AS 5100.5:2017
Bridge design
Part 5: Concrete
AP-G51.5-17
AS 5100.5:2017
This Australian Standard® was prepared by Committee BD-090, Bridge Design. It was
approved on behalf of the Council of Standards Australia on 17 March 2017.
This Standard was published on 31 March 2017.
Standards Australia wishes to acknowledge the participation of the expert individuals that
contributed to the development of this Standard through their representation on the
Committee and through the public comment period.
Standards may also be withdrawn. It is important that readers assure themselves they are
using a current Standard, which should include any amendments that may have been
published since the Standard was published.
Detailed information about Australian Standards, drafts, amendments and new projects can
be found by visiting www.standards.org.au
Australian Standard®
Bridge design
Part 5: Concrete
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
Originated as HB 77.5—1996.
Revised and redesignated as AS 5100.5—2004.
Second edition 2017.
COPYRIGHT
© Standards Australia Limited
All rights are reserved. No part of this work may be reproduced or copied in any form or by
any means, electronic or mechanical, including photocopying, without the written
permission of the publisher, unless otherwise permitted under the Copyright Act 1968.
Published by SAI Global Limited under licence from Standards Australia Limited, GPO Box
476, Sydney, NSW 2001, Australia
ISBN 978 1 76035 718 4
AS 5100.5:2017 2
PREFACE
This Standard was prepared by Standards Australia Committee BD-090, Bridge Design, to
supersede AS 5100.5—2004.
This Standard is also designated as Austroads publication AP-G51.5-17.
The objectives of the AS(AS/NZS) 5100 series are to provide nationally acceptable
requirements for—
(a) the design of road, rail, pedestrian and cyclist path bridges;
(b) the specific application of concrete, steel and composite construction, which embody
principles that may be applied to other materials in association with relevant
Standards; and
(c) the assessment of the load capacity and rehabilitation of existing bridges.
These requirements are based on the principles of structural mechanics and knowledge of
material properties, for both the conceptual and detailed design, to achieve acceptable
probabilities that the bridge or associated structure being designed will not become unfit for
use during its design life.
The objective of this Part (AS 5100.5) is to specify requirements for the design and
construction of concrete bridges and associated structures.
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
Whereas earlier editions of the Bridge design series were essentially administered by the
infrastructure owners and applied to their own inventory, an increasing number of bridges
are being built under the design-construct-operate principle and being handed over to the
relevant statutory authority after several years of operation. This Standard includes clauses
intended to facilitate the specification to the designer of the functional requirements of the
owner, to ensure the long-term performance and serviceability of the bridge and associated
structure.
Significant changes to the 2004 edition of AS 5100.5 are as follows:
(a) Increase in concrete strength specified in design rules from 65 MPa to 100 MPa. This
has resulted in the review of all equations in AS 5100.5 for strength and has meant, in
some instances, modification of equations such as the rectangular stress block model
and inclusion of requirements for confinement to the core of columns.
The application of the Standard is further influenced by the ductility class of the steel
reinforcement, with some new restrictions applying to the use of Ductility Class L
reinforcement. Ductility Class N stainless steel reinforcement may now be used.
(b) Section 2 ‘Design procedures actions and loads’, has been revised to align with the
AS/NZS 1170 series, Structural design actions, and additional design check methods
for designers to consider has been included.
(c) Section 3 ‘Design properties of materials’ has been reviewed to include—
(i) new shrinkage equations, to address autogenous and drying shrinkage; and
(ii) creep calculations, to modify the creep factor by revising the k2 and k3 factors,
including the addition of environmental and humidity factors.
(d) Specification of additional severe exposure classifications and requirements for
sulfate soils introduced in Section 4 on durability.
(e) The fire resistance criteria in Section 5 ‘Design for fire resistance’ have been
updated.
(f) Section 6 ‘Methods of structural analysis’ has been completely revised.
3 AS 5100.5:2017
CONTENTS
Page
TESTING................................................................................................................... 38
2.7 OTHER DESIGN REQUIREMENTS ........................................................................ 38
APPENDICES
A TESTING OF MEMBERS AND STRUCTURES.................................................... 200
B BEAM STABILITY DURING ERECTION ............................................................ 206
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
STANDARDS AUSTRALIA
Australian Standard
Bridge design
Part 5: Concrete
1.1 SCOPE
This Standard sets out minimum requirements for the design and construction of concrete
bridges and associated structures that contain reinforcement or tendons, or both. It also sets
out minimum requirements for plain and steel fibre reinforced concrete (SFRC) members.
NOTES:
1 It is intended that the properties and requirements for reinforcement or tendons, as set out in
this Standard, may also be used for the design and construction of elements not containing
concrete, for example, stress laminated timber decks.
2 For design life of bridges covered by this Standard, see Clause 4.1.
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
1.2 APPLICATION
This Standard applies to structures and members in which the materials conform to the
following:
(a) Concrete with—
(i) characteristic compressive strength at 28 days ( f c ) in the range of 25 MPa to
100 MPa; and
(ii) with a saturated surface-dry density in the range 2100 kg/m3 to 2800 kg/m3.
(b) Reinforcing steel of Ductility Class N in accordance with AS/NZS 4671.
NOTE: Reinforcement types with this ductility may be used without restriction, in all
applications referred to in this Standard, except where Ductility Class E reinforcing steel is
required.
(c) Reinforcing steel of Ductility Class E in accordance with AS/NZS 4671.
NOTE: Reinforcement types of this ductility class will need to be specially sourced to be used
in Australia.
(d) Reinforcing steel of Ductility Class L in accordance with AS/NZS 4671 shall not be
used in the design for strength, except in any of the following—
(i) As transverse shear and torsion reinforcement provided the additional
requirements specified in Clause 3.2.1 are satisfied.
(ii) As longitudinal shear reinforcement provided the additional requirements
specified in Clause 3.2.1 are satisfied.
(iii) As lateral restraint to longitudinal reinforcement and reinforcement for
confinement of the core in columns.
(iv) As bursting reinforcement in prestressed concrete anchorages.
concrete—Slump test
1012.3.5 Method 3.5: Determination of properties related to the consistency of
concrete--Slump flow, T500 and J-ring test
1012.4 Method 4: Determination of air content of freshly mixed concrete (all
methods)
1012.9 Method 9: Compressive strength tests—Concrete, mortar and grout
specimens
1012.10 Method 10: Determination of indirect tensile strength of concrete cylinders
(‘Brazil’ or splitting test)
1012.11 Method 11: Determination of the modulus of rupture
1012.12.1 Method 12.1: Determination of mass per unit volume of hardened concrete—
Rapid measuring method
1012.12.2 Method 12.2: Determination of mass per unit volume of hardened concrete—
Water displacement method
1012.13 Method 13: Determination of the drying shrinkage of concrete for samples
prepared in the field or in the laboratory
1012.14 Method 14: Method for securing and testing cores from hardened concrete
for compressive strength
1012.16 Method 16: Determination of creep of concrete cylinders in compression
1012.17 Method 17: Determination of the static chord modulus of elasticity and
Poisson’s ratio of concrete specimens
1012.20.1 Method 20.1: Determination of chloride and sulfate in hardened concrete and
aggregates—Nitric acid extraction method
1012.20.2 Method 20.2: Determination of water-soluble chloride in aggregates and
hardened concrete
1100 Technical drawing
1100.501 Part 501: Structural engineering drawing
1199 Sampling procedures and tables for inspection by attributes
1199.1 Part 1: Sampling schemes indexed by acceptance quality limit (AQL) for lot-
by-lot inspection
AS
1379 Specification and supply of concrete
1478 Chemical admixtures for concrete, mortar and grout
1478.1 Part 1: Admixtures for concrete
3600 Concrete structures
3610 Formwork for concrete
3610.1 Part 1: Documentation and surface finish
3799 Liquid membrane-forming curing compounds for concrete
AS/NZS
1170 Structural design actions
1170.0 Part 0: General principles
1554 Structural steel welding
1554.3 Part 3: Welding of reinforcing steel
1554.6 Part 6: Welding stainless steels for structural purposes
1597 Precast reinforced concrete box culverts
1597.2 Part 2: Large culverts (exceeding 1200 mm span or 1200 mm height and up to
and including 4200 mm span and 4200 mm height)
1768 Lightning protection
2425 Bar chairs in reinforced concrete—Product requirements and test methods
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
EN
14889 Fibres for concrete
14889-1 Part 1: Steel fibres—Definitions, Specifications and Conformity
BS
6744 Stainless steel bars—Reinforcement of concrete—Requirements and test
methods
1.4 DEFINITIONS
1.4.1 General
For the purposes of this Standard, the definitions below apply.
