You are on page 1of 4

Project: Shell NMIF Generator Building Date : 11-Apr-22

Customer: Pilipinas Shell Petroleum Corporation

NOISE MEASUREMENT SURVEY RESULTS

Location Corrales Ext. Cagayan de Oro Date : March 31 to April 1, 2022


Conditions:
Generator On and Ambient Conditions

Sound Level Meter Identification:


Make NTi Audio Model: XL2 + M2230 Serial No.
Calibration Certificate No. Date of Calibration: Analyzer AZA-11581-E0
Analyzer - 43992-A2A-11581-E0 2-Jun-21 Microphone 8154 / A16701
Microphone - 43992-8154-M2230 2-Jun-21

Environmental Quality Standards for Pre-Installation


Reference Noise in General Areas (Class C)
Location Genset On
Point
Morning Daytime Evening Nighttime Date Daytime Nighttime
Point A Perimeter Fence 65dBA 70dBA 65dBA 60dBA 26-May-20
Point B Acrross the Road 65dBA 70dBA 65dBA 60dBA 26-May-20 86.6 86.2
Point C 10 meters into the Lorry Parking N/A N/A N/A N/A 26-May-20 78.5 73.8
Point D 25 meters into the Lorry Parking N/A N/A N/A N/A 26-May-20 70.6 70.5

Pre- Post Installation


NPCC
Install
Evening Measurements Standard Genset On Ambient
Genset
Class C
(6PM to 10PM) On Lmax Lmin Leq Lmax Lmin Leq
Point A Perimeter Fence 65dBA 69 62 65 74 42 60
Point B Acrross the Road 65dBA 65 57 61 70 44 58
Point C 10 meters into the Lorry Parking N/A 59 48 53 58 39 48
Point D 25 meters into the Lorry Parking N/A 60 49 54 60 40 48

Pre- Post Installation


NPCC
Install
Nighttime Measurements Standard Genset On Ambient
Genset
Class C
(10PM to 5AM) On Lmax Lmin Leq Lmax Lmin Leq
Point A Perimeter Fence 60dBA 68 62 65 69 40 55
Point B Acrross the Road 60dBA 86.2 65 57 61 78 42 62
Point C 10 meters into the Lorry Parking N/A 73.8 60 48 53 56 40 46
Point D 25 meters into the Lorry Parking N/A 70.5 59 49 54 56 40 47
Project: Shell NMIF Generator Building Date : 11-Apr-22
Customer: Pilipinas Shell Petroleum Corporation

NOISE MEASUREMENT SURVEY RESULTS

Location Corrales Ext. Cagayan de Oro Date : March 31 to April 1, 2022


Conditions:
Generator On and Ambient Conditions

Pre- Post Installation


NPCC
Install
Morning Measurements Standard Genset On Ambient
Genset
Class C
(5AM to 9AM) On Lmax Lmin Leq Lmax Lmin Leq
Point A Perimeter Fence 65dBA 78 63 69 76 50 64
Point B Acrross the Road 65dBA 78 58 66 76 46 64
Point C 10 meters into the Lorry Parking N/A 63 49 55 57 41 49
Point D 25 meters into the Lorry Parking N/A 65 48 53 57 40 48

Pre- Post Installation


NPCC
Install
Daytime Measurements Standard Genset On Ambient
Genset
Class C
(8AM to 10PM) On Lmax Lmin Leq Lmax Lmin Leq
Point A Perimeter Fence 70dBA 80 64 69 80 52 66
Point B Acrross the Road 70dBA 86.6 77 59 67 80 51 68
Point C 10 meters into the Lorry Parking N/A 78.5 61 48 54 59 45 51
Point D 25 meters into the Lorry Parking N/A 70.6 60 48 53 59 43 50

Notes:
1 Test duration : 1 minute per test
2 No. of Samplings: 3x per point
3 Measurement Height : 1.2 meters from ground
4 Noise Characteristics of target machinery: Tonal
5 Testing undertaken under normal/standard conditions
6 Ground reflection taken into consideration (-3dB)
7 Environmental noise taken into consideration (-3dB)
8 # of people within test site: 3 people

Prepared by:

Eugene A. Bayhon
Rexim Philippines Universal Sales Corporation