Professional Documents
Culture Documents
𝑉𝑎0 0 𝑍0 0 0 𝐼𝑎0
𝑉𝑎1 = 𝐸𝑎 − 0 𝑍1 0 𝐼𝑎1
𝑉𝑎2 0 0 0 𝑍2 𝐼𝑎2
• During unsymmetrical fault analysis of any given type of fault, two sets of equations as follows
are considered for solving them simultaneously to get the required fault parameters:
• Equations for the conditions under fault
• Equations for the sequence components (sequence equations)
Single line-to-ground fault on an unloaded
synchronous generator
• A conventional generator is one that produces only the balanced voltages.
• Let Ea, Eb and Ec be the internally generated voltages and Zn be the neutral impedance.
• The fault is assumed to be on the phase ‘a’ as shown in figure.
• The conditions under fault:
• 𝐼𝑏 = 0, 𝐼𝑐 = 0 and 𝑉𝑎 = 0
𝐼𝑎0 1 1 1 𝐼𝑎
𝐼𝑎1 = 1/3 1 𝑎 𝑎2 0
𝐼𝑎2 1 𝑎2 𝑎 0
𝐸𝑎
𝐼𝑎1 =
(𝑍0 + 𝑍1 +𝑍2 )
Single line-to-ground fault on an unloaded
𝐼𝑎1 =
𝐸𝑎 synchronous generator (cont.)
(𝑍0 + 𝑍1 +𝑍2 )
𝐼𝑎0 = 𝐼𝑎1 = 𝐼𝑎2
3𝐸𝑎
• The fault current 𝐼𝑓 = 𝐼𝑎 = 3𝐼𝑎1 =
(𝑍0 +𝑍1 +𝑍2 )
• This equation implies that the three sequence networks are
connected in series to simulate SLG fault
𝐸𝑎 (𝑍0 + 𝑍2 )
𝑉𝑎1 = 𝐸𝑎 − 𝐼𝑎1 𝑍1 =
(𝑍0 + 𝑍1 +𝑍2 )
𝐸𝑎 𝑍2
𝑉𝑎2 = −𝐼𝑎2 𝑍2 = −
(𝑍0 + 𝑍1 +𝑍2 )
𝐸𝑎 𝑍0
𝑉𝑎0 = −𝐼𝑎0 𝑍0 = −
(𝑍0 + 𝑍1 +𝑍2 )
• Phase voltages can be computed using, 𝑉𝑎 1 1 1 𝑉𝑎0
𝑉𝑏 = 1 𝑎2 𝑎 𝑉𝑎1
𝑉𝑐 1 𝑎 𝑎2 𝑉𝑎2
Single line-to-ground fault on an unloaded
synchronous generator through a fault impedance
• A conventional generator is one that produces only the balanced voltages.
• Let Ea, Eb and Ec be the internally generated voltages and Zn be the neutral impedance.
• The fault is assumed to be on the phase ‘a’ through a fault impedance ‘Zf ’ shown in figure.
• The conditions under fault:
• 𝐼𝑏 = 0, 𝐼𝑐 = 0 and 𝑉𝑎 = 𝐼𝑎 𝑍𝑓
𝐼𝑎0 1 1 1 𝐼𝑎
𝐼𝑎1 = 1/3 1 𝑎 𝑎2 0
𝐼𝑎2 1 𝑎2 𝑎 0
𝑍2 𝑗0.35
𝑉𝑎2 = −𝐸𝑎 = −1.0 × = −0.50𝑝𝑢
(𝑍0 + 𝑍1 +𝑍2 ) 𝑗0.10 + 𝑗0.25 + 𝑗0.35
𝑍0 𝑗0.10
𝑉𝑎0 = −𝐸𝑎 = −1.0 × = −0.143𝑝𝑢
(𝑍0 + 𝑍1 +𝑍2 ) 𝑗0.10 + 𝑗0.25 + 𝑗0.35
Solution
𝑉𝑎 1 1 1 𝑉𝑎0
𝑉𝑏 = 1 𝑎2 𝑎 𝑉𝑎1
𝑉𝑐 1 𝑎 𝑎2 𝑉𝑎2
𝑉𝑎 1 1 1 −0.143
𝑉𝑏 = 1 1∠2400 1∠1200 0.643
𝑉𝑐 1 1∠1200 1∠2400 −0.50
𝑉𝑎 0
𝑉𝑏 = −0.215 − 𝑗0.989
𝑉𝑐 −0.215 + 𝑗0.989
13.8
𝑉𝑎𝑏 = 𝑉𝑎 − 𝑉𝑏 = 0.215 + 𝑗0.989 = 1.01∠770 𝑝𝑢 = 1.01 × = 8.05∠770 𝑘𝑉
3
13.8
𝑉𝑏𝑐 = 𝑉𝑏 − 𝑉𝑐 = −0.215 − 𝑗0.989 − 0.215 + 𝑗0.989 = 1.978∠2700 × = 15.73∠2700 𝑘𝑉
3
13.8
𝑉𝑐𝑎 = 𝑉𝑐 − 𝑉𝑎 = −0.215 + 𝑗0.989 = 1.01∠102.30 = 1.01 × = 8.05∠102.30 𝑘𝑉
3
Line to line fault on an unloaded
synchronous generator
• The circuit diagram for line to line fault is shown in figure.
