You are on page 1of 4

Project: Shell NMIF Generator Building Date : 11-Apr-22

Customer: Pilipinas Shell Petroleum Corporation

NOISE MEASUREMENT SURVEY RECORD

Location Corrales Ext. Cagayan de Oro Date : March 31 to April 1, 2022


Conditions:
Generator On and Ambient Conditions

Sound Level Meter Identification:


Make NTi Audio Model: XL2 + M2230 Serial No.
Calibration Certificate No. Date of Calibration: Analyzer AZA-11581-E0
Analyzer - 43992-A2A-11581-E0 2-Jun-21 Microphone 8154 / A16701
Microphone - 43992-8154-M2230 2-Jun-21

Environmental Quality Standards for Pre-Installation


Reference Noise in General Areas (Class C)
Location Genset On
Point
Morning Daytime Evening Nighttime Date Daytime Nighttime

Point B Acrross the Road 65dBA 70dBA 65dBA 60dBA 26-May-20 86.6 86.2
Point C 10 meters into the Lorry Parking N/A N/A N/A N/A 26-May-20 78.5 73.8
Point D 25 meters into the Lorry Parking N/A N/A N/A N/A 26-May-20 70.6 70.5

Pre- Post Installation


NPCC
Install
Nighttime Measurements Standard Genset On Ambient
Genset
Class C
(10PM to 5AM) On Lmax Lmin Leq Lmax Lmin Leq

Point B Acrross the Road 60dBA 86.2 65 57 61 78 42 62


Point C 10 meters into the Lorry Parking N/A 73.8 60 48 53 56 40 46
Point D 25 meters into the Lorry Parking N/A 70.5 59 49 54 56 40 47

Pre- Post Installation


NPCC
Install
Daytime Measurements Standard Genset On Ambient
Genset
Class C
(8AM to 10PM) On Lmax Lmin Leq Lmax Lmin Leq

Point B Acrross the Road 70dBA 86.6 77 59 67 80 51 68


Point C 10 meters into the Lorry Parking N/A 78.5 61 48 54 59 45 51
Point D 25 meters into the Lorry Parking N/A 70.6 60 48 53 59 43 50
Project: Shell NMIF Generator Building Date : 11-Apr-22
Customer: Pilipinas Shell Petroleum Corporation

NOISE MEASUREMENT SURVEY RECORD

Location Corrales Ext. Cagayan de Oro Date : March 31 to April 1, 2022


Conditions:
Generator On and Ambient Conditions

Notes:
1 Test duration : 1 minute per test
2 No. of Samplings: 3x per point
3 Measurement Height : 1.2 meters from ground
4 Noise Characteristics of target machinery: Tonal
5 Testing undertaken under normal/standard conditions
6 Ground reflection taken into consideration (-3dB)
7 Environmental noise taken into consideration (-3dB)
8 # of people within test site: 3 people

Prepared by:

Eugene A. Bayhon
Rexim Philippines Universal Sales Corporation

You might also like