1.4.2 Administrative definitions
1.4.2.1 Approved
Except as may be otherwise stated, approved by authority.
1.4.2.2 Authority
The body with jurisdiction over the provision of bridges and associated structures, and/or
responsible for the design, construction and maintenance of bridges within its jurisdiction.
1.4.2.3 Drawings
The drawings forming part of the documents setting out the work to be executed.
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
1.4.2.4 Specification
The specification forming part of the documents setting out the work to be executed.
1.4.3 Technical definitions
1.4.3.1 Action
Set of concentrated or distributed forces acting on a structure (direct action), or deformation
imposed on a structure or constrained within it (indirect action).
NOTE: The term ‘load’ is often used to describe direct actions.
1.4.3.2 Action effects
Internal forces and bending moments due to actions (stress resultants).
1.4.3.3 Anchorage zone
Region between the face of the member where the prestress is applied and the cross-section
at which a linear distribution of stress due to prestress is achieved.
1.4.3.4 Average ambient temperature
Average value of the daily maximum and minimum ambient temperatures over the relevant
period at a site.
1.4.3.5 B-region
Portion of a member in which the assumption that plane sections remain plane can be
applied.
1.4.3.6 Basic creep coefficient (φcc.b)
Mean value of the ratio of final creep strain to elastic strain for a specimen loaded at
28 days under a constant stress of 0.4 f c .
1.4.3.7 Bottle-shaped compression field
Compression field that is wider at mid-length than at its ends.
admixtures.
1.4.3.14 Construction joint
Joint that is located in a structure or part of a structure for convenience of construction and
made so that the load-carrying capacity and serviceability of the structure, or part of the
structure, will be unimpaired by the inclusion of the joint.
1.4.3.15 Cover
Distance between the outside of the reinforcing steel or tendons and the nearest permanent
surface of the member, excluding any applied surface finish.
1.4.3.16 Creep coefficient
Mean value of the ratio of creep strain to elastic strain under conditions of constant stress.
1.4.3.17 Critical shear perimeter
Perimeter defined by a line geometrically similar to the boundary of the effective area of a
support or concentrated load and located at a distance of d om/2 therefrom (see Figure 9.2.3).
1.4.3.18 Critical opening
Opening through the thickness of a slab where an edge, or part of the edge, of the opening
is located at a clear distance of less than 2.5b o from the critical shear perimeter [see
Figure 9.2.3(b)].
1.4.3.19 Design life
The period assumed in design for which a structure or a structural element required to
perform its intended purpose with minimal maintenance and without replacement or major
structural repairs.
1.4.3.20 Discontinuity
Abrupt change in geometry or loading, including prestress.
reinforcing bars in a column or pile, to restrain them from buckling and to carry shear,
torsion and diagonal tension, or around tendons at an anchorage to resist bursting action
effects.
1.4.3.39 Initial force
Force, immediately after transfer, at a stated position in a tendon.
1.4.3.40 Jacking force
Force in a tendon measured at the jack.
1.4.3.41 Ligature (reinforcement)
See fitment, Clause 1.4.3.32.
1.4.3.42 Limit state
As defined in AS 5100.1.
1.4.3.43 Mean strength
Statistical average of a number of test results representative of the strength of a member,
prototype or material.
1.4.3.44 Moist curing
Supplying additional moisture to the concrete surface by means of a complete and
continuous application of water to the surface of the concrete.
1.4.3.45 Movement joint
Joint that is made between parts of a structure for the specific purpose of permitting relative
movement between the parts of the structure on either side of the joint.
1.4.3.46 Node
Point in a joint in a strut-and-tie model where the axes of the struts, ties and concentrated
forces acting on the joint intersect.
1.4.3.65 Tendon
Wire, strand or bar (or any discrete group of such wires, strands or bars) that is intended to
be pretensioned or post-tensioned.
1.4.3.66 Tie
Tension member in a strut-and-tie model.
1.4.3.67 Transfer
Time of initial transfer of prestressing forces from the tendons to the concrete.
1.4.3.68 Transmission length
Length, at transfer, over which the stress in a pretensioned tendon builds up from zero at
one end to its full value.
1.4.3.69 Two-way slab
Slab characterized by significant flexural action in two directions at right angles to one
another.
1.4.3.70 Unbonded tendon
A post-tensioned tendon fabricated from sheathed prestressing strands, bars or rods
connected to the structure by anchorage only.
1.4.3.71 Uniform strain
Strain in the reinforcement at maximum stress, corresponding to the onset of necking.
1.4.3.72 Upper characteristic strength
Value of the material strength, as assessed by standard test, which is exceeded by 5% of the
material.
1.5 NOTATION
The symbols used in this Standard, including their definitions, are listed below.
Unless a contrary intention appears, the following applies:
(a) The symbols used in this Standard have the meanings ascribed to them below, with
respect to the structure, or member, or condition to which a clause is applied.
(b) Where non-dimensional ratios are involved, both the numerator and denominator are
expressed in identical units.
(c) The dimensional units for length, force and stress, in all expressions or equations, are
to be taken as millimetres (mm), newtons (N) and megapascals (MPa) respectively,
unless noted otherwise.
(d) An asterisk (*) placed after a symbol as a superscript (for example, M y* ) denotes a
design action effect due to the design load.
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
Symbol Definition
Ab cross-sectional area of a reinforcing bar
Ab.fit cross-sectional area of the fitment
Ac smallest cross-sectional area of the concrete strut at any point along its
length and measured normal to the line of action of the strut
Acp total area enclosed by outside perimeter of concrete section
Act area of concrete on flexural tension side of member; or
area of concrete within the tensile zone (mm2).
NOTE: The tensile zone is that part of the cross-section calculated to be in
tension just before formation of the first crack
Ag gross cross-sectional area of a member
Am an area enclosed by the median lines of the walls of a single cell
Ao area enclosed by shear flow path, including any area of holes therein
Aoh area enclosed by centre-line of exterior closed transverse torsion
reinforcement, including area of holes (if any)
Ap cross-sectional area of tendons
Apt cross-sectional area of the tendons in the zone that will be tensile under
ultimate load conditions
As cross-sectional area of reinforcement; or
cross-sectional area of a single anchored bar of diameter db
Asc cross-sectional area of longitudinal compressive reinforcement
Asf area of fully anchored reinforcement crossing the interface
Asi area of reinforcement in the ith direction crossing a strut
of the tendons in the zone of the concrete in tension under ultimate strength
conditions
ds overall dimension measured between centre-lines of the outermost fitments;
or
distance from the extreme compression fibre to the centroid of non-
prestressed tensile reinforcement
dsc distance from the extreme compressive fibre of the concrete to the centroid
of compressive reinforcement
dsp distance of the out-of-plane splitting force that may be considered
dv effective shear depth
Ec mean value of the modulus of elasticity of concrete at 28 days
Ecj mean value of the modulus of elasticity of concrete at age j
Ed design action effect
Ep modulus of elasticity of tendons, determined in accordance with
Clause 3.3.2
Epθ modulus of elasticity of tendons at elevated temperatures
Es modulus of elasticity of reinforcement, determined in accordance with
Clause 3.2.2
Esθ modulus of elasticity of steel reinforcement at elevated temperatures
e eccentricity of prestressing force or load; or
base of Napierian logarithms
eo vertical eccentricity between the centre of gravity of a beam and the
longitudinal axis through the lifting points
F force
f R,2 mean residual flexural strength determined at a crack mouth opening
displacement (CMOD) of 1.5 mm as determined from a 3-point notch
bending test undertaken in accordance with EN 14651
f R,4 mean residual flexural strength determined at a crack mouth opening
displacement (CMOD) of 3.5 mm as determined from a 3-point notch
bending test undertaken in accordance with EN 14651
f1.5 characteristic residual tensile strength of steel fibre reinforced concrete
(SFRC)
G permanent action (dead load)
gp permanent distributed load normal to the shear interface per unit length, in
newtons per millimetre
Hw floor-to-floor unsupported height of a wall
Hwe effective height of a wall
h overall depth of a joint
I second moment of area of the uncracked concrete cross-section about the
centroidal axis
Ic second moment of area of a concrete section
Icr second moment of area of a cracked section with the reinforcement
transformed to an equivalent area of concrete
