Professional Documents
Culture Documents
HR
Uputstva i napomene
IE
103
PL Ø 41,5 From 0 to 20
NONE Over 20
CZ
Ø 41,5 From 0 to 25
SL
NONE Over 25
HU
Duct length in metres
DIAPHRAGM
Ø 80/125 horizontal
Diaphragm installation. To ensure correct operation of the
IE boiler, a diaphragm (see figure) must be installed on output Ø 41,5 From 0 to 1.9
of the sealed chamber before the intake and exhaust duct.
Selection of a suitable diaphragm depends on the type of NONE Over 1,9
ducting used and maximum length: calculations can be made
using the values in the tables below:
Duct length in metres
DIAPHRAGM DIAPHRAGM
Ø 80/125 vertical
e kit comprises:
1 - Seal (1)
1 - Concentric bend
Ø 60/100 (2)
1 - Adapter Ø 60/100 for Ø
80/125 (3)
1 - Concentric int./exh. bend
Ø 80/125 (4)
1 - Internal washer (5)
1 - External washer (6)
• Extensions for horizontal kit. e horizontal intake- • Snap fit extension pipe fittings and concentric elbows Ø
exhaust kit Ø 60/100 can be extended up to a max. hori- 80/125. To install snap-fit extensions with other elements
zontal distance of 3000 mm including the grille terminal of the boiler assembly, proceed as follows: fit the concentric
and excluding the concentric bend on output of the boiler. pipe or elbow with the male section (smooth) on the female
is configuration corresponds to a resistance factor of section (with lip seal) to the end stop on the previously
100. In this case special extensions must be requested. installed to ensure sealing efficiency of the coupling.
Caution: if the exhaust terminal and/or extension concen-
tric pipe needs shortening, consider that the internal duct
must always protrude by 5 mm with respect to the external
duct.
Normally the horizontal intake/exhaust kit Ø 80/125 is used
in the event of using particularly long extensions; the kit Ø
80/125 can be installed with a rear, right-hand, left-hand
or front outlet.
107
SL
108
HR
SL
HU
HU
IE
• Temperature loss in insulated ducting. To avoid the pro- Flue exhaust via flues.
blem of flue condensation in insulated exhaust Ø 80 Flue exhaust does not necessarily have to be connected a
pipes, due to cooling via the wall, the exhaust pipe length branched type traditional flue and can be connected to a
must be restricted to 12 metres. e figure above illustrates special LAS type multiple flue. Flues must be specially desi-
a typical insulation application in which the intake pipe is gned according to specifications in the standard by qualified
short and the exhaust pipe very long (over 5 m). e entire professional personnel.
intake pipe is insulated to prevent condensation of humid Chimney or flue sections for connection of the exhaust pipe
air in the boiler environment in contact with the cooled must comply with requirements as laid down in standards.
pipe conveying cool outdoor air. e entire exhaust pipe
is insulated with the exception of the elbow on output of Existing ducting flues.
the splitter, to reduce heat dispersion from the duct and With a specific “ducting system” it is possible to reuse existing
prevent formation of flue condensate. flues, chimneys and technical slots to discharge the boiler
N.W.: when installing the insulated ducts, a section clamp fumes. Ducting requires the use of ducts declared suitable for
with pin must be installed every 2 metres. the purpose by the manufacturer, following the installation
and operation instructions provided by the manufacturer,
and the requirements standard.
111
IE
Head in m H20
113
PL
CZ
HR
SL
HU
IE
Key:
1 - Air/flue intake sockets (A air) - (F flue) 11 - Combustion chamber
2 - Flue extraction fan 12 - Automatic air vent valve
3 - Gas valve 13 - Circulating pump
4 - Positive signal pressure socket 14 - 3 bar safety valve
5 - Negative signal pressure socket 15 - System drain valve
6 - Fan safety pressure switch 16 - System filling valve
7 - Sealed chamber 17 - Flue extractor hood
8 - NTC limit and regulation sensor 18 - Primary heat exchanger
9 - Termp. overload safety thermostat 19 - Ignition/detection electrodes
10 - Expansion vessel 20 - Burner
114
Key:
1 - Boiler pressure/temperature gauge 4 - Switch 0-Anti-freeze - Heating-Reset
2 - Flame presence yellow indicator lamp 5 - Heating temperature selector
3 - Boiler block red indicator lamp 6 - Clock programmer (optional)
115
116
Decommissioning. PL
In the event of permanent shutdown of the boiler, contact
professional personnel for the procedures and ensure that
the electrical, water and gas supply lines are shut off and CZ
disconnected.