• The conditions under fault:
• 𝑉𝑏 = 𝑉𝑐 , 𝐼𝑎 = 0 , 𝐼𝑏 = −𝐼𝑐
𝐼𝑎0 1 1 1 0
𝐼𝑎1 = 1/3 1 𝑎 𝑎2 𝐼𝑏
𝐼𝑎2 1 𝑎2 𝑎 −𝐼𝑏
1 2
𝐼𝑏
𝐼𝑎2 = × 0 + 𝑎 𝐼𝑏 − 𝑎𝐼𝑏 = −𝑗
3 3
1
𝐼𝑎0 = × 0 + 𝐼𝑏 − 𝐼𝑏 = 0
3
Line to line fault on an unloaded
synchronous (cont.)
• The sequence equations :
𝑉𝑎 1 1 1 𝑉𝑎0
𝑉𝑏 = 1 𝑎2 𝑎 𝑉𝑎1
𝑉𝑐 1 𝑎 𝑎2 𝑉𝑎2
𝑉𝑎0 = 0
𝑉𝑎 1 1 1 𝑉𝑎0 1 1 1 0
𝑉𝑏 = 1 𝑎2 𝑎 𝑉𝑎1 = 1 𝑎2 𝑎 𝑉𝑎1
𝑉𝑐 1 𝑎 𝑎2 𝑉𝑎2 1 𝑎 𝑎2 𝑉𝑎1
𝑉𝑎 = 2𝑉𝑎1
3𝐸𝑎
• Fault current is 𝐼𝑏 = −𝐼𝑐 = −𝑗
(𝑍1 +𝑍2 )
Line to line fault on an unloaded
synchronous generator through a fault impedance
• The circuit diagram for line to line fault through a fault impedance ‘Zf ’ is shown in figure.
• The conditions under fault:
• 𝐼𝑎 = 0 , 𝐼𝑏 = −𝐼𝑐 , 𝑉𝑏 − 𝑉𝑐 = 𝐼𝑏 𝑍𝑓
𝐼𝑎0 1 1 1 0
𝐼𝑎1 = 1/3 1 𝑎 𝑎2 𝐼𝑏
𝐼𝑎2 1 𝑎2 𝑎 −𝐼𝑏
1
𝐼𝑎0 = × 0 + 𝐼𝑏 − 𝐼𝑏 = 0
3
Line to line fault on an unloaded
synchronous generator through a fault impedance (cont.)
• The sequence equations :
𝑉𝑎 1 1 1 𝑉𝑎0
𝑉𝑏 = 1 𝑎2 𝑎 𝑉𝑎1
𝑉𝑐 1 𝑎 𝑎2 𝑉𝑎2
𝐼𝑎 1 1 1 𝐼𝑎0 1 1 1 0
𝐼𝑏 = 1 𝑎2 𝑎 𝐼𝑎1 = 1 𝑎2 𝑎 𝐼𝑎1
• But, 𝐼𝑐 1 𝑎 𝑎2 𝐼𝑎2 1 𝑎 𝑎2 −𝐼𝑎1
𝐼𝑏 = (𝑎2 −𝑎)𝐼𝑎1
(𝑎 2 −𝑎)𝑉𝑎1 − (𝑎2 −𝑎)𝑉𝑎2 = (𝑎2 −𝑎)𝐼𝑎1 𝑍𝑓
Line to line fault on an unloaded
synchronous generator through a fault impedance (cont.)