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
ku neutral axis parameter being the ratio, at ultimate strength under any
combination of bending and compression, of the depth to the neutral axis
from the extreme compressive fibre to d
kuo ratio, at ultimate strength, without axial force of the depth to the neutral
axis from the extreme compressive fibre to do
k1 a coefficient which allows for the effect of non-uniform self-equilibrating
stresses due to non-linear shrinkage or temperature profiles through the
member depth
k1 compressive strength factor for concrete at elevated temperatures
k2 tension reinforcement factor with strain 2%
k3 modulus of elasticity factor of steel reinforcement at elevated temperatures
k4 minimum tensile strength factor of tendons at elevated temperatures
k5 modulus of elasticity of tendons factor at elevated temperatures
L centre-to-centre distance between the supports of a flexural member
Le effective length of a column
Lef effective span of a member, taken as the lesser of ( Ln + D) and L for a beam
or slab; or
Ln + D/2 for a cantilever
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
M x* , M y* design bending moment in a column about the major and minor axes
respectively under the design axial force N*
M 1* , M 2* smaller and larger design bending moment respectively at the ends of a
column
Mc moment used in the calculation of the buckling load (Nc)
Mcr bending moment causing cracking of the section with due consideration to
prestress, restrained shrinkage and temperature stresses
Mg bending moment due to self-weight plus dynamic allowance at
serviceability limit state (SLS)
Mu ultimate strength in bending at a cross-section of an eccentrically loaded
compressive member
Mub particular ultimate strength in bending when kuo = 0.003/(0.003 + fsy / Es)
Muo ultimate strength in bending, without axial force, at a cross-section
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
N G* design axial force due to permanent effects at the ultimate limit state (ULS)
Tb.cr bursting (or splitting) force across a strut caused at the time of cracking of
the strut
Tcr torsional cracking moment
Tu ultimate torsional strength
Tuc ultimate torsional strength of a beam without torsional reinforcement and in
the presence of shear
Tus ultimate torsional strength of a beam with torsional reinforcement
Tu.max ultimate torsional strength of a beam limited by web crushing failure
Tw vertical component of the force carried by the secondary struts
t time
coefficient of friction; or
structural ductility factor; or
displacement ductility
v Poisson’s ratio for concrete, determined in accordance with Clause 3.1.5
ρ density of plain concrete, in kilograms per cubic metre (kg/m3), determined
in accordance with Clause 3.1.3
ρccj residual creep coefficient; or
residual shrinkage coefficient
ρp transverse compressive pressure at the ultimate limit state (ULS) along the
development length perpendicular to the plane of splitting in megapascals
ρs volumetric ratio of the fitments relative to the volume of the core
σci sustained stress in the concrete at the level of the centroid of the tendons,
calculated using the initial prestressing force prior to any time-dependent
losses and the sustained portions of all the service loads
σcp average intensity of effective prestress in concrete
σcp.f compressive stress due to prestress, at the extreme fibre where cracking
occurs
σcs maximum shrinkage-induced tensile stress on the uncracked section at the
extreme fibre at which cracking occurs
σ min minimum compressive stress at the extreme fibres under consideration,
taken as zero if tensile.
σ max maximum compressive stress at the extreme fibres under consideration.
σ max σ min maximum permissible stress range under fatigue loading for the calculated
σ min and equal to 0.45 f c when σmin is zero.
σo a constant sustained stress
σp effective stress in the prestressing tendon at the time under consideration
σpa stress in the tendon at a distance ‘a’, measured from the jacking end
σp.ef effective stress in the tendon after allowing for all losses
σpi stress in the tendon immediately after transfer
σpj maximum stress in the tendon at the jacking end
σpu maximum stress that would be reached in a tendon at ultimate strength of a
flexural member
σsc a compressive stress being developed in a bar in compression
σscr tensile steel stress at the serviceability limit state (SLS) for a beam in
flexure or in tension or for a slab in flexure
σst tensile stress in reinforcement
τ* design shear stress acting on the interface
τu shear stress capacity
capacity reduction factor for design using linear elastic analysis
s stress reduction factor for design using linear stress analysis
st strength reduction factor for design using strut-and-tie analysis
sys system strength reduction factor for design using non-linear methods of
analysis
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
1.6 CONSTRUCTION
All concrete structures, designed in accordance with this Standard, shall be constructed so
that all the requirements of the design, as contained in the drawings and specifications, are
achieved.
1.8 DESIGN
1.8.1 Design data
In addition to the data specified in AS 5100.1, the drawings shall include the following
design data:
(a) Exposure classification for durability and associated cover to reinforcing steel and
tendons.
(b) Class and grade of concrete.
(c) Grade, ductility class and type of reinforcement and grade and type of tendons.
(d) Reference number and date of issue of applicable design Standards.
(e) Design life (if not 100 years).
1.8.2 Design details
The drawings or specifications for concrete members and structures shall include, as
appropriate, the following:
(a) The shape and size of each member.
(b) The finish and method of control for unformed surfaces.
(c) Class of formwork for the surface finish specified.
(d) The number of bars, size, bar shape, spacing and location of all reinforcement to
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
The maximum shear force in concrete slabs, as determined in accordance with Clause 9.2
under the combination of permanent effects and the fatigue design loading, shall be limited
to the values specified in this Clause.
Where the slab can act as a wide beam and a shear failure could occur across a substantial
width, the maximum calculated shear shall be limited to 0.60 times the value of Vu in
accordance with Clause 9.2. For slabs where the effective number of stress cycles is greater
than 2 000 000, the maximum calculated shear shall be limited to 0.54 times the value of
Vu. If the longitudinal tensile reinforcement ratio (Ast + Apt)/(bdo) is less than 0.01, the
permissible shear shall be reduced by multiplying the permissible value of Vu by the factor
[100(Ast + Apt)/(bdo)]1/3.
Where the potential failure surface could form a truncated cone or pyramid around a
support or loaded area, the maximum calculated shear shall be limited to 0.50 times the
value of Vuo specified in Clause 9.2.3.
2.2.5 Tensile stress range in steel
The maximum tensile stress range in tendons and reinforcement under the fatigue loading
specified in AS 5100.2 shall be limited to the appropriate values given in Table 2.2.5. These
stress ranges are applicable for 2 000 000 stress cycles.
To account for the design number of stress cycles (n), determined from AS 5100.2, the
values given in Table 2.2.5 shall be multiplied by the stress range factor αf—
where
αf = (2 106/n)1/3 . . . 2.2.5
0.74
In areas of high fluctuating stresses, such as in deck slabs, welded lap splices shall not be
used. All other welding, including tack-welding of reinforcing bar shall be in accordance
with AS/NZS 1554.3, or welded mesh in accordance with AS/NZS 4671, as appropriate.
The design for fatigue of welded reinforcement and welded mesh shall be in accordance
with recognised verification methods as approved by the relevant authority.
NOTE: Suitable verification methods for fatigue of welded reinforcement include:
(a) EN 1992-1-1
(b) EN 1992-2
(c) AASHTO LRFD
(d) FIB Model Code 2010
TABLE 2.2.5
PERMISSIBLE TENSILE FATIGUE
STRESS RANGES IN STEEL
Type of steel embedded in Fatigue design stress range
concrete limit, MPa
Reinforcement 150 (0.35 + 0.026d i /d b )
Prestressing wires and strands 150
in grouted plastic ducts
Prestressing wires, strands and 100
bars in grout steel ducts
Deflected pretensioned strands 70
and bent reinforcing bars
LEGEND:
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
TABLE 2.3.2
CAPACITY REDUCTION FACTORS (ϕ)
Type of action effect Capacity reduction factor (ϕ)
(a)
Axial force without bending:
(i) Tension: 0.8
(ii) Compression 0.6
(b) Bending without axial tension or compression: 0.6 (1.19 13k uo /12) 0.8
(c) Bending with axial tension: + [(0.8 ) (N u /N uot )] and
is obtained from Item (b)
(d) Bending with axial compression, where—
(i) N u N ub 0.6
(ii) N u < N ub 0.6 + [( 0.6) (1 N u /N uot )] and
is obtained from Item (b)
(e) Shear 0.7
(f) Torsion 0.7
(g) Bearing 0.6
(h) Bending, shear and compression in plain concrete 0.6
(i) Bending, shear and tension fixings 0.6
NOTE: Ductility Class L reinforcement shall only be used in accordance with Clause 1.2.
