATE OTHER


SupplierS STANDARD
& PAINTING

SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS

WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT

WEIGHT OF MOTOR kg STA


REMARKS WEIGHT OF BASEPLATE kg STA

CODES AND STANDARDS


CODES AND STANDARDS

CASING IMPELLER SHAFT OTHER


MATL. CERTIFICATION REQ'D: ü ü ü
NOZZLE WELD INSPECTION. MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CASTING INSPECTION MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CHARPY TESTS REQUIRED ITEMS
APPLICABLE CODES
REMARKS

9755-DAT-ME-016
Equipment Data Sheet
ROTARY POSITIVE DISPLACEMENT PUMPS 3 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-016
Proposal Curve No Sheet 3 of 3
Item Description Recovered Fuel Transfer Pump No. of Units 1 (Tag No. P2920)

QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA

PERFORMANCE CURVE APPR. DATE COMMENTS

SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE

HYDROTEST ü
PERFORMANCE ü
NPSH ü
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST

TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER

VENDOR TO SUBMIT TEST DATE COMMENTS


PROCEDURES

ENVIRONMENTAL & SITE DATA


ENVIRONMENTAL & SITE DATA

LOCATION INDOOR OUTDOOR UNDER ROOF PARTIAL SIDES


GRADE MEZZANINE HEATED UNHEATED
WINTERISATION REQUIRED NO TROPICALISATION REQUIRED YES
ELECTRICAL AREA ZONE NOTE 4 GAS GROUP NOTE 4 TEMPERATURE CLASS NOTE 4
CLASSIFICATION

SITE DATA ELEVATION - 0 m ATMOSPHERE - Tropical


AMBIENT TEMPERATURE deg C MINIMUM 10 NORMAL 30 MAXIMUM 50
RELATIVE HUMIDITY % MINIMUM NORMAL MAXIMUM 100

Note 1 The pump shown on this Data Sheet will be used to transfer recovered JetA1 fuel from a horizontal separator tank to the the main
depot storage tanks. Add 1.7 bar to the discharge pressure (to allow for the internal relief valve) when sizing the motor.

Note 2 See project design base memorandum and P&ID drawings for full details of pump monitoring and control instrumentation.
Note 3 Do not use zinc, copper, cadmium and their alloys for parts in contact with the fuel.
NOTES

Note 4 See Data Sheet 9755-DAT-EL-004


Note 5 Pumpsets to be prepared and painted in accordance with project specification 9755-SPC-CP-007.
Note 6 Tests on one pump of each type to be witnessed by the Purchaser.
Note 7 STA = Supplier to add details.

REMARKS

9755-DAT-ME-016
Equipment Data Sheet
ROTARY POSITIVE DISPLACEMENT PUMPS 1 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-015
Proposal Curve No Sheet 1 of 3
Item Description Tank to Tank Transfer Pump No. of Units 1 (Tag No. P2501)

Revision A B
Issue IDC Implementation Issue
Date 3/10/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client

LIQUID Jet A1
VISCOSITY cSt @ 5oC 2.2 S G @ 5oC 0.8 SP. HEAT (kJ/kg deg C) N/A
PROCESS
DATA

REID VAPOUR PRESSURE psia MIN NORMAL Negligible MAX


PUMPING TEMP. °C MIN + 10 NORMAL + 20 MAX + 30
H2S CONCENTRATION ppm MIN N/A NORMAL N/A MAX N/A
CHLORIDES ppm N/A CORROSIVE / EROSIVE AGENT N/A
LIQUIDS Type TOXIC ü FLAMMABLE ü OTHER N/A

CAPACITY (NOTE 1) m3/hr 250 NPSH REQUIRED - RATED CAP m H20 STA
SUCTION PRESSURE BARG + 0.02 SUCTION SPECIFIC SPEED STA
DISCHARGE PRESS. BARG + 2.37 MAX SOUND PRESS. LEVEL dBA 85
DIFFERENTIAL PRESS BAR 2.35 DIFFERENTIAL HEAD m 30
DESIGN

POWER REQUIRED kW STA SPEED rev/min STA


PUMPS TO OPERATE AS ELEC. MOTOR Required GEAR BOX STA
DUTY ONLY ELEC MOTOR BY Pump Supplier ROTATION : CW from motor end
MOTOR MOUNTED BY Pump Supplier
DATA SHEETS ELEC MOTOR 9755-DAT-EL-004
PUMP TYPE CASING
SPUR GEAR MAXIMUM ALLOWABLE PRESSURE STA
SCREW RELIEF VALVE SET PRESSURE STA
VANE ü HYDRAULIC TEST PRESSURE STA
HELICAL GEAR
PROGRESSIVE CAVITY CASING SPLIT AXIAL
OTHER Sliding vane required RADIAL ü
MOUNTING
BETWEEN BEARINGS ü CENTRELINE VERTICAL FOOT MOUNTING
OVERHUNG NEAR CENTRELINE IN LINE SUMP PLATE
MECHANICAL SEALS BEARINGS SLEEVE ROLLER BALL
TYPE : SINGLE ü RADIAL BEARINGS STA
CONSTRUCTION

DUAL THRUST BEARINGS STA


DOUBLE LUBRICATION STA
Supplier STA
COUPLING MAKE Metastream or equal COUPLING GUARD YES NO
MODEL STA
RATING
CONNECTIONS SIZE ANSI FLANGE POSITION OTHER CONNECTIONS
RATING FACE NO. SIZE TYPE
SUCTION 8" 150 RAISED SIDE VENT STA Valved and

DISCHARGE 8" 150 RAISED SIDE DRAIN STA Flanged to

BAL. DRUM N/A Edge of B'plate

INSTRUMENTATION (NOTE 2) PRESSURE GAUGE TYPE TEMPERATURE GAUGE TYPE


TEMP & PRESSURE LOCATION THERMOWELLS TYPE
PRESSURE SWITCH TYPE LOCATION(S)
LOCATION ACCELEROMETER
VIBRATION MOUNTING PROVISION ONLY MOUNTING ONLY NON CONTACT

9755-DAT-ME-015
Equipment Data Sheet
ROTARY POSITIVE DISPLACEMENT PUMPS 2 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-015
Proposal Curve No Sheet 2 of 3
Item Description Tank to Tank Transfer Pump No. of Units 1 (Tag No. P2501)

Supplier'S STANDARD ü
NOTE 3 BEARING HOUSING STA
MATERIALS

BARREL/CASING STA SHAFT SLEEVE STA


SHAFT STA BASE PLATE Fabricated Steel
ROTOR STA GASKETS Non Asbestos

TYPE NOTE 4
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 4 PHASE HERTZ ENCLOSURE NOTE 4
kW RATING NOTE 1 STA VERTICAL HORIZONTAL
DRIVER

SPEED rev / min STA EFFICIENCY %


MINIMUM STARTING VOLTAGE INSULATION NOTE 4
DRIVER

FULL LOAD AMPS LOCKED ROTOR AMPS


STARTING METHOD TEMP. RISE deg C
BEARINGS STA LUBRICATION STA
VERTICAL SHAFT SOLID HOLLOW
VERTICAL THRUST UPWARD DOWNWARD
REMARKS

VERTICAL PUMPS UP DOWN SEPARATE MOUNTING PLATE


PUMP THRUST N DRIVER ALIGNMENT SCREWS
AT MIN FLOW N PIT OR SUMP DEPTH m
AT DESIGN FLOW N PUMP LENGTH m
VERTICAL PUMPS

AT RUNOUT N MIN SUBMERGENCE REQD. m


MAX THRUST N COLUMN PIPE FLANGED THREADED
FLOW RATE m3/hr LINE SHAFT OPEN ENCLOSED
GUIDE BUSHINGS BOWL LINE SHAFT
GUIDE BUSHINGS LUBRICATION WATER OIL GREASE PUMPAGE

REMARKS

SURFACE PREPARATION AND PAINTING NOTE 5


SURFACE PREPARATION

PUMP MOTOR BASE PLATE OTHER


SupplierS STANDARD
& PAINTING

SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS

WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT

WEIGHT OF MOTOR kg STA


REMARKS WEIGHT OF BASEPLATE kg STA

CODES AND STANDARDS


CODES AND STANDARDS

CASING IMPELLER SHAFT OTHER


MATL. CERTIFICATION REQ'D: ü ü ü
NOZZLE WELD INSPECTION. MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CASTING INSPECTION MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CHARPY TESTS REQUIRED ITEMS
APPLICABLE CODES
REMARKS

9755-DAT-ME-015
Equipment Data Sheet
ROTARY POSITIVE DISPLACEMENT PUMPS 3 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-015
Proposal Curve No Sheet 3 of 3
Item Description Tank to Tank Transfer Pump No. of Units 1 (Tag No. P2501)

QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA

PERFORMANCE CURVE APPR. DATE COMMENTS

SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE

HYDROTEST ü
PERFORMANCE ü
NPSH ü
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST

TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER

VENDOR TO SUBMIT TEST DATE COMMENTS


PROCEDURES

ENVIRONMENTAL & SITE DATA


ENVIRONMENTAL & SITE DATA

LOCATION INDOOR OUTDOOR UNDER ROOF PARTIAL SIDES


GRADE MEZZANINE HEATED UNHEATED
WINTERISATION REQUIRED NO TROPICALISATION REQUIRED YES
ELECTRICAL AREA ZONE NOTE 4 GAS GROUP NOTE 4 TEMPERATURE CLASS NOTE 4
CLASSIFICATION

SITE DATA ELEVATION - 0 m ATMOSPHERE - Tropical


AMBIENT TEMPERATURE deg C MINIMUM 10 NORMAL 30 MAXIMUM 50
RELATIVE HUMIDITY % MINIMUM NORMAL MAXIMUM 100

Note 1 The pump shown on this Data Sheet will be used to transfer JetA1 fuel from tank to tank. Add 1.7 bar to the discharge pressure (to
allow for the internal relief valve) when sizing the motor.

Note 2 See project design base memorandum and P&ID drawings for full details of pump monitoring and control instrumentation.
Note 3 Do not use zinc, copper, cadmium and their alloys for parts in contact with the fuel.
NOTES

Note 4 See Data Sheet 9755-DAT-EL-004


Note 5 Pumpsets to be prepared and painted in accordance with project specification 9755-SPC-CP-007.
Note 6 Tests on one pump of each type to be witnessed by the Purchaser.
Note 7 STA = Supplier to add details.

