CALCULATION SHEET FOR SPIT ANCHORS


Company : Phone number :
Carried out by : Mail address :
Company : Project name :
Contact name : Location :
Phone number : Fastening point :
Mail address :

Comment :

Recommended anchors Product Code: BAR


EPCON C8 XTREM - Fe E500 Ø16 / hef = 112 mm Effective embedment : 112 mm
ETA-10/0309 issued 2015/10/01

Base material
Concrete resistance : C25/30
Cracking of concrete : Cracked concrete
Thickness of concrete : 200 mm
Reinforcement type : Wide concrete reinforcement
Edge reinforcement : No edge reinforcement

Conditions
Installation conditions : Dry concrete
Short term temperature : 40 °C
Long term temperature : 24 °C

Anchor plate
Thickness of part to be fixed : 10 mm
Recommended plate thickness : The base plate thickness has not been checked

Clearance diameter : 20 mm
Profile : HEA180
Profile position : Ex = 0 mm ; Ey = 0 mm
Stand-off : None

Design method : EN 1992-4 for static, quasi-static loading


Design Actions :

Action [kN] / [kNm] Action type

Combination 1 standard 1 1.2 15.16 0 0 0

Specifications :
Static
Sustained Load : False
Ref : 24‫ ﺹ‬6:48:14 - 2023/8/ / Version 2023.03.31
Date : 242023/8/
Page : 2/7

Geometry :

Calculation Hypothesis :
- The anchoring plate is assumed to be sufficient to resist deformation imposed by the load actions.
- Connection between profile and base plate has not been checked
- The calculation is done acc. to expert judgement, based on EN 1992-4

- SPIT can only be held responsible if the calculation examples exactly reflect the application and if the installation is carried out
according to the instruction given in the SPIT specifications. The calculation is correct for SPIT anchors only. The
contractor or specifier should make sure that the base material is able to support the loads especially in the case of a group of
anchors. SPIT cannot be held responsible if this software package is modified without its written approval.
Ref : 24‫ ﺹ‬6:48:14 - 2023/8/ / Version 2023.03.31
Date : 242023/8/
Page : 3/7

Resulting anchors forces

Loads on anchors

Anchor Tensile Shear[x] Shear[y]


1 0.25 kN 0.3 kN 3.79 kN
2 0.25 kN 0.3 kN 3.79 kN
3 0.25 kN 0.3 kN 3.79 kN

4 0.25 kN 0.3 kN 3.79 kN

1 0.25 0 0

15.21 3.8

Utilization

Tension load Tension force [kN] Strength [kN]


Combined pullout-concrete cone failure 1 45.92 2.2
Concrete cone failure 1 47.58 2.1
Splitting failure / / /

Steel failure 0.25 79.29 0.3

Shear load Shear force [kN] Strength [kN]


Concrete Edge failure / / /
Pryout failure 15.21 105.67 14.39
Steel failure 3.8 36.67 10.37

Combined tension and shear loads

THE APPLICATION IS SAFE


Ref : 24‫ ﺹ‬6:48:14 - 2023/8/ / Version 2023.03.31
Date : 242023/8/
Page : 4/7

CALCULATION DETAILS

Tension load - Combined pullout-concrete cone failure

Tension load - Concrete cone failure


Ref : 24‫ ﺹ‬6:48:14 - 2023/8/ / Version 2023.03.31
Date : 242023/8/
Page : 5/7

Tension load - Splitting failure


Failure mode not decisive.

Tension load - Steel failure


Ref : 24‫ ﺹ‬6:48:14 - 2023/8/ / Version 2023.03.31
Date : 242023/8/
Page : 6/7

Shear load - Concrete edge failure


Failure mode not decisive.

Shear load - Pryout failure

Shear load - Steel failure


Ref : 24‫ ﺹ‬6:48:14 - 2023/8/ / Version 2023.03.31
Date : 242023/8/
Page : 7/7

INSTALLATION DATA

EPCON C8 XTREM - Fe E500 Ø16 / hef = 112 mm Product Code: BAR


Effective embedment : 112 mm
ETA-10/0309 issued 2015/10/01

Minimum stud length: 138.5 mm


Effective embedment : 112 mm
Minimum thickness of base material : 152 mm
Hole diameter in the base material : 20 mm
Hole depth in the base material : 112 mm
Installation torque :
Base plate thickness : 10 mm
Profile family (section type) : HEA180
Clearance diameter : 20 mm

INSTALLATION Method