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
2.3.3 Strength check procedure for use with linear elastic stress analysis
The strength check procedure for use with a linear elastic stress analysis of a structure or
member shall be made as follows:
(a) The structure or member shall be analysed for the critical combination of factored
actions, as specified in AS 5100.2 and Clause 2.5, by linear stress analysis, in
accordance with Clause 6.4, assuming the concrete to be uncracked, and using
accepted principles of mechanics.
(b) The calculated principal compressive stresses shall not exceed the following value:
s 0.9 f c . . . 2.3.3
where
s = stress reduction factor with values taken from Table 2.3.3
β = an effective compressive strength factor, to be evaluated as follows:
(i) In regions not containing effective confining reinforcement, β shall equal
1.0 when the principal tensile stress does not exceed f ct , otherwise β shall
equal 0.6.
(ii) In regions where effective confining reinforcement is provided, β shall be
evaluated by rational calculation taking account of the amount of
confining steel and the details used, but shall not exceed 2.
(c) Reinforcement and/or tendons shall be provided to carry all of the internal tensile
forces, with stresses not exceeding s fsy and sfpy respectively, where values for the
stress reduction factor using linear analysis (s) are in accordance with Table 2.3.3.
(d) In determining the areas of steel reinforcement, it shall be permissible to reduce the
peak stresses by averaging the stresses over an area appropriate to the size of the
member.
(e) The stress development of the reinforcement and tendons shall be determined in
accordance with Clauses 13.1 and 13.3 respectively.
Standards Australia www.standards.org.au
35 AS 5100.5:2017
TABLE 2.3.3
STRESS REDUCTION FACTORS FOR DESIGN
USING LINEAR STRESS ANALYSIS ( s)
Material Stress reduction factor
( s )
Concrete 0.6
Reinforcement and tendons 0.8
NOTE: Ductility Class L reinforcement shall only be used in
accordance with Clause 1.2.
Table 2.3.4.
(d) The tensile force in any tie shall not exceed the design strength of the tie determined
in accordance with Clause 7.3.2 where the strength reduction factor ( st) is given in
Table 2.3.4.
(e) The reinforcement and/or tendons in the ties shall be anchored in accordance with
Clause 7.3.3.
(f) The design strength of nodes shall be calculated in accordance with Clause 7.4.2 and
shall not be exceeded. The strength reduction factor (s) shall be in accordance with
Table 2.3.4.
TABLE 2.3.4
STRENGTH REDUCTION FACTORS FOR DESIGN
USING STRUT-AND-TIE ANALYSIS ( st)
Material Strength reduction factor ( st )
Concrete in compression 0.6
Steel in tension 0.8
2.3.5 Strength check procedure for use with non-linear analysis of framed structures
The strength check procedure for use with non-linear analysis of framed structures at
collapse shall be carried out as follows:
(a) It shall be confirmed that the design capacity of the structure (Rd) is equal to or
greater than the design action effect (Ed)—
Rd Ed . . . 2.3.5
(b) The design action effect (Ed) is the critical combination of factored actions as
specified in AS 5100.2 and Clause 2.5.
(c) The design capacity of the structure ( Rd = sys Ru.sys) shall be obtained using the
appropriate system strength reduction factor (sys ) given in Table 2.3.5, and the mean
capacity of the structure (Ru.sys) determined for the same combination of actions
adopted in Item (b) to evaluate Ed, by using non-linear frame analysis as specified in
Clause 6.5, with mean values of material properties.
TABLE 2.3.5
SYSTEM STRENGTH REDUCTION FACTORS FOR DESIGN USING NON-
LINEAR METHODS OF ANALYSIS ( sys )
System strength
Type of failure
reduction factor ( sys )
For structural systems in which the deflections and local deformations at high 0.7
overload are an order of magnitude greater than those for service conditions; and
yielding of the reinforcement and/or the tendon occurs well before the peak load
is reached
In all other cases 0.5 (see Note)
NOTE: Larger values than 0.5 may be used if it can be shown that, at high overload, adequate warning is given
of impending collapse.
2.3.6 Strength check procedure for use with non-linear stress analysis
The strength check procedure for use with non-linear stress analysis at collapse shall be
carried out as follows:
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
(a) It shall be confirmed that the design capacity of the structure or the component
member is equal to or greater than the design action effect—
Rd Ed . . . 2.3.6
where
Rd = design capacity of the structure or component
Ed = design action effect on the structure or the design action effects for a
component
(b) The design action effect (Ed) shall be the critical combination of factored actions (or
action effects) as specified in AS 5100.2 and Clause 2.5.
(c) The design capacity of the structure (or component) (Rd = sysRu.sys) shall be obtained
using the appropriate system strength reduction factor (sys) given in Table 2.3.5, and
the mean capacity of the structure (or component) ( Ru.sys), which shall be determined
for the same combination of actions adopted for Ed, by non-linear stress analysis as
specified in Clause 6.6, with mean values of material properties.
2.4.3 Cracking
2.4.3.1 General
Cracking in concrete structures shall be controlled by appropriate design, specification and
construction measures so that structural performance, durability and appearance of the
structure are appropriate to its intended use, which shall include cracking in both the pre-
hardened and hardened concrete states.
2.4.3.2 Control of cracking
The design requirements for the control of cracking in the hardened concrete state, as set
out in Clause 2.4.3.1, shall be deemed to be satisfied by designing the structure and
members to conform to the following requirements:
(a) Flexural cracking in concrete beams and slabs under service conditions shall be
controlled in accordance with Clause 8.6, 9.4.1, 9.4.2, 9.4.4 or 9.4.5, as appropriate.
(b) Cracking caused by shrinkage and temperature in concrete slabs shall be controlled in
accordance with Clause 9.4.3.
(c) Cracking in concrete walls under service conditions shall be controlled in accordance
with Clause 11.7.2.
(d) Cracking in D-regions under service conditions shall be controlled in accordance with
Clause 12.8.
(e) Early age thermal cracking of large and/or restrained members shall be controlled in
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
The use of reinforcing steels complying with AS/NZS 4671 having a yield strength (fsy) of
500 MPa and Ductility Class E shall be considered for members and structures requiring
increased ductility to satisfy seismic design requirements. Grade 500E reinforcement shall
not be subjected to welding or heating.
Beam stability during lifting and erection shall be in accordance with Appendix B.
The uniaxial tensile strength (fct) is the maximum stress that concrete can withstand when
subjected to uniaxial tension.
The uniaxial tensile strength shall be determined from either the measured flexural tensile
strength (fct.f) or from the measured splitting tensile strength (fct.sp) using either—
fct = 0.6 fct.f
or
fct = 0.9 fct.sp
where fct.f and fct.sp are determined statistically from—
(a) flexural strength tests carried out in accordance with AS 1012.11; or
(b) indirect tensile strength tests carried out in accordance with AS 1012.10,
respectively.
In the absence of more accurate data, the characteristic flexural tensile strength of concrete
) and the characteristic uniaxial tensile strength of concrete ( f ct ) shall be taken as—
( f ct.f
0.6 f c and f ct 0.36 f c at 28 days and standard curing,
f ct.f
where the mean and upper characteristic values are obtained by multiplying these values by
1.4 and 1.8, respectively.
3.1.1.4 Supplementary cementitious materials
3.1.1.4.1 General
Values of fct.ef shall be obtained from 0.6 f cm but not less than 3.0 MPa and fcm is the mean
concrete compressive strength at the time cracking is expected to occur.
(b) For Standard strength grades at 28 days determined from Table 3.1.2 and determined
by test in accordance with AS 1012.17.
NOTES:
1 Where Ecj is determined from Item (a) or (b) above, consideration should be given to the fact
that this value has a range of 20%.
2 Where a load is sustained and where the concrete deformation is unrestrained such that time-
dependent deflections or strains are produced, or where a deformation is sustained so that the
time-dependent stress reductions occur, the final value of the time-dependent effects may be
calculated by using an effective modulus of elasticity equal to Ec divided by (1 + cc
*
) where
cc* is taken at its final value.
TABLE 3.1.2
CONCRETE PROPERTIES AT 28 DAYS
f c , MPa 20 25 32 40 50 65 80 100
f cmi , MPa 22 28 35 43 53 68 82 99
E c , MPa 24 000 26 700 30 100 32 800 34 800 37 400 39 600 42 200
3.1.3 Density
The density of concrete (ρ) shall be either—
(a) taken as not less than 2400 kg/m3 for normal weight concrete; or
(b) determined by test in accordance with AS 1012.12.1 or AS 1012.12.2.