(𝑎2 −𝑎)𝑉𝑎1 − (𝑎2 −𝑎)𝑉𝑎2 = (𝑎2 −𝑎)𝐼𝑎1 𝑍𝑓
𝑉𝑎1 = 𝐸𝑎 − 𝐼𝑎1 𝑍1
𝑉𝑎0 = 0
𝑉𝑎 1 1 1 𝑉𝑎0 1 1 1 0
𝑉𝑏 = 1 𝑎2 𝑎 𝑉𝑎1 = 1 𝑎2 𝑎 𝑉𝑎1
𝑉𝑐 1 𝑎 𝑎2 𝑉𝑎2 1 𝑎 𝑎2 𝑉𝑎1
3𝐸𝑎
• Fault current is 𝐼𝑏 = −𝐼𝑐 = −𝑗
(𝑍1 +𝑍2 +𝑍𝑓 )
Problem 2
A 20 MVA, 13.8 kV generator has a direct axis subtransient reactance of 0.25 per unit. The
negative and zero sequence reactances are 0.35 and 0.10 per unit respectively. The neutral of the
generator is solidly grounded. Find the subtransient currents and the line to line voltages at the fault
under subtransient conditions when a line to line fault occurs. Assume that the generator is
unloaded and operating at rated terminal voltage when the fault occurs.
Solution
𝐸𝑎 1.0
𝐼𝑎1 = = = −𝑗1.667𝑝𝑢
𝑍1 + 𝑍2 𝑗0.25 + 𝑗0.35
𝐼𝑎0 = 0
20 × 1000
𝐼𝑏 = −𝑗 3𝐼𝑎1 = −𝑗 3 −𝑗1.667 = −2.892𝑝𝑢 = −2.892 × = −2420𝐴
3 × 13.8
𝑉𝑎0 0 𝑍0 0 0 𝐼𝑎0
𝑉𝑎1 = 𝐸𝑎 − 0 𝑍1 0 𝐼𝑎1
𝑉𝑎2 0 0 0 𝑍2 𝐼𝑎2
𝑉𝑎0 0 𝑗0.1 0 0 0 0
𝑉𝑎1 = 1 − 0 𝑗0.25 0 −𝑗1.667 = 0.584
𝑉𝑎2 0 0 0 𝑗0.35 𝑗1.667 0.584
Solution
𝑉𝑎 1 1 1 𝑉𝑎0 1 1 1 0 1.168∠00
𝑉𝑏 = 1 𝑎2 𝑎 𝑉𝑎1 = 1 1∠2400 1∠1200 0.584 = −0.584
𝑉𝑐 1 𝑎 𝑎2 𝑉𝑎2 1 1∠1200 1∠2400 0.584 −0.584
13.8
𝑉𝑎𝑏 = 𝑉𝑎 − 𝑉𝑏 = 1.168 + 0.584 = 1.752∠00 𝑝𝑢 = 1.752 × = 13.95∠00 𝑘𝑉
3
𝑉𝑏𝑐 = 𝑉𝑏 − 𝑉𝑐 = −0.584 + 0.584 = 0
13.8
𝑉𝑐𝑎 = 𝑉𝑐 − 𝑉𝑎 = −0.584 − 1.168 = 1.752∠1800 = 1.752 × = 13.95∠1800 𝑘𝑉
3
13.8
• The voltage base is taken as because the internal voltage is taken as 1.0 pu, which is the
3
phase to neutral voltage.
Line to line to ground fault on an unloaded
synchronous generator
• The circuit diagram for line to line to ground fault is shown in figure.
• The conditions under fault:
• 𝑉𝑏 = 𝑉𝑐 = 0 , 𝐼𝑎 = 0
𝑉𝑎0 1 1 1 𝑉𝑎 𝑉𝑎 /3
𝑉𝑎1 = 1/3 1 𝑎 𝑎2 0 = 𝑉𝑎 /3
𝑉𝑎2 1 𝑎2 𝑎 0 𝑉𝑎 /3
𝑍1 𝑍1 1 1
⇒ 𝐼𝑎1 1+ + = 𝐸𝑎 +
𝑍0 𝑍2 𝑍0 𝑍2
𝑍 𝑍
1 + 𝑍1 + 𝑍1
0 2
⇒ 𝐼𝑎1 = 𝐸𝑎
1 1
+ • Sequence voltages are equal, so they have to
𝑍0 𝑍2
1 𝑍1
be connected in parallel.
⇒ 𝐼𝑎1 + = 𝐸𝑎
1
+
1 1
+
1 • The sequence current equation is also
𝑍0 𝑍2 𝑍0 𝑍2 satisfied in the diagram.
