You are on page 1of 2

Drawing Title Wavistrong® - Flange - Taper Bell & Flat Face

Project Name JI201- BUHASA FIREWATER NETWORK REPLACEMENT PROJECT


Location Abu Dhabi
Contractor PROGETTI EUROPA & GLOBAL ABU DHABI
End User ADNOC GAS PROCESSSING
Drawing Number FPI-2022-004183-VETM-CDE-PRD-AUH-22-027-R0-Fire water
Sheet Number 2 This document contains confidential and proprietary information of Future Pipe
Project Number 06I000533 Industries. No reproduction or disclosure of any part to third parties is allowed without
Scale Not To Scale written authorization by Future Pipe Industries.
Rev. Comment Date Prepared By Checked By Approved By
0 Issued for Reviews and Comments 15-Sep-2022 Arun Sarath Robert

Flange, TB/FF

Note:
1. Offered Material: GRE FM
2. Design Temperature (°C): 85°C
3. Installation Type: UG
4. The listed product weights are based on theoretical geometrical calculation and are meant for transportation and handling
purposes only. Actual weights of supplied products may vary
•Torque values mentioned are meant only for ‘’Flat Face’’ FRP Flange connected to ‘’Flat Face’’ FRP or other material Flange
and Blind Flange. Nothing that, FPI recommends to use steel spacer rings in case the steel flange and blind flange are ‘’Raised
Face’’.if the FRP Flange will be connected to Rubber-lined equipment such as valve, bellows, etc., FPI shall be contacted for
further review to advise the torque values in such cases.. Flange TF tolerance for ID<450 +2/-1.
•Kroll & Ziller type G-ST-P/S or equivalent (rubber gaskets with steel inlay) Can be used
Flange Drilling
Flange Qualified
Design Pressure

Minimum Total
Inner Diameter

Overall Length
Service/Piping

Laying Length

Thickness
Pressure

No. of Holes

Description
Weight

Bolt Pitch
Diameter

Diameter
Class

Bolt Size
Outside
Flange

Hole

- DP ID Pq L Lo TF W Du Dst d n dB -
- bar mm bar mm mm mm Kg mm mm inch - inch -
17100 19.6 300 50.0 50 175 85 19.5 483 431.8 1 12 7/8 ASME B16.5 Class 150
Design Pressure

Inner Diameter

FM APPROVED
Service/Piping

Rubber Type
Gasket Type
Bolt Torque
Class

- DP ID BT - - -
- bar mm Nm - - -
17100 19.6 300 75 Kroll & Ziller G-ST-P/S EPDM-S FM 20

FPI-2022-004183-VETM-CDE-PRD-AUH-22-027-R0-Fire water 3 of 4
Drawing Title Wavistrong® - Field Joint
Project Name JI201- BUHASA FIREWATER NETWORK REPLACEMENT PROJECT
Location Abu Dhabi
Contractor PROGETTI EUROPA & GLOBAL ABU DHABI
End User ADNOC GAS PROCESSSING
Drawing Number FPI-2022-004183-VETM-CDE-PRD-AUH-22-027-R0-Fire water
Sheet Number 3 This document contains confidential and proprietary information of Future Pipe
Project Number 06I000533 Industries. No reproduction or disclosure of any part to third parties is allowed without
Scale Not To Scale written authorization by Future Pipe Industries.
Rev. Comment Date Prepared By Checked By Approved By
0 Issued for Reviews and Comments 15-Sep-2022 Arun Sarath Robert

Field Joint Lamination

Note:
1. Offered Material: GRE FM
2. Design Temperature (°C): 85°C
3. Installation Type: UG
Design Pressure

Inner Diameter

FM APPROVED
Service/Piping

Bond Length
Lamination
Minimum

Thickness
Class

- DP ID TW.LAM BL -
- bar mm mm mm -
17100 19.6 300 10.2 150 FM 20

FPI-2022-004183-VETM-CDE-PRD-AUH-22-027-R0-Fire water 4 of 4