3.1.4 Stress-strain curves
The stress-strain curve for concrete shall be either—
(a) assumed to be of curvilinear form defined by recognized simplified equations; or
(b) determined from suitable test data.
For design purposes, the shape of the in situ uniaxial compressive stress-strain curve shall
be modified so that the maximum stress is 0.9 f c .
The maximum stress specified above shall not apply when assessing the flexural strength of
plastic hinge zones of bridge columns in accordance with Clause 10.2.4.2.
3.1.5 Poisson’s ratio
Poisson’s ratio for concrete (v) shall be either—
(a) taken as equal to 0.2; or
(b) determined by test in accordance with AS 1012.17.
3.1.6 Coefficient of thermal expansion
The coefficient of thermal expansion of concrete shall be either—
(a) taken as equal to 10 106/°C, consideration being given to the fact that this value
has a range of 20%; or
(b) determined from suitable test data.
3.1.7 Shrinkage
3.1.7.1 Calculation of design shrinkage strain
The design shrinkage strain of concrete (εcs) shall be determined—
(a) from measurements on similar local concrete;
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
(b) by tests after eight weeks of drying, in accordance with AS 1012.13 and modified for
the appropriate age; or
(c) by calculation in accordance with Clause 3.1.7.2.
3.1.7.2 Design shrinkage strain
When the design shrinkage strain of concrete (εcs) is to be calculated, it shall be determined
as the sum of the chemical (autogenous) shrinkage strain (ε cse) and the drying shrinkage
strain (εcsd), as follows:
εcs = εcse + εcsd . . . 3.1.7.2(1)
The autogenous shrinkage strain shall be taken as—
cse cse
*
1.0 e 0.1t . . . 3.1.7.2(2)
where t is the time (in days) after setting and cse
*
is the final autogenous shrinkage strain
given by—
cse
*
0.06 f c 1.0 50 10 6 . . . 3.1.7.2(3)
At any time (t), in days, after the commencement of drying, the drying shrinkage strain
shall be taken as—
csd k1k 4 csd.b . . . 3.1.7.2(4)
and k1 is obtained from Figure 3.1.7.2 and k4 is equal to 0.7 for an arid environment, 0.65
for an interior environment, 0.6 for a temperate inland environment and 0.5 for a tropical or
near-coastal environment.
The basic drying shrinkage strain ( csd.b ) shall be taken as—
csd.b 1.0 0.008 f c csd.b
*
. . . 3.1.7.2(5)
where the final drying basic shrinkage strain ( csd.b
*
) depends on the quality of the local
aggregates, which shall be taken as 800 10 for Sydney and Brisbane, 900 106 for
6
NOTES:
1 Based on a value of csd.b
*
= 1000 10 6 this method gives the typical design shrinkage strains
after 30 years shown in Table 3.1.7.2.
Consideration should be given to the fact that ε cs has a range of 30%.
2 Concrete exposed to early drying undergoes shrinkage due to capillary suction. This can
result in cracking and poor service performance, particularly of exposed slabs. The amount of
shrinkage from suction depends on the ambient conditions and the concrete mix, and can
exceed the combined shrinkage from other causes. Therefore, it is important to prevent
excessive drying of concrete between the commencement of casting and the application of
curing at the completion of finishing.
1.8
th = 50 mm
1.6
α 1t 0 . 8
k1 = t h = 10 0 m m
t 0 . 8 + 0.15 t h
1.4
α 1 = 0.8 + 1. 2e - 0 .0 0 5 t h
t h = 20 0 m m
1. 2
W h ere t i s in d ays
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
1.0
k1 th = 400 mm
0.8
0.6
0.4
0. 2
0
1 3 10 30 10 0 1 3 10 30
DAYS YE ARS
TIM E SIN CE CO M M EN CEM ENT OF DRYIN G, t
TABLE 3.1.7.2
TYPICAL DESIGN SHRINKAGE STRAINS AFTER 30 YEARS ( csd.b
*
1000 )
*
Design shrinkage strain cs 10 6
Tropical, near coastal
Temperate inland
f c Arid environment Interior environment and coastal
environment
MPa environment
t h , mm t h , mm t h , mm t h , mm
50 100 200 400 50 100 200 400 50 100 200 400 50 100 200 400
25 990 870 710 550 920 810 660 510 850 750 610 470 720 630 510 400
32 950 840 680 530 880 780 640 500 820 720 590 460 690 610 500 390
40 890 790 650 510 830 740 610 480 780 690 570 450 660 590 490 390
50 830 740 610 490 770 690 580 460 720 650 540 440 620 550 470 380
65 730 650 560 460 680 620 530 440 640 580 500 410 560 510 440 370
80 630 570 500 420 590 540 480 410 560 520 450 390 500 460 410 360
100 490 460 420 380 480 450 410 370 460 430 400 360 420 400 370 340
3.1.8 Creep
3.1.8.1 General
The creep strain at any time (t) caused by a constant sustained stress (σo) shall be calculated
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
TABLE 3.1.8.2
BASIC CREEP COEFFICENT
Characteristic strength ( f c ), MPa 20 25 32 40 50 65 80 100
Basic creep coefficient (φ cc.b) 5.2 4.2 3.4 2.8 2.4 2.0 1.7 1.5
In the absence of more accurate methods, φcc at any time (t) shall be taken as—
φcc = k2 k3 k4 k5 φcc.b . . . 3.1.8.3
where k2 is obtained from Figure 3.1.8.3 and k3 depends on the age of the concrete ( ) at the
time of loading (in days) and is given by the following:
k3 = 2.7/[1+log()] for 1 day
k4 = 0.7 for an arid environment, 0.65 for an interior environment, 0.60 for a
temperate inland environment and 0.50 for a tropical or near-coastal
environment
k5 = a modification factor for high strength concrete, which shall be taken as—
k5 = 1.0 when f c 50 MPa; or
1.8
th = 50 mm
1.6
α 2t 0.8
k2 = t h = 10 0 m m
t 0.8 + 0.15 t h
1.4
α 2 = 0.8 + 1.12e - 0 .0 0 5 t h
t h = 20 0 m m
1. 2
W h ere t i s in d ays
th = 400 mm
1.0
k2
0.8
0.6
0.4
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
0. 2
0
1 3 10 30 10 0 1 3 10 30
DAYS YE ARS
TIM E SIN CE CO M M EN CEM ENT OF DRYIN G, t
TABLE 3.1.8.3
FINAL DESIGN CREEP COEFFICIENTS ( cc* ) FOR CONCRETE FIRST LOADED
AT 28 DAYS
*
cc
The minimum values of uniform strain for Ductility Class LP reinforcement are not lower-
characteristic values, but are lower limits placed on every tensile test result. The uniform
strain in any test shall be not less than 0.025, and the tensile strength to yield stress ratio
shall be not less than 1.05.
NOTE: In AS/NZS 4671, ε su is referred to as Agt, expressed as a percentage, and fsy is referred to
as Re .
TABLE 3.2.1
YIELD STRENGTH AND DUCTILITY CLASS OF REINFORCEMENT
Reinforcement Characteristic Uniform
Ductility
yield strength (f sy ) strain
Type Designation grade class
MPa (ε su )
Bar plain to AS/NZS 4671 R250N 250 0.05 N
Bar plain deformed or indented to D500L 500 0.015 L
AS/NZS 4671 D500N 500 0.05 E
D500E 500 0.10
Bar deformed to Clause 3.2.1 D500LP 500 0.0253 LP
Welded mesh, plain, deformed or R500L, D500L, I500L 500 0.015 L
indented to AS/NZS 4671
R500N, D500N, 500 0.05 N
I500N
Welded mesh, plain, deformed or R500LP, D500LP, 500 0.0253 LP
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
TABLE 3.3.1
TENSILE STRENGTH OF COMMONLY USED WIRE STRAND AND BAR
Characteristic Characteristic
Nominal
Material type and Area minimum breaking minimum breaking
diameter
Standard load strength (f pb )
mm mm 2 kN MPa
As-drawn wire, 5.0 19.6 34.7 1700
AS/NZS 4672.1 7.0 38.5 64.3 1670
Stress-relieved wire, 5.0 19.9 33.8 1700
AS/NZS 4672.1 7.0 38.5 64.3 1670
7 wire ordinary strand, 9.5 55.0 102 1850
AS/NZS 4672.1 12.7 98.6 184 1870
15.2 140 250 1790
15.2 143 261 1830
7 wire compacted strand, 15.2 165 300 1820
AS/NZS 4672.1 18.0 223 380 1700
Hot-rolled bars, 26 562 579 1030
AS/NZS 4672.1 29 693 714 1030
(Super grade only) 32 840 865 1030
36 995 1025 1030
40 1232 1269 1030
56 2428 2501 1030
75 4371 4502 1030
COEFFICIENT k 7
A llll oy sste
te e l b
bar
ar
W ire an d str an d
0
0.4 0. 5 0.6 0.7 0.8
STRESS IN TEN D O N AS PRO PORTIO N O F f p b
NOTE: Revision of these values will be necessary in the estimation of total loss of prestress for
unusual conditions of exposure or where new processes or materials are introduced.