REMARKS

9755-DAT-ME-015
Equipment Data Sheet
CENTRIFUGAL PUMPS 1 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-014
Proposal Curve No Sheet 1 of 3
Item Description Water Drain Sump Pump, Slab (Road Offload Area) No. of Units 2 (Tag Nos. P3970 & P3971)

Revision A B
Issue IDC Implementation Issue
Date 3/13/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client

LIQUID Water or Jet fuel


VISCOSITY cSt @ 5oC 1 S G @ 5oC 1 SP. HEAT (kJ/kg deg C) N/A
PROCESS
DATA

REID VAPOUR PRESSURE psia MIN NORMAL Negligible MAX


PUMPING TEMP. °C MIN + 10 NORMAL + 20 MAX + 30
H2S CONCENTRATION ppm MIN N/A NORMAL N/A MAX N/A
CHLORIDES ppm N/A CORROSIVE / EROSIVE AGENT N/A
LIQUIDS Type TOXIC ü FLAMMABLE ü OTHER N/A

CAPACITY (NOTE 1) m3/hr MIN 4 RATED 10 MAX


MINIMUM CONTINUOUS FLOW THERMAL m3/hr
STABLE m3/hr
DESIGN

SUCTION PRESSURE BARG RATED Flooded suction MAXIMUM


DISCHARGE PRESS. BARG 0.84 DIFFERENTIAL PRESS. BARG
DIFFERENTIAL HEAD m 8.51 NPSH REQUIRED - RATED CAP m H2O
MAX HEAD-RATED IMPELLER m STA SUCTION SPECIFIC SPEED STA
MAX POWER-RATED IMPLLER. kW STA MAX SOUND PRESS. LEVEL 85 dBA
POWER REQUIRED kW STA SPEED rev/min STA ROTATION : STA
PUMPS TO OPERATE AS ELEC. MOTOR Required GEAR BOX N/A
DUTY AND STANDBY ELEC MOTOR BY Pump Supplier FLUID COUPLING BY N/A
MOTOR MOUNTED BY Pump Supplier FLUID COUPLING MOUNTED BY N/A
DATA SHEETS ELEC MOTOR 9755-DAT-EL-003 FLUID COUPLING N/A
IMPELLER CASING CASING SPLIT
TYPE CLOSED, RADIAL FLOW SINGLE VOLUTE AXIAL
DIAMETER mm STA DOUBLE VOLUTE RADIAL ü
BETWEEN BEARINGS VERTICAL SINGLE CASING ü
OVERHUNG MOUNTNG CENTRELINE VERTICAL FOOT MOUNTING
NEAR CENTRELINE IN LINE SUMP PLATE
MECHANICAL SEALS BEARINGS SLEEVE ROLLER BALL
CONSTRUCTION

TYPE : SINGLE ü RADIAL BEARINGS STA


DUAL THRUST BEARINGS STA
DOUBLE LUBRICATION STA
Supplier STA
COUPLING MAKE STA COUPLING GUARD YES NO
MODEL STA
RATING
CONNECTIONS SIZE ANSI FLANGE POSITION OTHER CONNECTIONS
RATING FACE NO. SIZE TYPE
SUCTION NOTE 5 VENT
DISCHARGE 2" 150 RAISED Side DRAIN
BAL. DRUM N/A
INSTRUMENTATION (NOTE 2) PRESSURE GAUGE TYPE TEMPERATURE GAUGE TYPE
TEMP & PRESSURE LOCATION THERMOWELLS TYPE
PRESSURE SWITCH TYPE LOCATION(S)
LOCATION ACCELEROMETER
VIBRATION MOUNTING PROVISION ONLY MOUNTING ONLY NON CONTACT

9755-DAT-ME-014
Equipment Data Sheet
CENTRIFUGAL PUMPS 2 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-014
Proposal Curve No Sheet 2 of 3
Item Description Water Drain Sump Pump, Slab (Road Offload Area) No. of Units 2 (Tag Nos. P3970 & P3971)

API 610 Material Classification S-1 BEARING HOUSING STA


BARREL/CASING STA WEAR RINGS STA
MATERIALS

SHAFT STA SHAFT SLEEVE STA


IMPELLER STA MOUNTING PLATE Fabricated Steel
GASKETS Non Asbestos

TYPE NOTE 3
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 3 PHASE HERTZ ENCLOSURE NOTE 3
kW RATING STA VERTICAL HORIZONTAL
DRIVER

SPEED rev / min STA EFFICIENCY %


MINIMUM STARTING VOLTAGE INSULATION NOTE 3
DRIVER

FULL LOAD AMPS LOCKED ROTOR AMPS


STARTING METHOD TEMP. RISE deg C
BEARINGS STA LUBRICATION STA
VERTICAL SHAFT SOLID HOLLOW
VERTICAL THRUST UPWARD DOWNWARD
REMARKS

VERTICAL PUMPS UP DOWN SEPARATE MOUNTING PLATE NOTE 5


PUMP THRUST N DRIVER ALIGNMENT SCREWS Required
AT MIN FLOW N PIT OR SUMP DEPTH m 0.5
AT DESIGN FLOW N PUMP LENGTH m STA
VERTICAL PUMPS

AT RUNOUT N MIN SUBMERGENCE m STA


MAX THRUST N COLUMN PIPE FLANGED ü THREADED
FLOW RATE m3/hr 10 LINE SHAFT OPEN ENCLOSED ü
GUIDE BUSHINGS BOWL LINE SHAFT
GUIDE BUSHINGS LUBRICATION WATER OIL GREASE PUMPAGE ü

REMARKS DRAIN TANK PUMP YES


NO ü
SURFACE PREPARATION AND PAINTING NOTE 4
SURFACE PREPARATION

PUMP MOTOR MOUNTING PLATE OTHER


SupplierS STANDARD
& PAINTING

SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS

WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT

WEIGHT OF MOTOR kg STA


REMARKS WEIGHT OF BASEPLATE kg STA

CODES AND STANDARDS


CODES AND STANDARDS

CASING IMPELLER SHAFT OTHER


MATL. CERTIFICATION REQ'D: ü ü ü
NOZZLE WELD INSPECTION. MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CASTING INSPECTION MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CHARPY TESTS REQUIRED ITEMS
APPLICABLE CODES
REMARKS

9755-DAT-ME-014
Equipment Data Sheet
CENTRIFUGAL PUMPS 3 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-014
Proposal Curve No Sheet 3 of 3
Item Description Water Drain Sump Pump, Slab (Road Offload Area) No. of Units 2 (Tag Nos. P3970 & P3971)

QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA

PERFORMANCE CURVE APPR. DATE COMMENTS

SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE

HYDROTEST ü
PERFORMANCE ü
NPSH
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST

TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER

VENDOR TO SUBMIT TEST DATE COMMENTS


PROCEDURES

ENVIRONMENTAL & SITE DATA


ENVIRONMENTAL & SITE DATA

LOCATION INDOOR OUTDOOR UNDER ROOF PARTIAL SIDES


GRADE MEZZANINE HEATED UNHEATED
WINTERISATION REQUIRED NO TROPICALISATION REQUIRED YES
ELECTRICAL AREA ZONE NOTE 3 GAS GROUP NOTE 3 TEMPERATURE CLASS NOTE 3
CLASSIFICATION

SITE DATA ELEVATION - 0 m ATMOSPHERE - Tropical


AMBIENT TEMPERATURE deg C MINIMUM 10 NORMAL 30 MAXIMUM 50
RELATIVE HUMIDITY % MINIMUM NORMAL MAXIMUM 100

Note 1 The pump shown on this Data Sheet will be used to transfer water from a slab drain sump to an open drain.
There could be Jet fuel in the sump occasionally.
Note 2 See project design base memorandum and P&ID drawings for full details of pump monitoring and control instrumentation.
Note 3 See Data Sheet 9755-DAT-EL-003
NOTES

Note 4 Pumpsets to be prepared and painted in accordance with project specification 9755-SPC-CP-007.
Note 5 Mounting plate to be suitable for galvanised open mesh flooring of drain sump. Sump depth = 0.5m.
Note 6 Tests on one pump of each type to be witnessed by the Purchaser.
Note 7 STA = Supplier to add details.

REMARKS

9755-DAT-ME-014
Equipment Data Sheet
CENTRIFUGAL PUMPS 1 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-013
Proposal Curve No Sheet 1 of 3
Item Description Oily Water Separator Pump, Water Sump (Road Offload Area) No. of Units 2 (Tag No. P3931 & P3932)

Revision A B
Issue IDC Implementation Issue
Date 3/13/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client

LIQUID Water
VISCOSITY cSt @ 5oC 1 S G @ 5oC 1 SP. HEAT (kJ/kg deg C) N/A
PROCESS
DATA

REID VAPOUR PRESSURE psia MIN NORMAL Negligible MAX


PUMPING TEMP. °C MIN + 10 NORMAL + 20 MAX + 30
H2S CONCENTRATION ppm MIN N/A NORMAL N/A MAX N/A
CHLORIDES ppm N/A CORROSIVE / EROSIVE AGENT N/A
LIQUIDS Type TOXIC FLAMMABLE OTHER N/A

CAPACITY (NOTE 1) m3/hr MIN 36 RATED 90 MAX


MINIMUM CONTINUOUS FLOW THERMAL m3/hr
STABLE m3/hr
DESIGN

SUCTION PRESSURE BARG RATED Flooded suction MAXIMUM


DISCHARGE PRESS. BARG 0.65 DIFFERENTIAL PRESS. BARG
DIFFERENTIAL HEAD m 6.66 NPSH REQUIRED - RATED CAP m H2O
MAX HEAD-RATED IMPELLER m STA SUCTION SPECIFIC SPEED STA
MAX POWER-RATED IMPLLER. kW STA MAX SOUND PRESS. LEVEL 85 dBA
POWER REQUIRED kW STA SPEED rev/min STA ROTATION : STA
PUMPS TO OPERATE AS ELEC. MOTOR Required GEAR BOX N/A
DUTY AND STANDBY ELEC MOTOR BY Pump Supplier FLUID COUPLING BY N/A
MOTOR MOUNTED BY Pump Supplier FLUID COUPLING MOUNTED BY N/A
DATA SHEETS ELEC MOTOR 9755-DAT-EL-003 FLUID COUPLING N/A
IMPELLER CASING CASING SPLIT
TYPE CLOSED, RADIAL FLOW SINGLE VOLUTE AXIAL
DIAMETER mm STA DOUBLE VOLUTE RADIAL ü
BETWEEN BEARINGS VERTICAL SINGLE CASING ü
OVERHUNG MOUNTNG CENTRELINE VERTICAL FOOT MOUNTING
NEAR CENTRELINE IN LINE SUMP PLATE
MECHANICAL SEALS BEARINGS SLEEVE ROLLER BALL
CONSTRUCTION

