You are on page 1of 22

Report Ref.

: GESC/ENVMR/2023/08/0077
September 09, 2023

Environmental Monitoring Report

ORIENT HOUSE FOR DEVELOPMENT &


CONSTRUCTION LLC

JABAL DHANNA PROJECT SITE


ABU DHABI, UAE

Environmental Monitoring Report of OHDC - Jabal Dhanna Project Site Page 1


Report Ref.: GESC/ENVMR/2023/08/0077
September 09, 2023

ENVIRONMENTAL MONITORING REPORT OF


 Ambient Air Quality Monitoring
 Generator Emission Monitoring

Submitted to:

ORIENT HOUSE FOR DEVELOPMENT &


CONSTRUCTION LLC
(Abu Dhabi UAE)

Date of issue : 06/09/2023

Prepared By : Mr. Ghulam Murtaza

Environmental Monitoring Report of OHDC - Jabal Dhanna Project Site Page 2


Report Ref.: GESC/ENVMR/2023/08/0077
September 09, 2023

Reviewed By : Mr. Muhammad Zahid Imam

Table of Contents
1. Introduction ......................................................................................................................... 6
2. Purpose of Monitoring ......................................................................................................... 6
3. UAE Laws and Regulations ................................................................................................. 6
3.1. Applicable Environmental Standards ............................................................................................ 7
4. Monitoring Methodology ...................................................................................................... 9
4.1. Air Quality Monitoring Methodology ........................................................................................... 9
4.2. Generator Emission Methodology ................................................................................................ 9
5. Ambient Air Quality Monitoring Results ............................................................................. 12
6. Noise Monitoring Results................................................................................................... 17
7. Conclusions....................................................................................................................... 19
8. Calibration ......................................................................................................................... 19
Annexure−I: Site Pictures ......................................................................................................... 20
\\ Error! Bookmark not defined.

Environmental Monitoring Report of OHDC - Jabal Dhanna Project Site Page 3


Report Ref.: GESC/ENVMR/2023/08/0077
September 09, 2023

List of Tables

Table 3- 1: Occupationnel Air Polluants Limits .................................................................................................. 7


Table 3-2: Ambient Air Pollutants Limits...................................................................................................... 8
Table 3-3: Air Pollutants Limits for Stationary Sources ............................................................................. 8
Table 4- 1: Air Quality Monitoring Techniques .................................................................................................. 9
Table 5-3: Ambient Air Quality Monitoring at Production Hall Entrance ............................................... 13
Table 5-4: Ambient Air Quality Monitoring at Storage Area Entrance .................................................. 15
Table 5- 5: Generator Emission Monitoring Results ................................................................................ 18

Environmental Monitoring Report of OHDC - Jabal Dhanna Project Site Page 4


Report Ref.: GESC/ENVMR/2023/08/0077
September 09, 2023

List of Acronyms

Acronym Definition
EAD Environment Agency - Abu Dhabi
AAQ Ambient Air Quality
ENVM Environmental Monitoring
EIA Environmental Impact Assessment
EMF Environmental Management Framework
HSEIA Health, Safety and Environmental Impact Assessment
EBS Environmental Baseline Survey
FEA Federal Environmental Authority
EMS Environmental Management Plan
HSE Health, Safety and Environmental
CoP Code of Practice
ADWEA Abu Dhabi Water and Electricity Authority
ADWMC Abu Dhabi Waste Management Centre
PMM Particulate Matter Monitoring
CO Carbon Monoxide
NML Noise Monitoring Location
NO2 Nitrogen Dioxide
NOx Nitrogen Oxides
O3 Ozone
SO2 Sulfur Dioxide
TSP Total Suspended Particles
TWA Time Weighted Average
TLV Threshold Limit Value
STEL Short Limit Value
UAE United Arab Emirates
VOC Volatile Organic Compounds

Environmental Monitoring Report of OHDC - Jabal Dhanna Project Site Page 5


Report Ref.: GESC/ENVMR/2023/08/0077
September 09, 2023

1. Introduction

In order to comply with the internal and statuary requirements for environmental monitoring at its
operation and surrounding environment the requirement of Construction Environment Management
plan of Jabal Dhanna site, ORIENT HOUSE FOR DEVELOPMENT & CONSTRUCTION LLC
(Located in Abu Dhabi, UAE) had commissioned with external support the process to carryout Air
Quality Monitoring at Three (02) established monitoring locations and Emission Monitoring at One
(01) suggested Generator within the premises of project site of ORIENT HOUSE FOR
DEVELOPMENT & CONSTRUCTION LLC located at Jabal Dhanna.

