You are on page 1of 1

UP STANDARD DETAIL REFERENCE DRAWINGS

DETAIL OF HEAVY WELDING BOSSES FOR THREADED CONNECTIONS AE-036175

N
AWAY AWAY
CONSTRUCTION-NOTES AND DETAILS FOR ISOMETRIC PIPING
INSULATION DETAILS FOR HOT PIPING
AD-036627
AA-036911

SHOP MATERIALS INSULATION DETAILS FOR COLD PIPING AA-036913

INSTALLATION OF JACK SCREWS FOR FLANGED JOINTS AC-036630

TOWARD TOWARD PT N.B.


NOTES
NO DESCRIPTION (INS) STOCK CODE QTY
1. MATERIAL SHOWN WITH A BROKEN LINE AND SPOOLS LISTED IN THE SAUDI ARAMCO
DOWN
PIPE FABRICATION LIST ARE NOT TO BE FURNISHED BY THE VENDOR.

2. PIPING DETAILS SHALL BE CUT AT ALL POINTS MARKED F.W. (FIELD WELD).

1 PIPE , CS API 5L-B-PSL2 , SMLS , BE , 10 PPPCPVSMBESTD5F 36.8 M 3. EACH FABRICATED SECTION SHALL BE CLEARLY MARKED WITH ITS CODE NUMBER.

STD , B36.10M , FBE INT COATED 4. UNLESS OTHERWISE NOTED. (A) ALL DIMENSIONS ARE TO C OR FACE OF FLANGES.

(B) BOLT HOLES ON FLANGES STRADDLE C . (C) WELDING ELBOWS ARE LONG RADIUS.

5. FABRICATION SHALL BE IN ACCORDANCE WITH SAUDI ARAMCO SPECIFICATION 01-SAMSS-10.


FITTINGS 6. GASKET ALLOWANCE

7. PIPING MATERIAL IS
2 90 LR ELBOW , CS A234-WPB , SMLS , BE , 10 P9LC34SMBESTDE5 2
STD , B16.9 , FBE INT COATED PIPE SIZE SCHEDULE SPECIFICATION

REFER MTO REFER MTO REFER MTO

FLANGES
3 WN FLG , CS A105N , CL150 , FF , STD , 10 PFWC1B15FFSTD5V 10
B16.5 , FBE INT COATED
FOR CONT. SEE 8. WELDING STRESS RELIEF - YES NO
X
SHT 028 PIPE SUPPORTS RADIOGRAPHY % 100% X-RAY SPOT X-RAY 01-SAMSS-10 SHOP FIELD

9. TESTING SHOP HYDROSTATIC TEST - YES NO


E 30331576 4 WEAR PAD FOR PIPE 10 WA01-10-550-CS 1 THE SHOP HYDROSTATIC TEST SHALL BE CARRIED OUT ON PIECES HAVING ALL ENDS
FLANGED.
N 30999990
FLG3 EL +99987 10. ALL PIPING MATERIAL IS IN ACCORDANCE WITH SAUDI ARAMCO ENGINEERING SPECIFICATION
SAES-L-105 CLASS 1LE0U . ALL EXCEPTIONS ARE NOTED ON THE ISOMETRIC.

S7 FIELD MATERIALS 11. INSULATION SHOWN ON DRAWING


REFER BELOW TABLE
1 12. REFER TO HYDROSTATIC TEST DIAGRAM FOR TEST LIMIT AND PRESSURE.

FR05-B-450-250-250-0-E-1 13. FOR SMALL BORE LINES (UPTO 1-1/2" ) DIMENSIONS, ROUTING & SUPPORTING SHALL BE FIELD ADJUSTED.

10"N.B. PT N.B. 14. ALL DIMENSIONS AND COORDINATES ARE IN MM. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS PRIOR TO FABRICATION OF THE SPOOL.
15. FOR INTERNAL LINED PIPE, LINING SHALL BE DONE AFTER SPOOL FABRICATION & COMPLETION OF ALL HOT WORKS.

93 NO DESCRIPTION (INS) STOCK CODE QTY 16. TIE-IN POINTS CO-ORDINATES TO BE VERIFIED BY CONTRACTOR IN FIELD.
17. PAINTING / COATING SHALL BE IN ACCORDANCE WITH SAES-H-001/002 AND PROJECT APPROVED COATING MAP.

S4 GASKETS
18. SEAL WELDING REQUIREMENT OF THREADED JOINTS SHALL BE AS PER CL.NO.9 OF SAES-L-110.
19. WELDS SHALL BE RADIOGRAPHED AS PER SAES-W-012 (FOR LINES WITH DESIGN CODE ASME B31.8/B31.4) &

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL, OR IN PART, SHALL BE OBTAINED FROM THIS DRAWING WITHOUT THE WRITTEN CONSENT OF SAUDI ARAMCO.
WA01-10-550-CS AS PER SAES-W-011 (FOR LINES WITH DESIGN CODE ASME B31.3).

5 GASKET , SYNTHETIC W/ CENTERING RING , 10 PGGNSC20115BL02 5 20. CONSTRUCTION OF PLANT PIPING SHALL BE IN ACCORDANCE WITH SAES-L-350.