TYPE : SINGLE ü RADIAL BEARINGS STA


DUAL THRUST BEARINGS STA
DOUBLE LUBRICATION STA
Supplier STA
COUPLING MAKE STA COUPLING GUARD YES NO
MODEL STA
RATING
CONNECTIONS SIZE ANSI FLANGE POSITION OTHER CONNECTIONS
RATING FACE NO. SIZE TYPE
SUCTION NOTE 5 VENT
DISCHARGE 3" 150 RAISED Side DRAIN
BAL. DRUM N/A
INSTRUMENTATION (NOTE 2) PRESSURE GAUGE TYPE TEMPERATURE GAUGE TYPE
TEMP & PRESSURE LOCATION THERMOWELLS TYPE
PRESSURE SWITCH TYPE LOCATION(S)
LOCATION ACCELEROMETER
VIBRATION MOUNTING PROVISION ONLY MOUNTING ONLY NON CONTACT

9755-DAT-ME-013
Equipment Data Sheet
CENTRIFUGAL PUMPS 2 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-013
Proposal Curve No Sheet 2 of 3
Item Description Oily Water Separator Pump, Water Sump (Road Offload Area) No. of Units 2 (Tag No. P3931 & P3932)

API 610 Material Classification S-1 BEARING HOUSING STA


BARREL/CASING STA WEAR RINGS STA
MATERIALS

SHAFT STA SHAFT SLEEVE STA


IMPELLER STA MOUNTING PLATE Fabricated Steel
GASKETS Non Asbestos

TYPE NOTE 3
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 3 PHASE HERTZ ENCLOSURE NOTE 3
kW RATING STA VERTICAL HORIZONTAL
DRIVER

SPEED rev / min STA EFFICIENCY %


MINIMUM STARTING VOLTAGE INSULATION NOTE 3
DRIVER

FULL LOAD AMPS LOCKED ROTOR AMPS


STARTING METHOD TEMP. RISE deg C
BEARINGS STA LUBRICATION STA
VERTICAL SHAFT SOLID HOLLOW
VERTICAL THRUST UPWARD DOWNWARD
REMARKS

VERTICAL PUMPS UP DOWN SEPARATE MOUNTING PLATE NOTE 5


PUMP THRUST N DRIVER ALIGNMENT SCREWS Required
AT MIN FLOW N PIT OR SUMP DEPTH m 4.375
AT DESIGN FLOW N PUMP LENGTH m 4.125
VERTICAL PUMPS

AT RUNOUT N MIN SUBMERGENCE m STA


MAX THRUST N COLUMN PIPE FLANGED ü THREADED
FLOW RATE m3/hr 90 LINE SHAFT OPEN ENCLOSED ü
GUIDE BUSHINGS BOWL LINE SHAFT
GUIDE BUSHINGS LUBRICATION WATER OIL GREASE PUMPAGE ü

REMARKS DRAIN TANK PUMP YES


NO ü
SURFACE PREPARATION AND PAINTING NOTE 4
SURFACE PREPARATION

PUMP MOTOR MOUNTING PLATE OTHER


SupplierS STANDARD
& PAINTING

SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS

WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT

WEIGHT OF MOTOR kg STA


REMARKS WEIGHT OF BASEPLATE kg STA

CODES AND STANDARDS


CODES AND STANDARDS

CASING IMPELLER SHAFT OTHER


MATL. CERTIFICATION REQ'D: ü ü ü
NOZZLE WELD INSPECTION. MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CASTING INSPECTION MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CHARPY TESTS REQUIRED ITEMS
APPLICABLE CODES
REMARKS

9755-DAT-ME-013
Equipment Data Sheet
CENTRIFUGAL PUMPS 3 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-013
Proposal Curve No Sheet 3 of 3
Item Description Oily Water Separator Pump, Water Sump (Road Offload Area) No. of Units 2 (Tag No. P3931 & P3932)

QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA

PERFORMANCE CURVE APPR. DATE COMMENTS

SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE

HYDROTEST ü
PERFORMANCE ü
NPSH
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST

TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER

VENDOR TO SUBMIT TEST DATE COMMENTS


PROCEDURES

ENVIRONMENTAL & SITE DATA


ENVIRONMENTAL & SITE DATA

LOCATION INDOOR OUTDOOR UNDER ROOF PARTIAL SIDES


GRADE MEZZANINE HEATED UNHEATED
WINTERISATION REQUIRED NO TROPICALISATION REQUIRED YES
ELECTRICAL AREA ZONE NOTE 3 GAS GROUP NOTE 3 TEMPERATURE CLASS NOTE 3
CLASSIFICATION

SITE DATA ELEVATION - 0 m ATMOSPHERE - Tropical


AMBIENT TEMPERATURE deg C MINIMUM 10 NORMAL 30 MAXIMUM 70
RELATIVE HUMIDITY % MINIMUM NORMAL MAXIMUM 100

Note 1 The pump shown on this Data Sheet will be used to transfer water from a separator water sump to an open drain sump.
Note 2 See project design base memorandum and P&ID drawings for full details of pump monitoring and control instrumentation.
Note 3 See Data Sheet 9755-DAT-EL-003
Note 4 Pumpsets to be prepared and painted in accordance with project specification 9755-SPC-CP-007.
NOTES

Note 5 See drawing 9755/CI/2/4534. Mounting plate to be suitable for galvanised open mesh flooring of intercepter.
Note 6 Tests on one pump of each type to be witnessed by the Purchaser.
Note 7 STA = Supplier to add details.

REMARKS

9755-DAT-ME-013
Equipment Data Sheet
CENTRIFUGAL PUMPS 1 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-012
Proposal Curve No Sheet 1 of 3
Item Description Oily Water Separator Pump, Oil Sump (Road Offload Area) No. of Units 1 (Tag No. P3930)

Revision A B
Issue IDC Implementation Issue
Date 3/13/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client

LIQUID Jet A1fuel


VISCOSITY cSt @ 5oC 2.2 S G @ 5oC 0.8 SP. HEAT (kJ/kg deg C) N/A
PROCESS
DATA

REID VAPOUR PRESSURE psia MIN NORMAL Negligible MAX


PUMPING TEMP. °C MIN + 10 NORMAL + 20 MAX + 30
H2S CONCENTRATION ppm MIN N/A NORMAL N/A MAX N/A
CHLORIDES ppm N/A CORROSIVE / EROSIVE AGENT N/A
LIQUIDS Type TOXIC ü FLAMMABLE ü OTHER N/A

CAPACITY (NOTE 1) m3/hr MIN 1.2 RATED 3 MAX


MINIMUM CONTINUOUS FLOW THERMAL m3/hr
STABLE m3/hr
DESIGN

SUCTION PRESSURE BARG RATED Flooded suction MAXIMUM


DISCHARGE PRESS. BARG 0.88 DIFFERENTIAL PRESS. BARG
DIFFERENTIAL HEAD m 11.19 NPSH REQUIRED - RATED CAP m H2O
MAX HEAD-RATED IMPELLER m STA SUCTION SPECIFIC SPEED STA
MAX POWER-RATED IMPLLER. kW STA MAX SOUND PRESS. LEVEL 85 dBA
POWER REQUIRED kW STA SPEED rev/min STA ROTATION : STA
PUMPS TO OPERATE AS ELEC. MOTOR Required GEAR BOX N/A
DUTY ONLY ELEC MOTOR BY Pump Supplier FLUID COUPLING BY N/A
MOTOR MOUNTED BY Pump Supplier FLUID COUPLING MOUNTED BY N/A
DATA SHEETS ELEC MOTOR 9755-DAT-EL-003 FLUID COUPLING N/A
IMPELLER CASING CASING SPLIT
TYPE CLOSED, RADIAL FLOW SINGLE VOLUTE AXIAL
DIAMETER mm STA DOUBLE VOLUTE RADIAL ü
BETWEEN BEARINGS VERTICAL SINGLE CASING ü
OVERHUNG MOUNTNG CENTRELINE VERTICAL FOOT MOUNTING
NEAR CENTRELINE IN LINE SUMP PLATE
MECHANICAL SEALS BEARINGS SLEEVE ROLLER BALL
CONSTRUCTION

TYPE : SINGLE ü RADIAL BEARINGS STA


DUAL THRUST BEARINGS STA
DOUBLE LUBRICATION STA
Supplier STA
COUPLING MAKE STA COUPLING GUARD YES NO
MODEL STA
RATING
CONNECTIONS SIZE ANSI FLANGE POSITION OTHER CONNECTIONS
RATING FACE NO. SIZE TYPE
SUCTION NOTE 5 VENT
DISCHARGE 2" 150 RAISED Side DRAIN
BAL. DRUM N/A
INSTRUMENTATION (NOTE 2) PRESSURE GAUGE TYPE TEMPERATURE GAUGE TYPE
TEMP & PRESSURE LOCATION THERMOWELLS TYPE
PRESSURE SWITCH TYPE LOCATION(S)
LOCATION ACCELEROMETER
VIBRATION MOUNTING PROVISION ONLY MOUNTING ONLY NON CONTACT

9755-DAT-ME-012
Equipment Data Sheet
CENTRIFUGAL PUMPS 2 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-012
Proposal Curve No Sheet 2 of 3
Item Description Oily Water Separator Pump, Oil Sump (Road Offload Area) No. of Units 1 (Tag No. P3930)

API 610 Material Classification S-1 BEARING HOUSING STA


BARREL/CASING STA WEAR RINGS STA
MATERIALS

SHAFT STA SHAFT SLEEVE STA


IMPELLER STA MOUNTING PLATE Fabricated Steel
GASKETS Non Asbestos

TYPE NOTE 3
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 3 PHASE HERTZ ENCLOSURE NOTE 3
kW RATING STA VERTICAL HORIZONTAL
DRIVER

SPEED rev / min STA EFFICIENCY %


MINIMUM STARTING VOLTAGE INSULATION NOTE 3
DRIVER

FULL LOAD AMPS LOCKED ROTOR AMPS


STARTING METHOD TEMP. RISE deg C
BEARINGS STA LUBRICATION STA
VERTICAL SHAFT SOLID HOLLOW
VERTICAL THRUST UPWARD DOWNWARD
REMARKS

VERTICAL PUMPS UP DOWN SEPARATE MOUNTING PLATE NOTE 5


PUMP THRUST N DRIVER ALIGNMENT SCREWS Required
AT MIN FLOW N PIT OR SUMP DEPTH m 4.375
AT DESIGN FLOW N PUMP LENGTH m 4.125
VERTICAL PUMPS