⇒ 𝐼𝑎1 𝑍0 || 𝑍2 + 𝑍1 = 𝐸𝑎
𝐸𝑎
⇒ 𝐼𝑎1 =
𝑍1 + 𝑍0 || 𝑍2
Line to line to ground fault on an unloaded
synchronous generator
𝑉𝑎0 = 𝑉𝑎1 = 𝑉𝑎2 = 𝐸𝑎 − 𝐼𝑎1 𝑍1
𝑉𝑎2
𝐼𝑎2 = −
𝑍2
𝑉𝑎0
𝐼𝑎0 = −
𝑍0
𝐼𝑏 = 𝐼𝑎0 + 𝑎2 𝐼𝑎1 + 𝑎𝐼𝑎2
𝐸𝑎 − 𝐼𝑎1 𝑍1
𝐼𝑎0 = −
𝑍0 +3 𝑍𝑓
Line to line to ground fault on an unloaded
synchronous generator through a fault impedance (cont.)
𝐼𝑎 = 𝐼𝑎0 + 𝐼𝑎1 + 𝐼𝑎2 = 0
𝐸𝑎 −𝐼𝑎1 𝑍1 𝑉𝑎2
𝐼𝑎 = − + 𝐼𝑎1 − =0
𝑍0 +3 𝑍𝑓 𝑍2
𝐸𝑎 −𝐼𝑎1 𝑍1 𝐸𝑎 −𝐼𝑎1 𝑍1
𝐼𝑎 = − + 𝐼𝑎1 − =0
𝑍0 +3 𝑍𝑓 𝑍2
𝑍1 𝑍1 1 1
⇒ 𝐼𝑎1 1+ + = 𝐸𝑎 +
𝑍0 +3 𝑍𝑓 𝑍0 +3 𝑍𝑓 𝑍0 +3 𝑍𝑓 𝑍0 +3 𝑍𝑓
𝐸𝑎
⇒ 𝐼𝑎1 =
𝑍1 + 𝑍0 +3 𝑍𝑓 )|| 𝑍2
Problem 3
• A 20 MVA, 13.8 kV generator has a direct axis subtransient reactance of 0.25 per unit. The
negative and zero sequence reactances are 0.35 and 0.10 per unit respectively. The neutral of the
generator is solidly grounded. Find the subtransient currents and the line to line voltages at the
fault under subtransient conditions when a double line to ground fault occurs. Assume that the
generator is unloaded and operating at rated terminal voltage when the fault occurs.
Solution
𝐸𝑎 1.0
𝐼𝑎1 = = = −𝑗3.05𝑝𝑢
𝑍0 𝑍2 𝑗0.1 × 𝑗0.35
𝑍0 + 𝑍2 + 𝑍1 𝑗0.1 + 𝑗0.35
+ 𝑗0.25
𝑉𝑎2 0.237
𝐼𝑎2 = − =− = 𝑗0.68𝑝𝑢
𝑍2 𝑗0.35
𝑉𝑎0 0.237
𝐼𝑎0 = − =− = 𝑗2.37𝑝𝑢
𝑍0 𝑗0.1
𝐼𝑏 = 𝐼𝑎0 + 𝑎2 𝐼𝑎1 + 𝑎𝐼𝑎2 = 𝑗2.37 + 𝑎2 × −𝑗3.05 + 𝑎 × 𝑗0.68 = 4.81∠132.5°
𝐼𝑐 = 𝐼𝑎0 + 𝑎𝐼𝑎1 + 𝑎2 𝐼𝑎2 = 𝑗2.37 + 𝑎 × −𝑗3.05 + 𝑎2 × 𝑗0.68 = 4.81∠47.5°
20 × 1000
𝐼𝑓 = 𝐼𝑏 + 𝐼𝑐 = 𝑗7.11𝑝𝑢 = 𝑗7.11 × = 5950∠90°
3 × 13.8
Solution
𝑉𝑏 = 𝑉𝑐 = 0
13.8
𝑉𝑎𝑏 = 𝑉𝑎 − 𝑉𝑏 = 0.711 − 0.711𝑝𝑢 = 0.711 × = 5.66∠00 𝑘𝑉
3
𝑉𝑏𝑐 = 𝑉𝑏 − 𝑉𝑐 = 0
13.8
𝑉𝑐𝑎 = 𝑉𝑐 − 𝑉𝑎 = 0 − 0.711 = −0.711 = −0.711 × = 5.66∠1800 𝑘𝑉
3
Problem 4
• A 60 Hz turbogenerator is rated 10,000 kVA, 13.8 kV. It is Y-connected, solidly grounded and is
operating at rated voltage at no load. It is disconnected from the rest of the system. Its reactances
are X’’=X2=0.15 and X0=0.05 per unit. Find the following:
A) ratio of the subtransient line current for a single line to ground fault to the subtransient
line current for a symmetrical three phase fault.
