CONCRETE COMPRESSIVE STRENGTH TEST REPORT NF EN

12390-3
Number of Test Report 015
Project CONGO – BIOFUEL 1st AGRI HUB - INDUSTRIAL START-UP
Contractor ZEROCK CONSTRUCTION CONGO
Origin of Concrete Zerock Concrete Batching Plant in Loudima

Temperature weather /
30,2 / 30,1 °C Size of specimen 160 x 320 mm
concrete
Pouring date 6/24/2023 Slump test at 0' 15,8 cm
Mix Design Code 25 - XC4 - D25 - S3 - 42.5N - SHR - S0/1
Composition Cement Water Sand Gravel 1 Gravel 2 Admixture
Type 42,5N - 0/1 5/12,5 16/25 Admix150
Quantity(Kg/m3) 450 178.78 574 260 1018 4
Part of Structure

Production Line Shed / Footing / G8IF01

30A100_RFI_26 EXT
Number notification Date of receipt 6/30/2023
30A100_RFI_58 EXT

Curing by Density Strength (Mpa)


Spec. Tag Crushing date Weight (Kg) Load (kN)
days (T/m3) Unit Average
AH103 16.28 2.53 579.24 28.81
AH104 7 7/1/2023 16.02 2.49 566.33 28.17 28.41
AH105 16.04 2.49 568.01 28.25
AH106 16.08 2.50 585.48 29.12
AH107 28 7/22/2023 15.98 2.48 644.67 32.06 30.64
AH108 16.00 2.49 618.02 30.74
AH109
AH110 56 8/19/2023 N/A
AH111

Inspection execution result


ACCEPTED ⃣ REJECTED ⃣ POSTPONED ⃣ CANCELLED ⃣
Remarks :

Inspectors for : GEOLAB ENI CONGO ZEROCK

Name

Signature

Date