Lal Pir (Pvt) Ltd /AES PAK GEN (Pvt)

COMPANY

Turbine Log Sheet


Unit :Lalpir
Date;- Wednesday, January 2, 2008 Date;- Thursday, January 3, 2008 Date;- Friday, January 4, 2008

Set
Parameters
Point
Units 2:00 8:00 14:00 20:00 2:00 8:00 14:00 20:00 2:00 8:00 14:00 20:00
Load MW 370 371 370 370 370 370 369 369 370 370 370 370

Condensate Pumps
Condensate Pump A
Motor oil level (L-N-H ) 50% N N N N N N N N N N N N

Suction strainer diff. press. <0.5 kg/cm2 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1

Suction pressure. --0.49 kg/cm2 -0.78 -0.77 -0.80 -0.80 -0.79 -0.78 -0.77 -0.78 -0.79 -0.79 -0.79 -0.80

Discharge pressure. >22.5 kg/cm2 21.5 21.6 22 22 22 22.5 23 22.4 22.3 22.3 22.3 22.5

Sealing water pressure. 2.0--4.0 kg/cm 2


4 4 4 4 4 4 4 4 4 4 4 4

Condensate Pump B
Motor oil level (L-N-H ) 50% N N N N N N N N N N N N
Suction strainer diff. press. <0.5 kg/cm2 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15

Suction pressure. --0.49 kg/cm2 -0.77 -0.78 -0.90 -0.90 -0.90 -0.90 -0.90 -0.81 -0.90 -0.80 -0.80 -0.81

Discharge pressure. >22.5 kg/cm2 22 22.5 23 23 22.5 22.6 23 22.5 22.2 22.2 22.5 22.2

Sealing water pressure. 2.0--4.0 kg/cm 2


4 4 4 4 4 4 4 4 4 4 4 4

Condensate Pump C
Motor oil level (L-N-H ) 50% N N N N N N N N N N N N

Suction strainer diff. press. <0.5 kg/cm2

Suction pressure. --0.49 kg/cm2


y

By

By

By

y
By

By

By

By
B

B
d

nd

d
an

an

an

an

an

an

an

an

an

an

an

an
Discharge pressure. >22.5 kg/cm2
a
St

St

St

St

St

St

St

St

St

St

St

St
St

Sealing water pressure. 2.0--4.0 kg/cm2

Condenser
Condr. vacuum (turbine floor) >650 mm Hg 690 690 688 690 690 690 686 688 690 690 685 685

Condr. CW inlet press. (south) 2 kg/cm2 1.55 1.55 1.6 1.6 1.6 1.65 1.65 1.67 1.68 1.68 1.68 1.67

Condr. CW inlet press. (north) 2 kg/cm2 1.6 1.61 1.7 1.7 1.7 1.7 1.7 1.69 1.66 1.66 1.66 1.65

Condr. CW outlet press. (south) 1.4 kg/cm2 1.1 1.1 1.15 1.15 1.15 1.1 1.1 1.12 1.11 1.1 1.1 1.11

Condr. CW outlet press. (north) 1.4 kg/cm 2


1.12 1.12 1.2 1.2 1.18 1.15 1.15 1.13 1.12 1.11 1.11 1.12
Lal Pir (Pvt) Ltd /AES PAK GEN (Pvt)
COMPANY

Turbine Log Sheet


Unit :Lalpir
Date Friday, February 1, 2008

Set
Parameters
Point
Units 2:00 8:00 14:00 20:00
Load MW 366 368 369 369

Condensate Pumps
Condensate Pump A
Motor oil level (L-N-H ) 50% N N N N

Suction strainer diff. press. <0.5 kg/cm2

Suction pressure. --0.49 kg/cm2

By

By
By
B

B
d

d
an

an

an

an

an
Discharge pressure. >22.5 kg/cm2

St

St

St

St

St
Sealing water pressure. 2.0--4.0 kg/cm2

Condensate Pump B
Motor oil level (L-N-H ) 50% N N N N
Suction strainer diff. press. <0.5 kg/cm2 0.15 0.15 0.15 0.15

Suction pressure. --0.49 kg/cm2 -0.76 -0.78 -0.79 -0.79

Discharge pressure. >22.5 kg/cm2 22 22 22 22

Sealing water pressure. 2.0--4.0 kg/cm 2


3.1 3 3 3

Condensate Pump C
Motor oil level (L-N-H ) 50% N N N N

Suction strainer diff. press. <0.5 kg/cm2 0.15 0.16 0.16 0.15

Suction pressure. --0.49 kg/cm2 0.88 0.83 0.82 0.82

Discharge pressure. >22.5 kg/cm2 20.5 21 21.5 20.5

Sealing water pressure. 2.0--4.0 kg/cm 2


3.1 3 3 3

Condenser
Condr. vacuum (turbine floor) >650 mm Hg 687 688 680 684

Condr. CW inlet press. (south) 2 kg/cm2 1.65 1.67 1.68 1.65

Condr. CW inlet press. (north) 2 kg/cm2 1.68 1.66 1.66 1.58

Condr. CW outlet press. (south) 1.4 kg/cm2 1.68 1.66 1.66 1.58

Condr. CW outlet press. (north) 1.4 kg/cm 2


1.15 1.14 1.17 1.15