B) ratio of the subtransient line current for a line to line fault to the subtransient line
current for a symmetrical three phase fault.
Solutions
• Single line to ground fault:
3𝐸𝑎 3 × 1.0
𝐼𝑓 = 𝐼𝑎 = = = −𝑗8.571𝑝𝑢
(𝑍0 + 𝑍1 +𝑍2 ) 𝑗0.05 + 𝑗0.15 + 𝑗0.15
• Line to line fault
𝐸𝑎 1.0
𝐼𝑓 = 𝐼𝑏 = −𝑗 3𝐼𝑎1 = −𝑗 3 = −𝑗 3 = −5.773𝑝𝑢
(𝑍1 +𝑍2 ) 𝑗0.15 + 𝑗0.15
• Three phase fault:
𝐸𝑎 1.0
𝐼𝑓 = 𝐼𝑎 = = = −𝑗6.667𝑝𝑢
𝑍1 𝑗0.15
𝐼𝑓_𝑆𝐿𝐺
• Case A: = 8.571/6.667 = 1.286
𝐼𝑓_3𝑝ℎ
𝐼𝑓_𝐿𝐿
• Case B: = 5.773/6.667 = 0.866
𝐼𝑓_3𝑝ℎ
Problem 5
• A generator is rated 500 MVA, 22 kV. It is Y-connected, solidly grounded and is operating at
rated voltage at no load. It is disconnected from the rest of the system. Its reactances are
X’’=X2=0.15 and X0=0.05 per unit.
A) Determine the inductive reactance in ohms to be inserted in the neutral connection of the
generator to limit the subtransient current for single line to ground fault to that of three
phase fault.
B) With the inductive reactance inserted, find the ratio of subtransient line currents for double
line to ground fault to the subtransient line current for a three phase fault
Solution
• Three phase fault current
𝐸𝑎 1.0
𝐼𝑓 = 𝐼𝑎 = = = −𝑗6.667𝑝𝑢
𝑍1 𝑗0.15
(A)
• Let ‘x’ be the inductive reactance to be inserted in the neutral,
• Single line to ground fault current
3𝐸𝑎 3 × 1.0
𝐼𝑓 = 𝐼𝑎 = = = −𝑗6.667𝑝𝑢
(𝑍0 + 𝑍1 +𝑍2 ) 𝑗0.05 + 𝑗3𝑥 + 𝑗0.15 + 𝑗0.15
3
= −𝑗6.667 ⇒ x = 0.0333pu
𝑗(0.35 + 𝑥)
222
x = 0.0333 × = 0.3226𝑜ℎ𝑚
500
Solution
(B) Double line to ground fault current
𝑍0 = 𝑗0.05 + 𝑗3 × 0.0333 = 𝑗0.15
𝐸𝑎 1.0
𝐼𝑎1 = = = −𝑗4.44𝑝𝑢
𝑍0 𝑍2 𝑗0.15 × 𝑗0.15
𝑍0 + 𝑍2 + 𝑍1 𝑗0.15 + 𝑗0.15
+ 𝑗0.15
𝑗0.15
𝐼𝑎2 = 𝐼𝑎0 = −𝑗4.44 = 𝑗2.22𝑝𝑢
𝑗0.3
𝐼𝑏 = 𝐼𝑎0 + 𝑎2 𝐼𝑎1 + 𝑎𝐼𝑎2 = 𝑗2.22 + 𝑎2 × −𝑗4.44 + 𝑎 × 𝑗2.22 = 6.667∠150°
𝐼𝑐 = 𝐼𝑎0 + 𝑎𝐼𝑎1 + 𝑎2 𝐼𝑎2 = 𝑗2.22 + 𝑎 × −𝑗4.44 + 𝑎2 × 𝑗2.22 = 6.667∠30°
𝐼𝑓 = 𝐼𝑏 + 𝐼𝑐 = 𝑗6.667𝑝𝑢
𝐼𝑓_𝐿𝐿𝐺
= 6.667/6.667 = 1.0
𝐼𝑓_3𝑝ℎ