AT RUNOUT N MIN SUBMERGENCE m STA


MAX THRUST N COLUMN PIPE FLANGED ü THREADED
FLOW RATE m3/hr 3 LINE SHAFT OPEN ENCLOSED ü
GUIDE BUSHINGS BOWL LINE SHAFT
GUIDE BUSHINGS LUBRICATION WATER OIL GREASE PUMPAGE ü

REMARKS DRAIN TANK PUMP YES


NO ü
SURFACE PREPARATION AND PAINTING NOTE 4
SURFACE PREPARATION

PUMP MOTOR MOUNTING PLATE OTHER


SupplierS STANDARD
& PAINTING

SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS

WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT

WEIGHT OF MOTOR kg STA


REMARKS WEIGHT OF BASEPLATE kg STA

CODES AND STANDARDS


CODES AND STANDARDS

CASING IMPELLER SHAFT OTHER


MATL. CERTIFICATION REQ'D: ü ü ü
NOZZLE WELD INSPECTION. MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CASTING INSPECTION MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CHARPY TESTS REQUIRED ITEMS
APPLICABLE CODES
REMARKS

9755-DAT-ME-012
Equipment Data Sheet
CENTRIFUGAL PUMPS 3 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-012
Proposal Curve No Sheet 3 of 3
Item Description Oily Water Separator Pump, Oil Sump (Road Offload Area) No. of Units 1 (Tag No. P3930)

QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA

PERFORMANCE CURVE APPR. DATE COMMENTS

SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE

HYDROTEST ü
PERFORMANCE ü
NPSH
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST

TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER

VENDOR TO SUBMIT TEST DATE COMMENTS


PROCEDURES

ENVIRONMENTAL & SITE DATA


ENVIRONMENTAL & SITE DATA

LOCATION INDOOR OUTDOOR UNDER ROOF PARTIAL SIDES


GRADE MEZZANINE HEATED UNHEATED
WINTERISATION REQUIRED NO TROPICALISATION REQUIRED YES
ELECTRICAL AREA ZONE NOTE 3 GAS GROUP NOTE 3 TEMPERATURE CLASS NOTE 3
CLASSIFICATION

SITE DATA ELEVATION - 0 m ATMOSPHERE - Tropical


AMBIENT TEMPERATURE deg C MINIMUM 10 NORMAL 30 MAXIMUM 70
RELATIVE HUMIDITY % MINIMUM NORMAL MAXIMUM 100

Note 1 The pump shown on this Data Sheet will be used to transfer fuel from an oil separator oil sump to a hose line.
Note 2 See project design base memorandum and P&ID drawings for full details of pump monitoring and control instrumentation.
Note 3 See Data Sheet 9755-DAT-EL-003
Note 4 Pumpsets to be prepared and painted in accordance with project specification 9755-SPC-CP-007.
NOTES

Note 5 See drawing 9755/CI/2/4534. Mounting plate to be suitable for galvanised open mesh flooring of intercepter.
Note 6 Tests on one pump of each type to be witnessed by the Purchaser.
Note 7 STA = Supplier to add details.

REMARKS

9755-DAT-ME-012
Equipment Data Sheet
CENTRIFUGAL PUMPS 1 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-011
Proposal Curve No Sheet 1 of 3
Item Description Drained Fuel Transfer Pump (Road Offload Area) No. of Units 1 (Tag No. P3901)

Revision A B
Issue IDC Implementation Issue
Date 3/13/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client

LIQUID Water or Jet A1 fuel


VISCOSITY cSt @ 5oC 1 S G @ 5oC 1 SP. HEAT (kJ/kg deg C) N/A
PROCESS
DATA

REID VAPOUR PRESSURE psia MIN NORMAL Negligible MAX


PUMPING TEMP. °C MIN + 10 NORMAL + 20 MAX + 30
H2S CONCENTRATION ppm MIN N/A NORMAL N/A MAX N/A
CHLORIDES ppm N/A CORROSIVE / EROSIVE AGENT N/A
LIQUIDS Type TOXIC ü FLAMMABLE ü OTHER N/A

CAPACITY (NOTE 1) m3/hr MIN 10 RATED 22 MAX


MINIMUM CONTINUOUS FLOW THERMAL m3/hr
STABLE 22 m3/hr
DESIGN

SUCTION PRESSURE BARG RATED Flooded suction MAXIMUM


DISCHARGE PRESS. BARG + 0.88 DIFFERENTIAL PRESS. BARG
DIFFERENTIAL HEAD m 9 NPSH REQUIRED - RATED CAP m H2O
MAX HEAD-RATED IMPELLER m STA SUCTION SPECIFIC SPEED STA
MAX POWER-RATED IMPLLER. kW STA MAX SOUND PRESS. LEVEL 85 dBA
POWER REQUIRED kW STA SPEED rev/min STA ROTATION : STA
PUMPS TO OPERATE AS ELEC. MOTOR Required GEAR BOX N/A
DUTY ONLY ELEC MOTOR BY Pump Supplier FLUID COUPLING BY N/A
MOTOR MOUNTED BY Pump Supplier FLUID COUPLING MOUNTED BY N/A
DATA SHEETS ELEC MOTOR 9755-DAT-EL-004 FLUID COUPLING N/A
IMPELLER CASING CASING SPLIT
TYPE CLOSED, RADIAL FLOW SINGLE VOLUTE AXIAL
DIAMETER mm STA DOUBLE VOLUTE RADIAL ü
BETWEEN BEARINGS VERTICAL SINGLE CASING ü
OVERHUNG MOUNTNG CENTRELINE VERTICAL FOOT MOUNTING
NEAR CENTRELINE IN LINE SUMP PLATE
MECHANICAL SEALS BEARINGS SLEEVE ROLLER BALL
CONSTRUCTION

TYPE : SINGLE ü RADIAL BEARINGS STA


DUAL THRUST BEARINGS STA
DOUBLE LUBRICATION STA
Supplier STA
COUPLING MAKE STA COUPLING GUARD YES NO
MODEL STA
RATING
CONNECTIONS SIZE ANSI FLANGE POSITION OTHER CONNECTIONS
RATING FACE NO. SIZE TYPE
SUCTION NOTE 5 VENT
DISCHARGE 2" 150 RAISED Side DRAIN
BAL. DRUM N/A
INSTRUMENTATION (NOTE 2) PRESSURE GAUGE TYPE TEMPERATURE GAUGE TYPE
TEMP & PRESSURE LOCATION THERMOWELLS TYPE
PRESSURE SWITCH TYPE LOCATION(S)
LOCATION ACCELEROMETER
VIBRATION MOUNTING PROVISION ONLY MOUNTING ONLY NON CONTACT

9755-DAT-ME-011
Equipment Data Sheet
CENTRIFUGAL PUMPS 2 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-011
Proposal Curve No Sheet 2 of 3
Item Description Drained Fuel Transfer Pump (Road Offload Area) No. of Units 1 (Tag No. P3901)

API 610 Material Classification S-1 BEARING HOUSING STA


BARREL/CASING STA WEAR RINGS STA
MATERIALS

SHAFT STA SHAFT SLEEVE STA


IMPELLER STA MOUNTING PLATE Fabricated Steel
GASKETS Non Asbestos

TYPE NOTE 3
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 3 PHASE HERTZ ENCLOSURE NOTE 3
kW RATING STA VERTICAL HORIZONTAL
DRIVER

SPEED rev / min STA EFFICIENCY %


MINIMUM STARTING VOLTAGE INSULATION NOTE 3
DRIVER

FULL LOAD AMPS LOCKED ROTOR AMPS


STARTING METHOD TEMP. RISE deg C
BEARINGS STA LUBRICATION STA
VERTICAL SHAFT SOLID HOLLOW
VERTICAL THRUST UPWARD DOWNWARD
REMARKS

VERTICAL PUMPS UP DOWN SEPARATE MOUNTING PLATE 24" Diameter, ANSI 150
PUMP THRUST N DRIVER ALIGNMENT SCREWS Required
AT MIN FLOW N PIT OR SUMP DEPTH m NOTE 5
AT DESIGN FLOW N PUMP LENGTH m NOTE 5
VERTICAL PUMPS

AT RUNOUT N MIN SUBMERGENCE m STA


MAX THRUST N COLUMN PIPE FLANGED ü THREADED
FLOW RATE m3/hr 22 LINE SHAFT OPEN ENCLOSED ü
GUIDE BUSHINGS BOWL LINE SHAFT
GUIDE BUSHINGS LUBRICATION WATER OIL GREASE PUMPAGE ü

REMARKS DRAIN TANK PUMP YES ü


NO
SURFACE PREPARATION AND PAINTING NOTE 4
SURFACE PREPARATION

PUMP MOTOR MOUNTING PLATE OTHER


SupplierS STANDARD
& PAINTING

SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS

WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT

WEIGHT OF MOTOR kg STA


REMARKS WEIGHT OF BASEPLATE kg STA

CODES AND STANDARDS


CODES AND STANDARDS

CASING IMPELLER SHAFT OTHER


MATL. CERTIFICATION REQ'D: ü ü ü
NOZZLE WELD INSPECTION. MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CASTING INSPECTION MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CHARPY TESTS REQUIRED ITEMS
APPLICABLE CODES
REMARKS

9755-DAT-ME-011
Equipment Data Sheet
CENTRIFUGAL PUMPS 3 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-011
Proposal Curve No Sheet 3 of 3
Item Description Drained Fuel Transfer Pump (Road Offload Area) No. of Units 1 (Tag No. P3901)

QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA

PERFORMANCE CURVE APPR. DATE COMMENTS

SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE

HYDROTEST ü
PERFORMANCE ü
NPSH
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST

TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER

VENDOR TO SUBMIT TEST DATE COMMENTS


PROCEDURES

ENVIRONMENTAL & SITE DATA


ENVIRONMENTAL & SITE DATA

LOCATION INDOOR OUTDOOR UNDER ROOF PARTIAL SIDES


GRADE MEZZANINE HEATED UNHEATED
WINTERISATION REQUIRED NO TROPICALISATION REQUIRED YES
ELECTRICAL AREA ZONE NOTE 3 GAS GROUP NOTE 3 TEMPERATURE CLASS NOTE 3
CLASSIFICATION

SITE DATA ELEVATION - 0 m ATMOSPHERE - Tropical


AMBIENT TEMPERATURE deg C MINIMUM 10 NORMAL 30 MAXIMUM 70
RELATIVE HUMIDITY % MINIMUM NORMAL MAXIMUM 100

Note 1 The pump shown on this Data Sheet will be used to transfer fuel and water slops from a buried tank to a separator tank.
Note 2 See project design base memorandum and P&ID drawings for full details of pump monitoring and control instrumentation.
Note 3 See Data Sheet 9755-DAT-EL-004
Note 4 Pumpsets to be prepared and painted in accordance with project specification 9755-SPC-CP-007.
NOTES

Note 5 See details on tank Data Sheet 9755-DAT-ME-043


Note 6 Tests on one pump of each type to be witnessed by the Purchaser.
Note 7 STA = Supplier to add details.