3.4.2 Immediate loss of prestress
3.4.2.1 General
The immediate loss of prestress shall be estimated by adding the calculated losses of
prestress due to elastic deformation of concrete, friction, anchoring and other immediate
losses as are applicable.
3.4.2.2 Loss of prestress due to curing conditions
Where curing of a prestressed member is carried out at ambient conditions, the design
relaxation shall be as determined by Clause 3.3.4.3.
Where curing of a prestressed member is carried out at elevated temperature (such as steam
curing), the design relaxation shall be determined from Clause 3.3.4.4 and shall be
considered as an immediate loss.
3.4.2.3 Loss of prestress due to elastic deformation of concrete
Calculation of the immediate loss of prestress due to elastic deformation of the concrete at
transfer shall be based on the value of modulus of elasticity of the concrete at that age. For
multi-stage prestressing, elastic deformation losses resulting from each stage of stressing
shall be determined.
3.4.2.4 Loss of prestress due to friction
The stress variation along the design profile of a tendon due to friction in the jack, the
anchorage and the duct shall be assessed in order to obtain an estimate of the prestressing
forces at the critical sections considered in the design.
The extension of the tendon shall be calculated allowing for the variation in tension along
its length, as follows:
(a) Friction in the jack and anchorage The loss of prestress due to friction in the jack
and anchorage shall be determined for the type of jack and anchorage system to be
used.
(b) Friction along the tendon Friction loss shall be calculated from an analysis of the
forces exerted by the tendon on the duct. In the absence of more detailed calculations,
the stress in the tendon at a distance (a) measured from the jacking end (σpa) shall be
taken as—
pa pje
p Lpa
tot
. . . 3.4.2.4
where
σpj = maximum stress in the tendon at the jacking end
e = base of Napierian logarithms
μ = friction curvature coefficient for different conditions
In the absence of specific data and when all tendons in contact in the
one duct are stressed simultaneously, μ shall be taken as—
(i) for greased-and-wrapped coating, 0.15;
(ii) for bright and zinc-coated metal sheathing, 0.15 to 0.20;
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
(iii) for bright and zinc-coated flat metal ducts, 0.20; and
(iv) for polyethylene ducts, 0.14.
αtot = sum in radians of the absolute values of successive angular deviations of
the prestressing tendon over a length of the tendon from the jacking end
to a point at distance (a) from that end (Lpa)
p = an estimate of the angular deviation due to wobble effects, in radians per
metre (rad/m)
As a first approximation, βp shall be taken as—
(i) for sheathing containing tendons other than bars and having an
internal diameter—
50 mm: 0.024 to 0.016 rad/m
>50 mm but 90 mm: 0.016 to 0.012 rad/m
>90 mm but 140 mm: 0.012 to 0.008 rad/m;
(ii) for flat metal ducts containing tendons other than bars, 0.024 rad/m
to 0.016 rad/m;
(iii) for sheathing containing bars and having an internal diameter of
50 mm or less, 0.016 rad/m to 0.008 rad/m; and
(iv) for bars of any diameter in a greased-and-wrapped coating,
0.008 rad/m.
Lpa = length of the tendon from the jacking end to a point at a distance (a)
from that end
The magnitude of the friction due to duct curvature and wobble used in the design shall be
verified during the stressing operation.
values of all relevant material properties shall be used in the form of the stress-strain curve
for the material.
4.1 GENERAL
The requirements of this Section apply to plain, steel fibre reinforced, and steel reinforced
and prestressed concrete structures and members with a design life of 100 years in
accordance with AS 5100.1.
For structures with design life of 50 (20%) years, the durability requirements of AS 3600
may be adopted.
NOTES:
1 More stringent requirements may be appropriate for structures with a design life in excess of
100 years (for example, monumental structures or high risk significant structures crossing
major waterways), while some relaxation of the requirements may be acceptable for structures
with a design or service life of less than 40 years (for example, temporary structures).
2 Durability is a complex topic and compliance with these requirements may not be sufficient
to ensure a durable structure.
3 Design life is defined in Clause 1.4.3.19 and is the period assumed in design for which a
structure or structural element is required to perform its intended purpose with minor
maintenance and without replacement or major structural repairs.
TABLE 4.3
EXPOSURE CLASSIFICATIONS
Exposure classification
reinforced or prestressed
Surface and exposure environment
concrete members
(see Notes 1 and 13)
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
1 Surface of members in contact with the ground (see Notes 2 and 3):
(a) Members protected by a damp-proof membrane in non-aggressive A
soils
(b) Members in non-aggressive soils (see Note 4) B1
(c) Members in aggressive soils:
(i) Sulfate bearing (magnesium content <1g/L) See Table 4.8
(ii) Sulfate bearing (magnesium content 1g/L) (see Notes 5and 6) U
(iii) Other U
(d) Salt-rich soils and soils in areas affected by salinity See Table 4.8
2 Surfaces of members in interior environments:
Fully enclosed within a structure except for a brief period of weather A
exposure during construction (see Note 14)
3 Surfaces of members in above-ground exterior environments in areas that
are:
(a) Inland (>50 km from coastline) environment being:
(i) Non-industrial and arid climatic zone (see Notes 7 and 8) A
(ii) Non-industrial and temperate climatic zone A
(iii) Non-industrial and tropical climatic zone B1
(iv) Industrial (see Note 8) and any climatic zone B1
(b) Near-coastal (1 km to 50 km from coastline), any climatic zone B1
(c) Coastal (see Note 9) and any climatic zone B2
4 Surfaces of members in water (see Note 3):
(a) In fresh water (chloride content <300 ppm) B1
(b) In brackish water (chloride content 300–6000 ppm) B2
(c) In soft or running water U
(continued)
aggressive, exposure classification A may be used, provided the soil is not subject to wetting and drying.
Typically, members in the top 500 mm of soil would not qualify for this reduction.
5 Permeable soils with a pH less than 4.5, or with groundwater containing more than 1 g per litre of sulfate-
bearing magnesium ions, should be considered highly aggressive.
6 Severity of sulfate attack depends on the type of sulfate. For example, magnesium sulfate is more
aggressive than sodium sulfate. The use of concrete containing supplementary cementitious materials may
be adequate for sodium sulfate conditions. For the magnesium sulfate conditions, specific consideration
should be given to concrete containing not only supplementary cementitious materials but also other
protective measures that are likely to resist this type of sulfate.
7 The climatic zones referred to are those given in Figure 4.3, which is based on the Bureau of Meteorology
map, Major seasonal rainfall zones of Australia, Commonwealth of Australia, 2005.
8 Industrial refers to areas that are within 3 km of industries that discharge atmospheric pollutants.
9 For the purpose of this Table, the coastal zone includes locations within 1 km of the shoreline of large
expanses of saltwater. Where there are strong prevailing winds or vigorous surf, the distance should be
increased beyond 1 km and higher levels of protection should be considered.
10 The spray zone is the zone from 1 m above wave crest level.
11 The tidal/splash zone is immediately below the spray zone and includes the zone 1 m below lowest
astronomical tide (LAT) and up to 1 m above highest astronomical tide (HAT) on vertical structures, and all
exposed soffits of horizontal structures over the sea.
12 Further guidance on measures appropriate in exposure classification U may be obtained from AS 3735 and
AS 3735 Supp l respectively which cover exposure classifications and aggressiveness of various liquids and
ground environments in contact with a concrete surface.
13 In this Table, classifications A, B1, B2, C1 and C2 represent increasing degrees of severity of exposure,
while classification U represents an exposure environment not specified in this Table but for which a
degree of severity of exposure should be appropriately assessed. Protective surface coatings may be taken
into account in the assessment of the exposure classification.