ORIENT HOUSE FOR DEVELOPMENT & CONSTRUCTION LLC commissioned Geo


Environmental Safety Consultancy (GSEC) to conduct above mention Environmental Monitoring.

Requested Environmental Monitoring was carried out on 2nd September 2023. AQM Analyzer was
utilized to carry out Ambient Air Quality Analysis at two (02) selected locations. Air Quality Monitoring
was carried out for Temperature, Relative Humidity, Carbon Monoxide (CO), Carbon Dioxide (CO 2),
Nitrogen Dioxide (NO2), Sulfur Dioxide (SO2), Ammonia (NH3), Ozone (O3) and dust monitoring.

Gaseous emission monitoring\ was carried out on same day dated 2 nd September 2023. Emission
Analyzer was utilized to carry out gaseous emission monitoring at one (01) selected Generator place
at the project site of Jabal Dhanna. Gaseous Emission Monitoring was carried out for Ambient
Temperature (Ta), Gas Temperature (Tg), Carbon Monoxide (CO), Carbon Dioxide (CO2), Nitrogen
monoxide (NO), Nitrogen Dioxide (NO2), Nitrogen Oxides (NOx), Sulfur Dioxide (SO2), Oxygen (O2)
and Hydrogen Sulfide (H2S).

2. Purpose of Monitoring
The purpose of monitoring was to check air quality and generator emission monitornig by employing
the environmental monitoring equipment in order to comply with the requirements arising out from
approved CEMP of the project.

3. UAE Laws and Regulations

 Federal Law No. (24) Of 1999 for the “Protection and Development of the Environment”

Environmental Monitoring Report of OHDC - Jabal Dhanna Project Site Page 6


Report Ref.: GESC/ENVMR/2023/08/0077
September 09, 2023

 Federal By Law, Cabinet Decree 12 of 2006 Regarding Regulation Concerning Protection


of Air from Pollutants
 OSHAD SF Version 3.0 “Abu Dhabi Occupational Safety and Health System Framework”

3.1. Applicable Environmental Standards

Applicable air pollutants standards are sourced from UAE Federal Law No. 24 (Environmental
Protection and Development) 1999. This refers to the statutory document through section 3,
Chapter IV, “Protection against Air Pollution”, at Article 55 states Enterprises and establishments
provide the necessary means of protection to the workers in accordance with conditions of safety
and occupational health including choice of machine, equipment’s and suitable types of fuel,
taking into consideration on the time of exposure to such pollutants. Article 54 States all parties
and individuals undertaking the production or services or other activities especially when
operating machines, equipment, working devices shall not exceed the permissible limits for
noise. Applicable air quality and noise level standards have been given under the following
tables.
Table 3- 1: Occupationnel Air Polluants Limits

Maximum Allowable Limits


S.No. Substance Unit
TWA
1 CO 25 ppm

2 CO2 5000 ppm

3 SO2 *2 ppm

4 NO2 3 ppm

5 O3 0.10/15 min ppm

Note: TWA: 8 Hour, time-weighted average exposure concentration.


Source: OSHAD – SF Version 3.0 “Abu Dhabi Occupational Safety and Health System Framework”
*Cabinet Decree (12) of 2006 (Regarding Regulation Concerning Protection of Air from Pollution)

Environmental Monitoring Report of OHDC - Jabal Dhanna Project Site Page 7


Report Ref.: GESC/ENVMR/2023/08/0077
September 09, 2023

Table 3-2: Ambient Air Pollutants Limits

Maximum Allowable
Substance Symbol Average Time
Limits (g / m3)
350 1 hour
Sulphur Dioxide SO2 150 24 hour
60 1 year
30 (mg) 1 hour
Carbon Monoxide CO
10 (mg) 8 hour
400 1 hour
Nitrogen Dioxide NO2
150 24 hour
200 1 hour
Ozone O3
120 8 hour
Particulate Matter PM10 150 24 hour

Source: Cabinet Decree (12) of 2006 (Regarding Regulation Concerning Protection of Air from Pollution)

Table 3-3: Air Pollutants Limits for Stationary Sources

Maximum Allowable
Substance Symbol Average Time
Limits (g / m3)
Fuel Combustion Units –
Nitrogen Oxides having a gross heat input
[expressed as Nitrogen NOx above 100,000 MJ 500
Dioxide (NO2)] excluding glass furnaces:
Liquid Fuel

Sulphur Dioxide SO2 All sources 500

Carbon Monoxide CO All sources 500

Source: Cabinet Decree (12) of 2006 (Regarding Regulation Concerning Protection of Air from Pollution)

Environmental Monitoring Report of OHDC - Jabal Dhanna Project Site Page 8


Report Ref.: GESC/ENVMR/2023/08/0077
September 09, 2023

4. Monitoring Methodology

4.1. Air Quality Monitoring Methodology

The following methods were utilized during the air quality monitoring.