REMARKS

9755-DAT-ME-011
Equipment Data Sheet
CENTRIFUGAL PUMPS 1 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-010
Proposal Curve No Sheet 1 of 3
Item Description Water Drain Sump Pump, Pipe Trench No. of Units 1 (Tag No. P2971)

Revision A B
Issue IDC Implementation Issue
Date 3/13/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client

LIQUID Water
VISCOSITY cSt @ 5oC 1 S G @ 5oC 1 SP. HEAT (kJ/kg deg C) N/A
PROCESS
DATA

REID VAPOUR PRESSURE psia MIN NORMAL Negligible MAX


PUMPING TEMP. °C MIN + 10 NORMAL + 20 MAX + 30
H2S CONCENTRATION ppm MIN N/A NORMAL N/A MAX N/A
CHLORIDES ppm N/A CORROSIVE / EROSIVE AGENT N/A
LIQUIDS Type TOXIC FLAMMABLE OTHER N/A

CAPACITY (NOTE 1) m3/hr MIN 4 RATED 10 MAX


MINIMUM CONTINUOUS FLOW THERMAL m3/hr
STABLE m3/hr
DESIGN

SUCTION PRESSURE BARG RATED Flooded suction MAXIMUM


DISCHARGE PRESS. BARG 0.49 DIFFERENTIAL PRESS. BARG
DIFFERENTIAL HEAD m 4.95 NPSH REQUIRED - RATED CAP m H2O
MAX HEAD-RATED IMPELLER m STA SUCTION SPECIFIC SPEED STA
MAX POWER-RATED IMPLLER. kW STA MAX SOUND PRESS. LEVEL 85 dBA
POWER REQUIRED kW STA SPEED rev/min STA ROTATION : STA
PUMPS TO OPERATE AS ELEC. MOTOR Required GEAR BOX N/A
DUTY ONLY ELEC MOTOR BY Pump Supplier FLUID COUPLING BY N/A
MOTOR MOUNTED BY Pump Supplier FLUID COUPLING MOUNTED BY N/A
DATA SHEETS ELEC MOTOR 9755-DAT-EL-003 FLUID COUPLING N/A
IMPELLER CASING CASING SPLIT
TYPE CLOSED, RADIAL FLOW SINGLE VOLUTE AXIAL
DIAMETER mm STA DOUBLE VOLUTE RADIAL ü
BETWEEN BEARINGS VERTICAL SINGLE CASING ü
OVERHUNG MOUNTNG CENTRELINE VERTICAL FOOT MOUNTING
NEAR CENTRELINE IN LINE SUMP PLATE
MECHANICAL SEALS BEARINGS SLEEVE ROLLER BALL
CONSTRUCTION

TYPE : SINGLE ü RADIAL BEARINGS STA


DUAL THRUST BEARINGS STA
DOUBLE LUBRICATION STA
Supplier STA
COUPLING MAKE STA COUPLING GUARD YES NO
MODEL STA
RATING
CONNECTIONS SIZE ANSI FLANGE POSITION OTHER CONNECTIONS
RATING FACE NO. SIZE TYPE
SUCTION NOTE 5 VENT
DISCHARGE 2" 150 RAISED Side DRAIN
BAL. DRUM N/A
INSTRUMENTATION (NOTE 2) PRESSURE GAUGE TYPE TEMPERATURE GAUGE TYPE
TEMP & PRESSURE LOCATION THERMOWELLS TYPE
PRESSURE SWITCH TYPE LOCATION(S)
LOCATION ACCELEROMETER
VIBRATION MOUNTING PROVISION ONLY MOUNTING ONLY NON CONTACT

9755-DAT-ME-010
Equipment Data Sheet
CENTRIFUGAL PUMPS 2 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-010
Proposal Curve No Sheet 2 of 3
Item Description Water Drain Sump Pump, Pipe Trench No. of Units 1 (Tag No. P2971)

API 610 Material Classification S-1 BEARING HOUSING STA


BARREL/CASING STA WEAR RINGS STA
MATERIALS

SHAFT STA SHAFT SLEEVE STA


IMPELLER STA MOUNTING PLATE Fabricated Steel
GASKETS Non Asbestos

TYPE NOTE 3
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 3 PHASE HERTZ ENCLOSURE NOTE 3
kW RATING STA VERTICAL HORIZONTAL
DRIVER

SPEED rev / min STA EFFICIENCY %


MINIMUM STARTING VOLTAGE INSULATION NOTE 3
DRIVER

FULL LOAD AMPS LOCKED ROTOR AMPS


STARTING METHOD TEMP. RISE deg C
BEARINGS STA LUBRICATION STA
VERTICAL SHAFT SOLID HOLLOW
VERTICAL THRUST UPWARD DOWNWARD
REMARKS

VERTICAL PUMPS UP DOWN SEPARATE MOUNTING PLATE NOTE 5


PUMP THRUST N DRIVER ALIGNMENT SCREWS Required
AT MIN FLOW N PIT OR SUMP DEPTH m 3.0m below mount plate level
AT DESIGN FLOW N PUMP LENGTH m 2.7
VERTICAL PUMPS

AT RUNOUT N MIN SUBMERGENCE m STA


MAX THRUST N COLUMN PIPE FLANGED ü THREADED
FLOW RATE m3/hr 10 LINE SHAFT OPEN ENCLOSED ü
GUIDE BUSHINGS BOWL LINE SHAFT
GUIDE BUSHINGS LUBRICATION WATER OIL GREASE PUMPAGE ü

REMARKS DRAIN TANK PUMP YES


NO ü
SURFACE PREPARATION AND PAINTING NOTE 4
SURFACE PREPARATION

PUMP MOTOR MOUNTING PLATE OTHER


SupplierS STANDARD
& PAINTING

SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS

WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT

WEIGHT OF MOTOR kg STA


REMARKS WEIGHT OF BASEPLATE kg STA

CODES AND STANDARDS


CODES AND STANDARDS

CASING IMPELLER SHAFT OTHER


MATL. CERTIFICATION REQ'D: ü ü ü
NOZZLE WELD INSPECTION. MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CASTING INSPECTION MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CHARPY TESTS REQUIRED ITEMS
APPLICABLE CODES
REMARKS

9755-DAT-ME-010
Equipment Data Sheet
CENTRIFUGAL PUMPS 3 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-010
Proposal Curve No Sheet 3 of 3
Item Description Water Drain Sump Pump, Pipe Trench No. of Units 1 (Tag No. P2971)

QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA

PERFORMANCE CURVE APPR. DATE COMMENTS

SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE

HYDROTEST ü
PERFORMANCE ü
NPSH
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST

TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER

VENDOR TO SUBMIT TEST DATE COMMENTS


PROCEDURES

ENVIRONMENTAL & SITE DATA


ENVIRONMENTAL & SITE DATA

LOCATION INDOOR OUTDOOR UNDER ROOF PARTIAL SIDES


GRADE MEZZANINE HEATED UNHEATED
WINTERISATION REQUIRED NO TROPICALISATION REQUIRED YES
ELECTRICAL AREA ZONE NOTE 3 GAS GROUP NOTE 3 TEMPERATURE CLASS NOTE 3
CLASSIFICATION

SITE DATA ELEVATION - 0 m ATMOSPHERE - Tropical


AMBIENT TEMPERATURE deg C MINIMUM 10 NORMAL 30 MAXIMUM 70
RELATIVE HUMIDITY % MINIMUM NORMAL MAXIMUM 100

Note 1 The pump shown on this Data Sheet will be used to transfer water from a pipe trench drain sump to an oily water drainage system.
Note 2 See project design base memorandum and P&ID drawings for full details of pump monitoring and control instrumentation.
Note 3 See Data Sheet 9755-DAT-EL-003
Note 4 Pumpsets to be prepared and painted in accordance with project specification 9755-SPC-CP-007.
NOTES

Note 5 Mounting plate to be suitable for galvanised open mesh platform affixed level with top of wall at +1.3m AOD.
Sump depth = - 1.7m AOD.
Note 6 Tests on one pump of each type to be witnessed by the Purchaser.
Note 7 STA = Supplier to add details.

REMARKS

9755-DAT-ME-010
Equipment Data Sheet
CENTRIFUGAL PUMPS 1 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-009
Proposal Curve No Sheet 1 of 3
Item Description Water Drain Sump Pump, Slab (Hydrant Shelter) No. of Units 1 (Tag No. P2970)

Revision A B
Issue IDC Implementation Issue
Date 3/13/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client

LIQUID Water or Jet fuel


VISCOSITY cSt @ 5oC 1 S G @ 5oC 1 SP. HEAT (kJ/kg deg C) N/A
PROCESS
DATA

REID VAPOUR PRESSURE psia MIN NORMAL Negligible MAX


PUMPING TEMP. °C MIN + 10 NORMAL + 20 MAX + 30
H2S CONCENTRATION ppm MIN N/A NORMAL N/A MAX N/A
CHLORIDES ppm N/A CORROSIVE / EROSIVE AGENT N/A
LIQUIDS Type TOXIC ü FLAMMABLE ü OTHER N/A

CAPACITY (NOTE 1) m3/hr MIN RATED 1 MAX


MINIMUM CONTINUOUS FLOW THERMAL m3/hr
STABLE m3/hr
DESIGN

SUCTION PRESSURE BARG RATED Flooded suction MAXIMUM


DISCHARGE PRESS. BARG 0.25 DIFFERENTIAL PRESS. BARG
DIFFERENTIAL HEAD m 2.53 NPSH REQUIRED - RATED CAP m H2O
MAX HEAD-RATED IMPELLER m STA SUCTION SPECIFIC SPEED STA
MAX POWER-RATED IMPLLER. kW STA MAX SOUND PRESS. LEVEL 85 dBA
POWER REQUIRED kW STA SPEED rev/min STA ROTATION : STA
PUMPS TO OPERATE AS ELEC. MOTOR Required GEAR BOX N/A
DUTY ONLY ELEC MOTOR BY Pump Manufacturer FLUID COUPLING BY N/A
MOTOR MOUNTED BY Pump Manufacturer FLUID COUPLING MOUNTED BY N/A
DATA SHEETS ELEC MOTOR 9755-DAT-EL-003 FLUID COUPLING N/A
IMPELLER CASING CASING SPLIT
TYPE CLOSED, RADIAL FLOW SINGLE VOLUTE AXIAL
DIAMETER mm STA DOUBLE VOLUTE RADIAL ü
BETWEEN BEARINGS VERTICAL SINGLE CASING ü
OVERHUNG MOUNTNG CENTRELINE VERTICAL FOOT MOUNTING
NEAR CENTRELINE IN LINE SUMP PLATE
MECHANICAL SEALS BEARINGS SLEEVE ROLLER BALL
CONSTRUCTION