14 The interior of a box girder or voided member is typically determined to be a classification A, unless a
more detailed assessment is carried out identifying a different exposure classification. Where the exterior of
a box girder or voided member is exposed to a salt spray, the interior should be at least a classification B1.
This Note does not apply to the internal surfaces of the segmental box girders.
13 0 ° 14 0 °
C L AS S I FI CAT I O N 15 0 °
10 ° T h u r s d ay I s
T R O PI CA L 10 °
Yirrkala
Ashmore Is DA RW I N We i p a
T E M PER AT E
Tr o u g h t o n I s Katherine
ARID
Wyndham Cook town
Cairns Willis Is
D e r by
TROPICAL Normanton
Broome Halls Creek
To w n s v i l l e
Camooweal
Te n n a n t C r e e k
Pt Hedland Mt Isa
Hughenden 20°
20° M a c k ay
North West
Cape Wittenoom
Alice Springs Longreach
Rockhampton
Mundiwindi
Giles Bundaberg
ARID Birdsville Ta r o o m
C a r n a r vo n
C h a r l ev i l l e
Meekatharra Wiluna Oodnadatta
BRISBANE
L ave r t o n Marree
Moree
Geraldton Grafton
Fo r r e s t Cook Ta r c o o l a B o u r ke
Kalgoorlie
30°
Eu c l a Cobar Ta m w o r t h
30° Ceduna Po r t A u g u s t a
Dubbo
PER T H TEMPER ATE TEMPER ATE Newcastle
Wa g i n Mildura
Esperance SY D N E Y
ADEL AIDE
CA N B ER R A Wo l l o n g o n g
Cape Leeuwin
A l b a ny Horsham Ec h u c a
Kangaroo Is.
Cooma
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
MELBOURNE
Po r t l a n d Sale
CLIMATIC ZO NES
AUSTR ALIA Currie Burnie
40°
Launceston
40° Queenstown
Kilometres 200 0 200 400 600 800 Kilometres
PR O J EC T I O N A L B ER S C O N I CA L EQ UA L A R E A Hobar t
110 ° 12 0 ° 13 0 ° 14 0 ° 15 0 °
An alternative concrete mix for durability may be used if approved by the authority. The
concrete mix and associated testing shall demonstrate that the concrete can provide a level
of durability at least equal to that provided by this Standard for the concrete structure over
its required design life.
Where self-compacting concrete (SCC) as defined in Clause 1.4.3.57 is used, it shall also
comply with the required properties specified in Table 4.4.1(C) for slump flow, T500 time
and passing ability as determined by test method AS 1012.3.5.
TABLE 4.4.1(A)
MINIMUM STRENGTH AND CEMENT MATERIAL CONTENT,
MAXIMUM WATER/CEMENT (W/C) MATERIAL RATIO
AND CURING REQUIREMENTS FOR CONCRETE
Column 1 Column 2 Column 3 Column 4 Column 5 Column 6
Minimum
average
compressive
strength at the
Minimum Minimum
completion of
Maximum water/ initial curing
Exposure Minimum cement accelerated
cement material requirement
classification f c material curing and/or at
(W/C) ratio (see
content the time of
Clause 17.3.5.1)
stripping of
forms or
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
removal from
moulds
NOTE: For acidic and sulfate deterioration mechanisms in exposure classifications C1 and C2, a water
cementitous material (w/c) ratio of less than or equal to 0.4 and with a limit for the minimum cement material
content of 420 kg/m3 may be used.
TABLE 4.4.1(B)
COMPLIANT CEMENT MATERIAL PROPORTIONS (MINIMUM TO MAXIMUM
RANGE)
Proportioning of cement material
Exposure (% mass) in concrete mixes
classification Fly ash Amorphous silica
Slag Triple blends
(FA) (SF)
Up to 60 * /up to 40 ‡ , up to
A 100 * /0 to 70 * /30 † 100 * /0 to 60 * /40 ‡ 100 * /0 to 90 * /10 §
25 † , up to 10 §
Up to 60 * /up to 40 ‡ , up to
B1 100 * /0 to 70 * /30 † 100 * /0 to 60 * /40 ‡ 100 * /0 to 90 * /10 §
25 † , up to 10 §
70 * /30 ‡ to Up to 60 * /up to 40 ‡ , up to
B2 80 * /20 † to 70 * /30 † 92 * /8 § to 90 * /10 §
60 * /40 ‡ 25 † , up to 10 §
C1 75 * /25 † to 60 * /40 † 50 * /50 ‡ to 92 * /8 § to 90 * /10 § 25 * 30 * /60 ‡ 67 ‡ /8 § 10 §
30 * /70 ‡ 70 * 75 * /17† 20† /8 § 10 §
C2 75 * /25 † to 60 * /40 † 50 * /50 ‡ to 92 * /8 § to 90 * /10 § 25 * 30 * /60 ‡ 67 ‡ /8 § 10 §
30 * /70 ‡ 70 * 75 * /17† 20† /8 § 10 §
* % of GP (general purpose Portland cement to AS 3972)
† % of FA
‡ % of slag
§ % of SF
NOTES:
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
TABLE 4.4.1(C)
REQUIRED PROPERTIES OF SELF COMPACTING CONCRETE (SCC)
Properties of SCC Measurement Observations
Slump flow 550–750 mm spread The aggregate shall be evenly distributed
throughout the concrete paste within the spread
and shall not exhibit signs of segregation
T 500 time Achieve a spread of 500 mm The final spread shall not exceed 750 mm in
(measure of viscosity) within 2 to 5 seconds diameter
Passing ability 10 mm The concrete shall not exhibit signs of
segregation
4.4.2 Curing
4.4.2.1 General
Concrete shall be cured, using one or a combination of the methods set out in
Clauses 4.4.2.2 to 4.4.2.6 and as stated in Table 4.4.
The concrete shall be protected from moisture loss until the commencement of the curing.
Curing shall not be interrupted for more than half an hour when a combination of curing
methods is used.
For accelerated curing methods, the concrete strength for checking the adequacy of curing
shall be determined by test specimens cured with and in the same manner as the concrete
member.
4.4.2.2 Moist curing
Concrete shall be kept continuously moist and the concrete maintained at a temperature
above 5°C.
4.4.2.3 Membrane curing
Where curing compounds are permitted by the authority, they shall be correctly applied to
all exposed concrete surfaces. The concrete shall be maintained at a temperature above 5°C.
Curing compounds shall not be used on concrete surfaces of structures in seawater or
brackish water.
4.4.2.4 Polyethylene sheet
Polyethylene sheet may be used, provided its application ensures effective sealing.
4.4.2.5 Retaining formwork in place
Where formwork is left in place to satisfy formwork removal times, either as stated in the
relevant Standard or as required by the authority, or where formwork is left in place for
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
curing purposes, any exposed surfaces of the concrete shall be cured by other means in
accordance with the Clause 4.4.2.1.
Where formwork is removed prior to the completion of the curing period, curing shall
recommence within half an hour of formwork stripping and continue until the total curing
time is achieved or the required minimum average compressive strength is achieved.
4.4.2.6 Accelerated curing
Accelerated curing shall be carried out by low-pressure steam curing in accordance with
AS 1597.2.
NOTE: Other methods, such as radiant heat accelerated curing, may be used if approved by the
authority.
4.6 ABRASION
In addition to the other durability requirements of this Section, concrete for members
subject to abrasion from traffic shall have a characteristic compressive strength not less
than the applicable value given in Table 4.6.
TABLE 4.6
STRENGTH REQUIREMENTS FOR ABRASION
Minimum
characteristic
Member type and/or traffic condition compressive strength
( f c )
MPa
Footpaths and cyclist paths 25
Combined pedestrian pavements and cyclist paths, subject to 32
occasional pneumatic tyre traffic
Pavement and bridge decks subject to the following:
(a) Pneumatic tyre traffic 40
(b) Non-pneumatic tyre traffic (excluding studded tyres) 50
(c) Studded tyres To be assessed
but not less than 50
NOTE: f c refers to the characteristic compressive strength of the required member subject
to abrasion.
includes exposure to cycles of freezing and thawing, concrete in the member shall—
(a) have an f c not less than—
(i) 40 MPa for occasional exposure (<25 cycles per annum); or
(ii) 50 MPa for frequent exposure (25 cycles per annum); and
(b) contain a percentage of entrained air within the range—
(i) for 10 mm to 20 mm nominal size aggregate .................................. 4% to 8%; or
(ii) for 40 mm nominal size aggregate ..................................................... 3% to 6%,
where the percentage of entrained air is determined in accordance with AS 1012.4.