Table 4- 1: Air Quality Monitoring Techniques

Lowest
Monitoring Measurement
Parameters Method Detection
Technique Range
Limit

Temperature Thermistor Standard ISO 7730 0 – 50 0C 0.1 C

Non-Dispersive Standard ASHRAE


Carbon Dioxide (CO2) 0 – 5000 ppm 1 ppm
Infrared 62:2001
Standard European
Carbon Monoxide
GSE Method Directive 0 – 500 ppm 1 ppm
(CO)
2000/69/CEE

Nitrogen Dioxide(NO2) GSS Method EN 50270:2015 0.2 – 100 ppm 1 ppm

Electro-
Sulfur Dioxide(SO2) EN 50270:2015 0.2 – 100 ppm 1 ppm
Chemical

Ozone (O3) GSS Method EN 50270:2015 0 - 0.15 ppm 0.01 ppm

Total Volatile Organic 0.1 ppm


GSS Method EN 50270:2015 0 – 25 ppm
Compounds (TVOCs)

4.2. Generator Emission Methodology

Generator emission monitoring was conducted at one (01) Generator by using flue gas analyzer.
Emission monitoring has been conducted as per standard USEPA CTM 034.

Environmental Monitoring Report of OHDC - Jabal Dhanna Project Site Page 9


Report Ref.: GESC/ENVMR/2023/08/0077
September 09, 2023

Environmental Monitoring Report of OHDC - Jabal Dhanna Project Site Page 10


Report Ref.: GESC/ENVMR/2023/08/0077
September 09, 2023

Environmental Monitoring Report of OHDC - Jabal Dhanna Project Site Page 11


Report Ref.: GESC/ENVMR/2023/08/0077
September 09, 2023

5. Ambient Air Quality Monitoring Results

Type of Monitoring Ambient Air Quality Monitoring

Samling ID AAQ-01

Sampling Duration 8 Hour

Sampling Date 2nd September 2023

Relative Humidity 42.0%

Temperature 39.0 °C

Sample Location Project site near Sea

AAQ-01 – Project Site Near Sea

Environmental Monitoring Report of OHDC - Jabal Dhanna Project Site Page 12


Report Ref.: GESC/ENVMR/2023/08/0077
September 09, 2023

Table 5-3: Ambient Air Quality Monitoring at Production Hall Entrance

Observed Concentration
Parameters Applicable Standards
Method Avg

Temperature(°C) Standard ISO 7730 39.5 NA

Relative Humidity % Method 4 - Moisture Content 42.0 NA

CO (mg/Nm3) BSEN 60079-29-2-2015 2.90 10/ 8hrs.

NH3 (ppm) BSEN 60079-29-2-2015 03 50

USEPA TITLE 40 CFR PART


SO2 (µg/Nm3) 02.00 150/ 24hrs.
EQS-0775-002:1975

USEPA TITLE 40 CFR PART


NO2 (µg/Nm3) 16.00 150/ 24hrs.
EQN-1277-026:2003

USEPA TITLE 40 CFR PART


O3 (µg/Nm3) 0.00 120/ 8hrs.
50 APPENDIX B:2015

USEPA TITLE 40 CFR PART


PM10 98.8 150
50 APPENDIX B:2015

USEPA TITLE 40 CFR PART


TSP 123 230
50 APPENDIX B:2015

ND = Not Detected
Source: Cabinet Decree (12) of 2006 (Regarding Regulation Concerning Protection of Air from Pollution)

Results of all the above Air Quality Monitoring Tests are in compliance and within the limits of
relevant applicable standards of Cabinet Decree (12) of 2006 and OSHAD SF.