TYPE : SINGLE ü RADIAL BEARINGS STA


DUAL THRUST BEARINGS STA
DOUBLE LUBRICATION STA
Supplier STA
COUPLING MAKE STA COUPLING GUARD YES NO
MODEL STA
RATING
CONNECTIONS SIZE ANSI FLANGE POSITION OTHER CONNECTIONS
RATING FACE NO. SIZE TYPE
SUCTION NOTE 5 VENT
DISCHARGE 2" 150 RAISED Side DRAIN
BAL. DRUM N/A
INSTRUMENTATION (NOTE 2) PRESSURE GAUGE TYPE TEMPERATURE GAUGE TYPE
TEMP & PRESSURE LOCATION THERMOWELLS TYPE
PRESSURE SWITCH TYPE LOCATION(S)
LOCATION ACCELEROMETER
VIBRATION MOUNTING PROVISION ONLY MOUNTING ONLY NON CONTACT

9755-DAT-ME-009
Equipment Data Sheet
CENTRIFUGAL PUMPS 2 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-009
Proposal Curve No Sheet 2 of 3
Item Description Water Drain Sump Pump, Slab (Hydrant Shelter) No. of Units 1 (Tag No. P2970)

API 610 Material Classification S-1 BEARING HOUSING STA


BARREL/CASING STA WEAR RINGS STA
MATERIALS

SHAFT STA SHAFT SLEEVE STA


IMPELLER STA MOUNTING PLATE Fabricated Steel
GASKETS Non Asbestos

TYPE NOTE 3
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 3 PHASE HERTZ ENCLOSURE NOTE 3
kW RATING STA VERTICAL HORIZONTAL
DRIVER

SPEED rev / min STA EFFICIENCY %


MINIMUM STARTING VOLTAGE INSULATION NOTE 3
DRIVER

FULL LOAD AMPS LOCKED ROTOR AMPS


STARTING METHOD TEMP. RISE deg C
BEARINGS STA LUBRICATION STA
VERTICAL SHAFT SOLID HOLLOW
VERTICAL THRUST UPWARD DOWNWARD
REMARKS

VERTICAL PUMPS UP DOWN SEPARATE MOUNTING PLATE NOTE 5


PUMP THRUST N DRIVER ALIGNMENT SCREWS Required
AT MIN FLOW N PIT OR SUMP DEPTH m 0.5
AT DESIGN FLOW N PUMP LENGTH m STA
VERTICAL PUMPS

AT RUNOUT N MIN SUBMERGENCE m STA


MAX THRUST N COLUMN PIPE FLANGED ü THREADED
FLOW RATE m3/hr 1 LINE SHAFT OPEN ENCLOSED ü
GUIDE BUSHINGS BOWL LINE SHAFT
GUIDE BUSHINGS LUBRICATION WATER OIL GREASE PUMPAGE ü

REMARKS DRAIN TANK PUMP YES


NO ü
SURFACE PREPARATION AND PAINTING NOTE 4
SURFACE PREPARATION

PUMP MOTOR MOUNTING PLATE OTHER


MANUFACTURERS STANDARD
& PAINTING

SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS

WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT

WEIGHT OF MOTOR kg STA


REMARKS WEIGHT OF BASEPLATE kg STA

CODES AND STANDARDS


CODES AND STANDARDS

CASING IMPELLER SHAFT OTHER


MATL. CERTIFICATION REQ'D: ü ü ü
NOZZLE WELD INSPECTION. MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CASTING INSPECTION MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CHARPY TESTS REQUIRED ITEMS
APPLICABLE CODES
REMARKS

9755-DAT-ME-009
Equipment Data Sheet
CENTRIFUGAL PUMPS 3 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-009
Proposal Curve No Sheet 3 of 3
Item Description Water Drain Sump Pump, Slab (Hydrant Shelter) No. of Units 1 (Tag No. P2970)

QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA

PERFORMANCE CURVE APPR. DATE COMMENTS

SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE

HYDROTEST ü
PERFORMANCE ü
NPSH
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST

TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER

VENDOR TO SUBMIT TEST DATE COMMENTS


PROCEDURES

ENVIRONMENTAL & SITE DATA


ENVIRONMENTAL & SITE DATA

LOCATION INDOOR OUTDOOR UNDER ROOF PARTIAL SIDES


GRADE MEZZANINE HEATED UNHEATED
WINTERISATION REQUIRED NO TROPICALISATION REQUIRED YES
ELECTRICAL AREA ZONE NOTE 3 GAS GROUP NOTE 3 TEMPERATURE CLASS NOTE 3
CLASSIFICATION

SITE DATA ELEVATION - 0 m ATMOSPHERE - Tropical


AMBIENT TEMPERATURE deg C MINIMUM 10 NORMAL 30 MAXIMUM 50
RELATIVE HUMIDITY % MINIMUM NORMAL MAXIMUM 100

Note 1 The pump shown on this Data Sheet will be used to transfer water from a slab drain sump to an oily water system.
There could be Jet fuel in the sump occasionally.
Note 2 See project design base memorandum and P&ID drawings for full details of pump monitoring and control instrumentation.
Note 3 See Data Sheet 9755-DAT-EL-003
NOTES

Note 4 Pumpsets to be prepared and painted in accordance with project specification 9755-SPC-CP-007.
Note 5 Mounting plate to be suitable for galvanised open mesh flooring of drain sump. Sump depth = 0.5m.
Note 6 Tests on one pump of each type to be witnessed by the Purchaser.
Note 7 STA = Supplier to add details.

REMARKS

9755-DAT-ME-009
Equipment Data Sheet
CENTRIFUGAL PUMPS 1 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-008
Proposal Curve No Sheet 1 of 3
Item Description Oily Water Separator Pump, Water Sump No. of Units 2 (Tag No. P2931 & P2932)

Revision A B
Issue IDC Implementation Issue
Date 3/13/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client

LIQUID Water
VISCOSITY cSt @ 5oC 1 S G @ 5oC 1 SP. HEAT (kJ/kg deg C) N/A
PROCESS
DATA

REID VAPOUR PRESSURE psia MIN NORMAL Negligible MAX


PUMPING TEMP. °C MIN + 10 NORMAL + 20 MAX + 30
H2S CONCENTRATION ppm MIN N/A NORMAL N/A MAX N/A
CHLORIDES ppm N/A CORROSIVE / EROSIVE AGENT N/A
LIQUIDS Type TOXIC FLAMMABLE OTHER N/A

CAPACITY (NOTE 1) m3/hr MIN 36 RATED 90 MAX


MINIMUM CONTINUOUS FLOW THERMAL m3/hr
STABLE m3/hr
DESIGN

SUCTION PRESSURE BARG RATED Flooded suction MAXIMUM


DISCHARGE PRESS. BARG 0.73 DIFFERENTIAL PRESS. BARG
DIFFERENTIAL HEAD m 7.46 NPSH REQUIRED - RATED CAP m H2O
MAX HEAD-RATED IMPELLER m STA SUCTION SPECIFIC SPEED STA
MAX POWER-RATED IMPLLER. kW STA MAX SOUND PRESS. LEVEL 85 dBA
POWER REQUIRED kW STA SPEED rev/min STA ROTATION : STA
PUMPS TO OPERATE AS ELEC. MOTOR Required GEAR BOX N/A
DUTY AND STANDBY ELEC MOTOR BY Pump Supplier FLUID COUPLING BY N/A
MOTOR MOUNTED BY Pump Supplier FLUID COUPLING MOUNTED BY N/A
DATA SHEETS ELEC MOTOR 9755-DAT-EL-003 FLUID COUPLING N/A
IMPELLER CASING CASING SPLIT
TYPE CLOSED, RADIAL FLOW SINGLE VOLUTE AXIAL
DIAMETER mm STA DOUBLE VOLUTE RADIAL ü
BETWEEN BEARINGS VERTICAL SINGLE CASING ü
OVERHUNG MOUNTNG CENTRELINE VERTICAL FOOT MOUNTING
NEAR CENTRELINE IN LINE SUMP PLATE
MECHANICAL SEALS BEARINGS SLEEVE ROLLER BALL
CONSTRUCTION

TYPE : SINGLE ü RADIAL BEARINGS STA


DUAL THRUST BEARINGS STA
DOUBLE LUBRICATION STA
Supplier STA
COUPLING MAKE STA COUPLING GUARD YES NO
MODEL STA
RATING
CONNECTIONS SIZE ANSI FLANGE POSITION OTHER CONNECTIONS
RATING FACE NO. SIZE TYPE
SUCTION NOTE 5 VENT
DISCHARGE 3" 150 RAISED Side DRAIN
BAL. DRUM N/A
INSTRUMENTATION (NOTE 2) PRESSURE GAUGE TYPE TEMPERATURE GAUGE TYPE
TEMP & PRESSURE LOCATION THERMOWELLS TYPE
PRESSURE SWITCH TYPE LOCATION(S)
LOCATION ACCELEROMETER
VIBRATION MOUNTING PROVISION ONLY MOUNTING ONLY NON CONTACT

9755-DAT-ME-008
Equipment Data Sheet
CENTRIFUGAL PUMPS 2 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-008
Proposal Curve No Sheet 2 of 3
Item Description Oily Water Separator Pump, Water Sump No. of Units 2 (Tag No. P2931 & P2932)

API 610 Material Classification S-1 BEARING HOUSING STA


BARREL/CASING STA WEAR RINGS STA
MATERIALS

SHAFT STA SHAFT SLEEVE STA


IMPELLER STA MOUNTING PLATE Fabricated Steel
GASKETS Non Asbestos

TYPE NOTE 3
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 3 PHASE HERTZ ENCLOSURE NOTE 3
kW RATING STA VERTICAL HORIZONTAL
DRIVER

