CONCRETE COMPRESSIVE STRENGTH TEST REPORT NF EN

12390-3
Number of Test Report 067
Project CONGO – BIOFUEL 1st AGRI HUB - INDUSTRIAL START-UP
Contractor ZEROCK CONSTRUCTION CONGO
Origin of Concrete Zerock Concrete Batching Plant in Loudima

Temperature weather /
33,4 / 34 °C Size of specimen 160 x 320 mm
concrete
Pouring date 8/26/2023 Slump test at 0' 15,2 cm
Mix Design Code 25 - XC4 - D25 - S3 - 42.5N - SHR - S0/1
Composition Cement Water Sand Gravel 1 Gravel 2 Admixture
Type 42,5N - 0/1 5/12,5 16/25 Admix150
Quantity(Kg/m3) 450 178.78 574 260 1018 4
Part of Structure

2nd line Production / Seed Cleaner Bag Filter A; Bucket; Elevator - BE5; Bucket Elevator - BE6; Bucket Elevator -
BE8 / F32G-H; F14 wall; F24wall; F16 wall

30A100_RFI_132 EXT
Number notification Date of receipt 8/30/2023
30A100_RFI_169 EXT

Curing by Density Strength (Mpa)


Spec. Tag Crushing date Weight (Kg) Load (kN)
days (T/m3) Unit Average
AH562 15.98 2.48 443.42 22.05
AH563 7 9/2/2023 15.76 2.45 403.11 20.05 21.36
AH564 15.80 2.46 441.85 21.98
AH565 16.12 2.51 421.34 20.96
AH566 28 9/23/2023 15.90 2.47 544.45 27.08 24.54
AH567 15.92 2.48 514.29 25.58
AH568
AH569 56 10/21/2023 N/A
AH570

Inspection execution result


ACCEPTED ⃣ REJECTED ⃣ POSTPONED ⃣ CANCELLED ⃣
Remarks :

Inspectors for : GEOLAB ENI CONGO ZEROCK

Name

Signature

Date