Design calculation sheet

Project no.: Date: Sheet no.: Computed by:

Subject: Checked by:

Approved by:

Hydraulic Calculation:

1- Determine the area of sprinkler operation (ft2)

Hazard Type Minimum area of sp. Operation


ft2 m2
Light 1500 139.4
Ordinary 1500 139.4
Extra 2500 232.3

2- Select a hydraulic design density (gpm/ft2) from chart

3- Calculate minimum flow and pressure at the hydraulically most demanding sprinkler

Flow = Design Density x Area Covered by Sprinkler QK P


2
Q
Pressure = ( Sprinkler Flow / Sp. Discharge Coeff. (K) ) ^2 P   
K 

For standard sprinkler: K = 5.6 (US) = 80.6 (metric)