SPEED rev / min STA EFFICIENCY %


MINIMUM STARTING VOLTAGE INSULATION NOTE 3
DRIVER

FULL LOAD AMPS LOCKED ROTOR AMPS


STARTING METHOD TEMP. RISE deg C
BEARINGS STA LUBRICATION STA
VERTICAL SHAFT SOLID HOLLOW
VERTICAL THRUST UPWARD DOWNWARD
REMARKS

VERTICAL PUMPS UP DOWN SEPARATE MOUNTING PLATE NOTE 5


PUMP THRUST N DRIVER ALIGNMENT SCREWS Required
AT MIN FLOW N PIT OR SUMP DEPTH m 4.975
AT DESIGN FLOW N PUMP LENGTH m 4.730
VERTICAL PUMPS

AT RUNOUT N MIN SUBMERGENCE m STA


MAX THRUST N COLUMN PIPE FLANGED ü THREADED
FLOW RATE m3/hr 90 LINE SHAFT OPEN ENCLOSED ü
GUIDE BUSHINGS BOWL LINE SHAFT
GUIDE BUSHINGS LUBRICATION WATER OIL GREASE PUMPAGE ü

REMARKS DRAIN TANK PUMP YES


NO ü
SURFACE PREPARATION AND PAINTING NOTE 4
SURFACE PREPARATION

PUMP MOTOR MOUNTING PLATE OTHER


SupplierS STANDARD
& PAINTING

SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS

WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT

WEIGHT OF MOTOR kg STA


REMARKS WEIGHT OF BASEPLATE kg STA

CODES AND STANDARDS


CODES AND STANDARDS

CASING IMPELLER SHAFT OTHER


MATL. CERTIFICATION REQ'D: ü ü ü
NOZZLE WELD INSPECTION. MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CASTING INSPECTION MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CHARPY TESTS REQUIRED ITEMS
APPLICABLE CODES
REMARKS

9755-DAT-ME-008
Equipment Data Sheet
CENTRIFUGAL PUMPS 3 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-008
Proposal Curve No Sheet 3 of 3
Item Description Oily Water Separator Pump, Water Sump No. of Units 2 (Tag No. P2931 & P2932)

QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA

PERFORMANCE CURVE APPR. DATE COMMENTS

SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE

HYDROTEST ü
PERFORMANCE ü
NPSH
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST

TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER

VENDOR TO SUBMIT TEST DATE COMMENTS


PROCEDURES

ENVIRONMENTAL & SITE DATA


ENVIRONMENTAL & SITE DATA

LOCATION INDOOR OUTDOOR UNDER ROOF PARTIAL SIDES


GRADE MEZZANINE HEATED UNHEATED
WINTERISATION REQUIRED NO TROPICALISATION REQUIRED YES
ELECTRICAL AREA ZONE NOTE 3 GAS GROUP NOTE 3 TEMPERATURE CLASS NOTE 3
CLASSIFICATION

SITE DATA ELEVATION - 0 m ATMOSPHERE - Tropical


AMBIENT TEMPERATURE deg C MINIMUM 10 NORMAL 30 MAXIMUM 70
RELATIVE HUMIDITY % MINIMUM NORMAL MAXIMUM 100

Note 1 The pump shown on this Data Sheet will be used to transfer water from a separator water sump to an open drain sump.
Note 2 See project design base memorandum and P&ID drawings for full details of pump monitoring and control instrumentation.
Note 3 See Data Sheet 9755-DAT-EL-003
Note 4 Pumpsets to be prepared and painted in accordance with project specification 9755-SPC-CP-007.
NOTES

Note 5 See drawing 9755/CI/2/4530. Mounting plate to be suitable for galvanised open mesh flooring of intercepter.
Note 6 Tests on one pump of each type to be witnessed by the Purchaser.
Note 7 STA = Supplier to add details.

REMARKS

9755-DAT-ME-008
Equipment Data Sheet
CENTRIFUGAL PUMPS 1 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-007
Proposal Curve No Sheet 1 of 3
Item Description Oily Water Separator Pump, Oil Sump No. of Units 1 (Tag No. P2930)

Revision A B
Issue IDC Implementation Issue
Date 3/13/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client

LIQUID Jet A1 fuel


VISCOSITY cSt @ 5oC 2.2 S G @ 5oC 0.8 SP. HEAT (kJ/kg deg C) N/A
PROCESS
DATA

REID VAPOUR PRESSURE psia MIN NORMAL Negligible MAX


PUMPING TEMP. °C MIN + 10 NORMAL + 20 MAX + 30
H2S CONCENTRATION ppm MIN N/A NORMAL N/A MAX N/A
CHLORIDES ppm N/A CORROSIVE / EROSIVE AGENT N/A
LIQUIDS Type TOXIC ü FLAMMABLE ü OTHER N/A

CAPACITY (NOTE 1) m3/hr MIN 1.2 RATED 3 MAX


MINIMUM CONTINUOUS FLOW THERMAL m3/hr
STABLE m3/hr
DESIGN

SUCTION PRESSURE BARG RATED Flooded suction MAXIMUM


DISCHARGE PRESS. BARG 0.92 DIFFERENTIAL PRESS. BARG
DIFFERENTIAL HEAD m 11.69 NPSH REQUIRED - RATED CAP m H2O
MAX HEAD-RATED IMPELLER m STA SUCTION SPECIFIC SPEED STA
MAX POWER-RATED IMPLLER. kW STA MAX SOUND PRESS. LEVEL 85 dBA
POWER REQUIRED kW STA SPEED rev/min STA ROTATION : STA
PUMPS TO OPERATE AS ELEC. MOTOR Required GEAR BOX N/A
DUTY ONLY ELEC MOTOR BY Pump Supplier FLUID COUPLING BY N/A
MOTOR MOUNTED BY Pump Supplier FLUID COUPLING MOUNTED BY N/A
DATA SHEETS ELEC MOTOR 9755-DAT-EL-003 FLUID COUPLING N/A
IMPELLER CASING CASING SPLIT
TYPE CLOSED, RADIAL FLOW SINGLE VOLUTE AXIAL
DIAMETER mm STA DOUBLE VOLUTE RADIAL ü
BETWEEN BEARINGS VERTICAL SINGLE CASING ü
OVERHUNG MOUNTNG CENTRELINE VERTICAL FOOT MOUNTING
NEAR CENTRELINE IN LINE SUMP PLATE
MECHANICAL SEALS BEARINGS SLEEVE ROLLER BALL
CONSTRUCTION

TYPE : SINGLE ü RADIAL BEARINGS STA


DUAL THRUST BEARINGS STA
DOUBLE LUBRICATION STA
Supplier STA
COUPLING MAKE STA COUPLING GUARD YES NO
MODEL STA
RATING
CONNECTIONS SIZE ANSI FLANGE POSITION OTHER CONNECTIONS
RATING FACE NO. SIZE TYPE
SUCTION NOTE 5 VENT
DISCHARGE 2" 150 RAISED Side DRAIN
BAL. DRUM N/A
INSTRUMENTATION (NOTE 2) PRESSURE GAUGE TYPE TEMPERATURE GAUGE TYPE
TEMP & PRESSURE LOCATION THERMOWELLS TYPE
PRESSURE SWITCH TYPE LOCATION(S)
LOCATION ACCELEROMETER
VIBRATION MOUNTING PROVISION ONLY MOUNTING ONLY NON CONTACT

9755-DAT-ME-007
Equipment Data Sheet
CENTRIFUGAL PUMPS 2 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-007
Proposal Curve No Sheet 2 of 3
Item Description Oily Water Separator Pump, Oil Sump No. of Units 1 (Tag No. P2930)

API 610 Material Classification S-1 BEARING HOUSING STA


BARREL/CASING STA WEAR RINGS STA
MATERIALS

SHAFT STA SHAFT SLEEVE STA


IMPELLER STA MOUNTING PLATE Fabricated Steel
GASKETS Non Asbestos

TYPE NOTE 3
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 3 PHASE HERTZ ENCLOSURE NOTE 3
kW RATING STA VERTICAL HORIZONTAL
DRIVER

SPEED rev / min STA EFFICIENCY %


MINIMUM STARTING VOLTAGE INSULATION NOTE 3
DRIVER

FULL LOAD AMPS LOCKED ROTOR AMPS


STARTING METHOD TEMP. RISE deg C
BEARINGS STA LUBRICATION STA
VERTICAL SHAFT SOLID HOLLOW
VERTICAL THRUST UPWARD DOWNWARD
REMARKS

VERTICAL PUMPS UP DOWN SEPARATE MOUNTING PLATE NOTE 5


PUMP THRUST N DRIVER ALIGNMENT SCREWS Required
AT MIN FLOW N PIT OR SUMP DEPTH m 4.975
AT DESIGN FLOW N PUMP LENGTH m 4.730
VERTICAL PUMPS

AT RUNOUT N MIN SUBMERGENCE m STA


MAX THRUST N COLUMN PIPE FLANGED ü THREADED
FLOW RATE m3/hr 3 LINE SHAFT OPEN ENCLOSED ü
GUIDE BUSHINGS BOWL LINE SHAFT
GUIDE BUSHINGS LUBRICATION WATER OIL GREASE PUMPAGE ü

REMARKS DRAIN TANK PUMP YES


NO ü
SURFACE PREPARATION AND PAINTING NOTE 4
SURFACE PREPARATION

PUMP MOTOR MOUNTING PLATE OTHER


SupplierS STANDARD
& PAINTING

SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS

WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT

WEIGHT OF MOTOR kg STA


REMARKS WEIGHT OF BASEPLATE kg STA

CODES AND STANDARDS


CODES AND STANDARDS

CASING IMPELLER SHAFT OTHER


MATL. CERTIFICATION REQ'D: ü ü ü
NOZZLE WELD INSPECTION. MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CASTING INSPECTION MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CHARPY TESTS REQUIRED ITEMS
APPLICABLE CODES
REMARKS

9755-DAT-ME-007
Equipment Data Sheet
CENTRIFUGAL PUMPS 3 OF 3

Client Bangkok Aviation Fuel Services Job No : PJ9755A


Location Aviation Fuel Depot Doc No : 9755-DAT-ME-007
Proposal Curve No Sheet 3 of 3
Item Description Oily Water Separator Pump, Oil Sump No. of Units 1 (Tag No. P2930)

QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA

PERFORMANCE CURVE APPR. DATE COMMENTS

SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE

HYDROTEST ü
PERFORMANCE ü
NPSH
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST

TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER

VENDOR TO SUBMIT TEST DATE COMMENTS


PROCEDURES

ENVIRONMENTAL & SITE DATA


ENVIRONMENTAL & SITE DATA

LOCATION INDOOR OUTDOOR UNDER ROOF PARTIAL SIDES


GRADE MEZZANINE HEATED UNHEATED
WINTERISATION REQUIRED NO TROPICALISATION REQUIRED YES
ELECTRICAL AREA ZONE NOTE 3 GAS GROUP NOTE 3 TEMPERATURE CLASS NOTE 3
CLASSIFICATION

SITE DATA ELEVATION - 0 m ATMOSPHERE - Tropical


AMBIENT TEMPERATURE deg C MINIMUM 10 NORMAL 30 MAXIMUM 70
RELATIVE HUMIDITY % MINIMUM NORMAL MAXIMUM 100

Note 1 The pump shown on this Data Sheet will be used to transfer fuel from a separator oil sump to a hose line.
Note 2 See project design base memorandum and P&ID drawings for full details of pump monitoring and control instrumentation.
Note 3 See Data Sheet 9755-DAT-EL-003
Note 4 Pumpsets to be prepared and painted in accordance with project specification 9755-SPC-CP-007.
NOTES

Note 5 See drawing 9755/CI/2/4530. Mounting plate to be suitable for galvanised open mesh flooring of intercepter.
Note 6 Tests on one pump of each type to be witnessed by the Purchaser.
Note 7 STA = Supplier to add details.