HR
SL
HU
IE
117
Power supply
Brown
Brown
Brown
White
White
Black
Black
Black
Blue
Blue
Red
Red
Yellow/green
Key:
Brown
Blue
E3 - Detection electrode
JP1 - Gas selector
JP3 - Heating timer selector
LD1 - Flame presence led
Primary LD2 - Fault indicator led
MOD - Modulating coil
Secondary
MP - Circulating pump
MV - Fan
Heating adjustment
Ignition power NM - Delivery NTC sensor
OP - Timer
Heating power
P1 - Room thermostat jumper
SV - Air pressure microswitch
TA - Room thermostat On/Off (optional)
TS1 - Temp. overload safety thermostat
VG - Gas valve
Room thermostat and clock programmer: the boiler is - Jumper JP1: when inserted the appliance operates with
designed for application of an room thermostat (TA) and LPG; when removed the appliance operates with natural
of a clock programmer (CP). If you have only one of these gas.
devices, connect to terminals 6 and 9 and remove jumper P1. - JP3 jumper; when inserted, after the heating temperature
Whereas if you have both, connect (TA) on terminals 8 and is reached the boiler only re-starts after 3 minutes; when
9, and (CP) on terminals 6 and 7, after removing P1. removed, the interval before re-start changes to 30 seconds,
useful for convection fan systems.
Electronic card function options.
e electronic card is equipped with jumpers designed to
regulate boiler operation according to specific installation
118
requirements.
PL
Key:
1 - Filling valve
2 - Gas valve
3 - Main burner CZ
4 - Primary heat exchanger
5 - Sealed chamber
6 - Flue extraction fan
7 - Fan safety pressure switch HR
8 - Flue extraction hood
9 - Temp. overload safety thermostat
10 - NTC limit and regulation sensor
11 - Expansion vessel SL
12 - Automatic air venting valve
13 - Circulating pump
14 - Drain valve
15 - 3 bar safety valve HU
G - Gas supply
E - Domestic water inlet
IE
R - System return
M - System delivery
PL
DOMESTIC
CZ
DOMESTIC OFF
TURAL GAS
TIMER
HR
SL
Key:
1 - Coil 6 - Protection hood
2 - Minimum power adjustment screw 10 - 2A fuse HU
3 - Maximum power adjustment screw 11 - Slow lighting adjustment trimmer
4 - Gas valve outlet pressure point 12 - Heating adjustment trimmer
5 - Gas valve inlet pressure point 13 - Jumper for operation with natural gas/LPG.
IE
Casing disassembly. - Slacken the 2 fixing screws on the control panel and tilt
To facilitate boiler maintenance the casing can be disassem- forward to open.
bled as follows: - Slacken the two casing fixing screws (2).
- Remove the lower filling valve.
- Detach the rear boiler panel as shown in the figure.
- Remove the lower cover by slackening the two screws
(1). - Pull the casing forwards and up at the same time (see figure)
to detach from the upper hooks.
2
121
N.W.: Pressure values specified in the table indicate the dif- positive pressure test outlet . Power data specified in the
ference of pressure values between the gas valve outlet and table refer to a 0,5 metre intake/exhaust pipe. Gas flow rates
the combustion chamber. Adjustments are therefore carried refer to heat power below temperature of 15°C and at a
out with the differential pressure gauge ( “U” or digital type) pressure of 1013 mbar. Burner pressure values refer to use
with the sensors inserted in the test pressure outlet of the of gas at 15°C.
modulating adjustable gas valve and on the sealed chamber
122
123