Environmental Monitoring Report of OHDC - Jabal Dhanna Project Site Page 13


Report Ref.: GESC/ENVMR/2023/08/0077
September 09, 2023

Type of Monitoring Ambient Air Quality Monitoring

Samling ID AAQ-02

Sampling Duration 8 Hour

Sampling Date 2nd September 2023

Relative Humidity 42.0%

Temperature 39.5 °C

Sample Location Project site near camp area

AAQ-02 – Near Camp Area

Environmental Monitoring Report of OHDC - Jabal Dhanna Project Site Page 14


Report Ref.: GESC/ENVMR/2023/08/0077
September 09, 2023

Table 5-4: Ambient Air Quality Monitoring at Storage Area Entrance

Observed Concentration
Parameters Applicable Standards
Method Avg

Temperature(°C) Standard ISO 7730 39.5 NA

Relative Humidity % Method 4 - Moisture Content 43.0 NA

CO (mg/Nm3) BSEN 60079-29-2-2015 3.90 10/ 8hrs.

NH3 (ppm) BSEN 60079-29-2-2015 01 50

USEPA TITLE 40 CFR PART


SO2 (µg/Nm3) 03.00 150/ 24hrs.
EQS-0775-002:1975

USEPA TITLE 40 CFR PART


NO2 (µg/Nm3) 21.00 150/ 24hrs.
EQN-1277-026:2003

USEPA TITLE 40 CFR PART


O3 (µg/Nm3) 0.00 120/ 8hrs.
50 APPENDIX B:2015

USEPA TITLE 40 CFR PART


PM10 65.5 150
50 APPENDIX B:2015

USEPA TITLE 40 CFR PART


TSP 112 230
50 APPENDIX B:2015

ND = Not Detected
Source: Cabinet Decree (12) of 2006 (Regarding Regulation Concerning Protection of Air from Pollution)

Results of all the above Air Quality Monitoring Tests are in compliance and within the limits of
relevant applicable standards of Cabinet Decree (12) of 2006 and OSHAD SF.

Environmental Monitoring Report of OHDC - Jabal Dhanna Project Site Page 15


Report Ref.: GESC/ENVMR/2023/08/0077
September 09, 2023

Environmental Monitoring Report of OHDC - Jabal Dhanna Project Site Page 16


Report Ref.: GESC/ENVMR/2023/08/0077
September 09, 2023

6. Noise Monitoring Results

Type of Monitoring Generator Emission Monitoring

Samling ID GM-01

Sampling Duration 1 Hour

Sampling Date 2nd September 2023

Relative Humidity 48.5%

Temperature 40.0 °C

Generator ID No TMG-45

Serial No E622CDGL1169

GM-01 – Generator TGM 45

Environmental Monitoring Report of OHDC - Jabal Dhanna Project Site Page 17


Report Ref.: GESC/ENVMR/2023/08/0077
September 09, 2023

Table 5- 5: Generator Emission Monitoring Results

Observed Concentration Applicable


Parameters
Standards
Reading 1 Reading 2 Reading 3

CO (mg/Nm3) 86 89 91 500

SO2 (mg/Nm3) 9 9 10 500

O2 % 14.53 14.09 14.01 -

CO2 % 2.95 3.10 3.20 -

NO2 (mg/Nm3) 7.80 7.50 7.90 -

NO (mg/Nm3) 76.0 82.0 87.0 -

NOx (mg/Nm3) 83.8 89.5 94.9 500

H2S (mg/Nm3) ND ND ND 5

HC (mg/Nm3) 0.01 0.01 0.01 -

ND = Not Detected
Source: Cabinet Decree (12) of 2006 (Regarding Regulation Concerning Protection of Air from Pollution)

Environmental Monitoring Report of OHDC - Jabal Dhanna Project Site Page 18


Report Ref.: GESC/ENVMR/2023/08/0077
September 09, 2023

7. Conclusions

Results of all the above Air Quality Monitoring Tests and Generator Emission Monitoring are in
compliance and within the limits of relevant applicable Federal standards of Cabinet Decree (12) of
2006

8. Calibration

All monitoring instruments utilized during the monitoring carried valid external calibration
certifications through supplier / internationally recognized facilities.

Environmental Monitoring Report of OHDC - Jabal Dhanna Project Site Page 19


Report Ref.: GESC/ENVMR/2023/08/0077
September 09, 2023

Annexure−I: Site Pictures

Environmental Monitoring Report of OHDC - Jabal Dhanna Project Site Page 20


Report Ref.: GESC/ENVMR/2023/08/0077
September 09, 2023

AAQ-01 Project Site Near Sea

AAQ-02 Project Site Near Camp Area

Environmental Monitoring Report of OHDC - Jabal Dhanna Project Site Page 21


Report Ref.: GESC/ENVMR/2023/08/0077
September 09, 2023

AAQ-02 Project Site Near Camp Area

GM-01 – Generator TGM 45

Environmental Monitoring Report of OHDC - Jabal Dhanna Project Site Page 22

You might also like