REMARKS

9755-DAT-ME-007
Equipment Data Sheet
CENTRIFUGAL PUMPS

Client PT TRANSPORTASI GAS INDONESIA (TGI) Job No : 50002AW


Location Jabung GAS Booster Station Doc No : 22-DS-R-003
Tag No. 22-P-2210 Sheet 1 of 3
Item Description DIESEL FUEL LOADING PUMP - ELECTRICALLY DRIVEN No. of Units 1

Revision A 0
Issue Preliminary Issue Approved for Design
Date 2/21/2006 2/24/2006
By NMC NMC
Checked DWA DWA
Approved AJG AJG
Client

LIQUID Diesel
VISCOSITY cSt @ 59oF 2.1 S G @ 59oF 0.84 SP. HEAT (kJ/kg deg C) 1.8
PROCESS
DATA

REID VAPOUR PRESSURE psia MIN NORMAL Negligible MAX


PUMPING TEMP. °F MIN + 77 NORMAL + 85 MAX + 95
H2S CONCENTRATION ppm MIN N/A NORMAL N/A MAX N/A
CHLORIDES ppm N/A CORROSIVE / EROSIVE AGENT N/A
LIQUIDS Type TOXIC ü FLAMMABLE ü OTHER N/A

CAPACITY (NOTE 1) m3/hr MIN 5.1 RATED 17 MAX 19.55


MINIMUM CONTINUOUS FLOW THERMAL m3/hr API CODE No. OH2
STABLE 17 m3/hr
DESIGN

SUCTION HEAD m RATED -8 MAXIMUM


DISCHARGE PRESS. barg 0 DISCHARGE HEAD m 6.28
DIFFERENTIAL HEAD m 14.5 NPSH AVAILBLE (m) NPSH REQUIRED (m) 4
MAX HEAD-RATED IMPELLER m STA SUCTION SPECIFIC SPEED (Max @ BEP- SI Units) STA
MAX POWER-RATED IMPLLER. kW STA MAX SOUND PRESS. LEVEL @ 1 Metre 85 dBA
HYDRAULIC POWER REQUIRED kW STA SPEED rev/min STA ROTATION : STA
PUMPS TO OPERATE AS ELEC. MOTOR - REQ'D FLUID COUPLING - N/A GEAR BOX N/A
DUTY ONLY ELEC MOTOR BY Pump Supplier FLUID COUPLING BY N/A
MOTOR MOUNTED BY Pump Supplier FLUID COUPLING MOUNTED BY N/A
FLUID COUPLING N/A
IMPELLER CASING CASING SPLIT
TYPE CLOSED, RADIAL FLOW SINGLE VOLUTE ü AXIAL
DIAMETER mm STA DOUBLE VOLUTE RADIAL ü
BETWEEN BEARINGS VERTICAL DOUBLE CASING
OVERHUNG ü MOUNTNG CENTRELINE VERTICAL FOOT MOUNTING
NEAR CENTRELINE IN LINE SUMP PLATE
MECHANICAL SEALS BEARINGS SLEEVE ROLLER BALL
CONSTRUCTION

API SEAL CODE STA RADIAL BEARINGS STA


TYPE (NOTE 2) STA THRUST BEARINGS STA
SUPPLIER STA LUBRICATION FORCED STA SEAL STA

COUPLING MAKE Spacer Type, Flexibox/Thomas or Equal COUPLING GUARD YES NO


MODEL STA
RATING
CONNECTIONS SIZE ANSI FLANGE POSITION OTHER CONNECTIONS
RATING FACE NO. SIZE TYPE
SUCTION 2" 150 RAISED END VENT STA Valved and

DISCHARGE 2" 150 RAISED TOP DRAIN STA Flanged to

BAL. DRUM N/A Edge of B'plate

INSTRUMENTATION (NOTE 3) PRESSURE GAUGE TYPE TEMPERATURE GAUGE TYPE


TEMP & PRESSURE LOCATION THERMOWELLS TYPE
PRESSURE SWITCH TYPE LOCATION(S)
LOCATION ACCELEROMETER
VIBRATION MOUNTING PROVISION ONLY MOUNTING ONLY NON CONTACT

680212567.xls
Equipment Data Sheet
CENTRIFUGAL PUMPS

Client PT TRANSPORTASI GAS INDONESIA (TGI) Job No : 50002AW


Location Jabung GAS Booster Station Doc No : 22-DS-R-003
Tag No. 22-P-2210 Sheet 2 of 3
Item Description DIESEL FUEL LOADING PUMP - ELECTRICALLY DRIVEN No. of Units 1

API 610 Material Classification S-6 BEARING HOUSING STA


BARREL/CASING STA WEAR RINGS STA
MATERIALS

SHAFT STA SHAFT SLEEVE STA


IMPELLER STA BASE PLATE Fabricated Steel
DIFFUSERS GASKETS Non Asbestos

TYPE NOTE 3
SUPPLIER STA TYPE STA FRAME STA
VOLTS NOTE 4 PHASE HERTZ ENCLOSURE NOTE 3
kW RATING STA VERTICAL HORIZONTAL
SPEED rev / min STA EFFICIENCY %
MINIMUM STARTING VOLTAGE INSULATION NOTE 4
DRIVER

FULL LOAD AMPS LOCKED ROTOR AMPS


STARTING METHOD TEMP. RISE deg C
BEARINGS STA LUBRICATION STA
VERTICAL SHAFT SOLID HOLLOW
VERTICAL THRUST UPWARD DOWNWARD
REMARKS

VERTICAL PUMPS UP DOWN SEPARATE MOUNTING PLATE


PUMP THRUST N DRIVER ALIGNMENT SCREWS
AT MIN FLOW N PIT OR SUMP DEPTH m
AT DESIGN FLOW N PUMP LENGTH m
VERTICAL PUMPS

AT RUNOUT N MIN SUBMERGENCE REQD. m


MAX THRUST N COLUMN PIPE FLANGED THREADED
FLOW RATE m3/hr LINE SHAFT OPEN ENCLOSED
GUIDE BUSHINGS BOWL LINE SHAFT
GUIDE BUSHINGS LUBRICATION WATER OIL GREASE PUMPAGE

REMARKS

SURFACE PREPARATION AND PAINTING NOTE 5


SURFACE PREPARATION

PUMP MOTOR BASE PLATE OTHER


SUPPLIER'S STANDARD
& PAINTING

SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS

WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT

WEIGHT OF MOTOR kg STA


REMARKS WEIGHT OF BASEPLATE kg STA

CODES AND STANDARDS


CODES AND STANDARDS

CASING IMPELLER SHAFT OTHER


MATL. CERTIFICATION REQ'D: ü ü ü
NOZZLE WELD INSPECTION. MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CASTING INSPECTION MAG.PARTICLE LIQ. PENETR. RADIOGRAPH. ULTRASON.
CHARPY TESTS REQUIRED ITEMS
APPLICABLE CODES
REMARKS

680212567.xls
Equipment Data Sheet
CENTRIFUGAL PUMPS

Client PT TRANSPORTASI GAS INDONESIA (TGI) Job No : 50002AW


Location Jabung GAS Booster Station Doc No : 22-DS-R-003
Tag No. 22-P-2210 Sheet 3 of 3
Item Description DIESEL FUEL LOADING PUMP - ELECTRICALLY DRIVEN No. of Units 1

QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA

PERFORMANCE CURVE APPR. DATE COMMENTS

SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 7/9 OBSERVE

HYDROTEST ü
PERFORMANCE ü
NPSH ü
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST ü
DISMANTLE & INSPECT AFTER ü
TEST

TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER

VENDOR TO SUBMIT TEST DATE COMMENTS


PROCEDURES

ENVIRONMENTAL & SITE DATA


ENVIRONMENTAL & SITE DATA

LOCATION INDOOR OUTDOOR UNDER ROOF PARTIAL SIDES


GRADE MEZZANINE HEATED UNHEATED
WINTERISATION REQUIRED NO TROPICALISATION REQUIRED YES
ELECTRICAL AREA ZONE NOTE 4 GAS GROUP NOTE 4 TEMPERATURE CLASS NOTE 4
CLASSIFICATION

SITE DATA ELEVATION: 13 m


AMBIENT TEMPERATURE deg F MINIMUM 77 NORMAL 85 MAXIMUM 95
RELATIVE HUMIDITY % MINIMUM 60 NORMAL 80 MAXIMUM 100

Note 1 The pump shown on this Data Sheet will be used to transfer fuel from road tankers.

Note 2 Pumps are to be equipped with hydraulically balanced mechanical seals with dry running standby seals for enhanced safety.
Note 3 See project specification 22-SP-R-003 and P&ID drawings for full details of pump monitoring and control instrumentation.
NOTES

Note 4 Pumpsets to be in accordance with Project Specification 22-SP-R-003


Note 5 Pumpsets to be prepared and painted in accordance with Project Specification 22-SP-C-001
Note 6 Manufacturer's standard material quality control procedures to apply
Note 7 Tests on all pumps to be witnessed by the Owner at Supplier's works.
Note 8 STA = Supplier to Advise.
Note 9 Supplier to undertake 4 hour test with contract motor for vibration and bearing temperature measurement. Owner to witness
Note 10 Data Sheet to be completed in API format by Supplier/Manufacturer/Contractor as appropriate.
REMARKS

This Data Sheet to be read in conjunction with Project Specification 22-SP-R-003

680212567.xls