41 36 21. ALL INTERFACE CONNECTIONS WITH OTHER PROJECT (WHEREVER APPLICABLE), CO-ORDINATES AND ELEVATIONS

21 01 FULL FACE , 1/16" (1.6 MM) THK , SHALL BE VERIFIED BY CONTRACTOR IN FIELD.

S9 22. INTERNAL FBE LINING CONTRACTOR TO VERIFY AND CONFIRM THE BREAK UP FLANGES PRIOR TO THE SPOOL FABRICATION

1 S7 CL150 , B16.5 , B16.21 23. PLANT COORDINATE SYSTEM HAS BEEN FOLLOWED AS PART OF BI-10-00930.
HIGH POINT OF PLANT DATUM ELEVATION 100.000m WHICH EQUALS 2.05m ABOVE MEAN SEA LEVEL
GL01-10
FR05-B-450-250-250-0-E-1 SPOOLS TO BE FABRICATED BY VENDOR
S8 BOLTS NO. WEIGHT NO. WEIGHT
MARK NO. SIZE MARK NO. SIZE
BP01-C-300-25 S10 S7
PIECES LBS PIECES LBS

FLG3 6 STUD BOLT (CONT) , CR-MO A193-B7 , W/ 2 7/8 PB1BLCSACS16002 60


60 LS01-10 FR05-B-450-250-250-0-E-1
FLG3 GAS5 BLT6 00 SF HVY HEX NUTS , A194-2H , B1.1 ,
S8 12
00 CERAMIC-FLUOROPOLYMER COATED , DIA
0 92 S9
BP01-C-300-25 (IMP) X LEN (MET) - 115 mm Length
46 GL01-10
02
S8 1 S8 PIPE SUPPORTS
BP01-C-300-25 BP01-C-300-25 7 T-POST 10 FR05-B-450-250-250-0-E-1 5
FLG3 GAS5 BLT6
FLG3 60 91 FLG3 GAS5 BLT6
00 8 BASE PLATES ON CONCRETE 10 BP01-C-300-25 5
S7 12 SPOOLS TO BE FABRICATED BY SAUDI ARAMCO
S8 00 FLG3
FR05-B-450-250-250-0-E-1 0 9 GUIDE FOR BARE PIPE 10 GL01-10 2 NO.
MARK NO. SIZE
NO.
MARK NO. SIZE
BP01-C-300-25 PIECES PIECES

46
04
10 LINE STOP FOR BARE PIPE 10 LS01-10 1
S7 2
FR05-B-450-250-250-0-E-1 1 PIECE MARKS
481 89 90 91 92 93
90
FLG3
FOR CONT. SEE 41
REST 85 78
SHT 026 54
E 30321432
1
N 30970900
REFERENCE DRAWINGS
EL +99987
REST DRAWING CONTROL SHEET FOR J.O. 10-00930-0002 RD-086148
10"N.B.
88 02 RA-685466.001
17
PIPING PLAN
2 23 FLG3 GAS5 BLT6
P&ID NA-518622.008
LINE DESIGNATION TABLE RD-912750

89 HYDROSTATIC TEST DIAGRAM RA-901147-001

48 PROJECT PIPING MATERIAL SPECIFICATION RE-685500


1 PIPE SUPPORT STANDARD RE-901041
FLG3 GAS5 BLT6

REVISION VALIDATION

THIS REVISION NO. 00 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION


REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:

10-00930-0002-001

Worley DESIGN CERTIFICATION

ENGG./DATE
(DESIGN AGENCY)
CERTIFIED BY/DATE
REVIEW FOR KEY DRAWINGS
REQUIRED
CONST. AGENCY/DATE
(SAUDI ARAMCO)
OPERATIONS/DATE BY/DATE
OTHER

RAM WAB MKH AMM


04/07/23 04/07/23 04/07/23 04/07/23

07 May 2023 REV.NO. DATE REVISION DESCRIPTION

00 04/07/23 ISSUED FOR CONSTRUCTION

JOB ORDER/EWO NO.


THIS REVISION IS NOT TO BE USED FOR
10-00930-0002
ISSUED FOR CONSTRUCTION
CONSTRUCTION UNTIL CERTIFIED AND DATED

SAUDI ARABIAN OIL COMPANY


DRAWING TYPE
ISO 10"-OW-5063-1LE0U ISO
EQUALIZATION TANKS
CHEMICAL DESIGN OPERATING TEST PRESS. TEST RADIOGRAPHY % INSULATION TRACING PAINTING STRESS LINE ID
CLEANING TEMP. PRESS. TEMP. PRESS. (PSIG) MEDIUM SHOP FIELD THK. TYPE SYS NO. TERMINAL NORTH
(DEG. F) (PSIG) (DEG. F) (MM) SAUDI ARABIA
(PSIG) RAS TANURA
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

NO 150 262 120 49 NOTE-12 WATER NOTE-19 NOTE-19 0 mm NO NOTE-17 SYS-02 OW-5063
060 L RB-901085 027 00
Saudi Aramco 2825 ENG. (05/05)

RESTRICTED
SA-TR-799 SMART CADD-03