TABLE 4.8
EXPOSURE CLASSIFICATION FOR CONCRETE IN SULFATE, ACIDIC
AND SALINE SOILS
Exposure conditions * Exposure classification
Sulfates (expressed as SO 4 ) † Chlorides in Soil
Soil conditions
In soil ** In groundwater pH groundwater conditions
A‡
B§
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
6 pH alone may be a misleading measure of aggressivity without a full analysis of causes (for example,
still vs running water).
7 Contamination by the tipping of mineral and domestic wastes or by spillage from mining, processing or
manufacturing industries presents special durability risks due to the presence of certain aggressive
acids, salts and solvents, which can either chemically attack concrete or lead to a corrosion risk.
Certain ground conditions cannot be properly addressed by reference only to Table 4.8. These
conditions include, for example, areas where acid-sulfate soils exist, contamination by industrial and
domestic waste, or spillage from mining, processing or manufacturing industries. This presents special
durability risks due to the presence of certain aggressive acids, alkalis, salts and solvents that can lead
to either chemical attack of concrete or lead to a corrosion risk. In the absence of site-specific chemical
information, the exposure condition should be assessed as ‘exposure classification C1’ for domestic
refuse and ‘exposure classification C2’ for industrial/mining waste tips. Chemical analysis of the latter
may allow a lower risk classification.
8 For piles and other concrete elements in disturbed soil where accelerated corrosion may occur, the
exposure classification shall be for soil conditions A in the above Table.
9 Attention is drawn to regions of dry land salinity where the chloride concentrations in the soil can be
greater than seawater (for example, Murray River basin). This can affect the upper few metres of a
concrete element where the aggressive salts accumulate.
10 Cathodic protection should not fall below the levels recommended in AS 2832.5.
11 Testing for pH shall be in accordance with AS 1289.4.3.1. Testing for sulfate shall be in accordance
with BS 1377.
implemented to retard the ingress of chlorides into the concrete in its early maturing and
strength-developing period:
(a) Protection against ingress of chlorides All reinforcement and embedded metallic
fixtures shall be protected against chloride contamination prior to and during concrete
placement.
(b) Curing Further to the requirements of this Section, the period of continuous curing
for all cast-in-place concrete shall be not less than 14 days.
Curing compounds shall not be used on structures within tidal and splash zones of a
marine environment.
(c) Electrical continuity of the steel reinforcement Steel reinforcement shall be made
electrically continuous in concrete members, including piles, below 1 m above the
highest astronomical tide to allow for future application of a cathodic protection
system.
(d) Application of protective coatings Where required by the authority, a protective
coating against chloride ingress shall be applied to exposed concrete surfaces
subjected to an exposure classification C2 environment.
NOTE: Concrete surfaces exposed to an exposure classification C1 environment may also
require additional protection.
(e) Reinforcement Steel reinforcement shall be supported by premium grade extruded
fibre concrete supports and spacers manufactured under factory-controlled conditions
and of material compatible with the surrounding concrete.
NOTE: Other measures that may be considered to enhance concrete durability include the use
of controlled permeability formwork, use of stainless steel reinforcement in high exposure
locations, the addition of corrosion-inhibiting admixtures in the concrete and the installation
and maintenance of a cathodic protection system.
TABLE 4.10
SUPPLEMENTARY CEMENTITIOUS MATERIAL LIMITS IN THE CONCRETE
MIX TO MITIGATE ALKALI AGGREGATE REACTIVITY (AAR)
Proportion of supplementary cementitious material
Supplementary cementitious material
%
Fly ash 20 to 30
Slag 50 to 70
Amorphous silica 8 to 10
NOTE: The table is by percent of total combined weight (Portland cement portion not shown).
NOTE: Thermocouples should be located within the concrete member being constructed to
monitor the maximum temperature and differential temperature across the concrete. Typical large
and restrained members include crossheads, diaphragms, columns, abutments, footings and pile
caps.
TABLE 4.13.1
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
The minimum cover at the ends of post-tensioned tendons or anchorage devices shall be
50 mm.
NOTES:
1 Where anchorage recesses are to be filled with materials other than concrete, appropriate dual
shrinkage compensating cement materials should be used as they provide the same
compatibility as concrete.
2 Due to the significant differences between the physical properties of epoxy resin and epoxy
materials and concrete, they do not act monolithically under physically or chemically applied
loadings, and may result in the failure of the seal. In particular, differences in the coefficient
of thermal expansion may result in excessive stresses at the bond interface. This could
eventually result in failure at the interface or within the concrete substrate (lower strength),
unless a balance is achieved between the sizes of the cross-sectional area of the repair and the
bond area required at the interface, to sustain the stresses generated.
In the determination of an appropriate cover, consideration shall be given to—
(i) the size and shape of the member;
(ii) the size, type and configuration of the reinforcement and, if present, the tendons or
ducts; and
(iii) the aggregate size, the workability of the concrete and the direction of concrete
placement.
4.14.3 Cover for corrosion protection
4.14.3.1 General
For corrosion protection, the cover shall be not less than the appropriate value given in
Clauses 4.14.3.2 to 4.14.3.7.
4.14.3.2 Standard formwork and compaction
Where concrete is cast in formwork complying with AS 3610.1 and transported, placed and
compacted so as to—
(a) limit segregation or loss of materials;
TABLE 4.14.3.2
REQUIRED COVER WHERE STANDARD FORMWORK
AND COMPACTION ARE USED
C2 — 80
NOTES:
1 Cover requirements are based on effective, continuous and uninterrupted curing
in accordance with Clause 4.4.2.1. Where curing compounds are used, the cover
shall be increased by 5 mm for classifications A and B1, and 10 mm for other
classifications.
2 In construction, the specified position of reinforcements and tendons shall not
deviate from the required cover by more than the fixing tolerances specified in
Clause 17.7.3.
TABLE 4.14.3.3
REQUIRED COVER WHERE INTENSE COMPACTION
IS USED IN RIGID STEEL FORMWORK
Where concrete members are cast with self-compacting concrete in accordance with the
requirements of Clause 4.4.1 and Table 4.4.1(C), the cover shall be not less than the value
given in Table 4.14.3.2. Cover to screeded surfaces of members shall be in accordance with
Table 4.14.3.2.
4.14.3.5 Cast on or against ground
Where concrete is cast on or against ground and compacted in accordance with
Clause 4.14.3.2 or where self-compacting concrete is used without formwork, the cover to a
surface in contact with the ground shall be as given in Table 4.14.3.2 but increased by—
(a) 10 mm if the concrete surface is protected by a damp-proof membrane; or
(b) 30 mm otherwise.
4.14.3.6 Structural members manufactured by spinning or rolling
Where structural members are manufactured by spinning or rolling concrete, having a total
water cementitious material (w/c) ratio of less than 0.35, and provided that negative
tolerance is not allowed on the fixing of reinforcement, the cover for corrosion protection
shall be not less than the values given in Table 4.14.3.6 for the appropriate exposure
classification.
TABLE 4.14.3.6
REQUIRED COVER FOR SPUN OR ROLLED MEMBERS
Concrete characteristic Cover
Exposure classification compressive strength ( f c )
MPa mm
A, B1 32 30
40 35
B2
50 30
C1 50 40
C2 50 45
5.1 GENERAL
The relevant authority shall determine whether a bridge is required to be designed for fire
resistance, and nominate the type of fire loading to be applied and fire resistance rating as
applicable.
(d) Design each member taking into account the section reduction due to spalling and the
representative materials strength and stiffness under the imposed temperature
conditions.
TABLE 5.4.1.1
COMPRESSIVE STRENGTH FACTOR
Temperature of concrete, °C 0 100 200 900 1200
k θ1 1.0 1.0 0.95 0.09 0
NOTE: Linear interpolation between values is permissible.
TABLE 5.4.1.2
COEFFICIENT OF THERMAL EXPANSION
Temperature of concrete, °C 0 to 200 200 to 700 700 to 1200
Coefficient of thermal expansion (10 -6 ), /°C 10 24 0
NOTE: Coefficient has a range of 20%.
TABLE 5.4.1.4
THERMAL CONDUCTIVITY
Temperature of concrete (°C) 0 400 700 1000 1200
Thermal conductivity, W/m K 2.0 1.2 0.8 0.6 0.6
NOTE: Linear interpolation between values is permissible.
TABLE 5.4.2.1(A)
TENSION REINFORCEMENT WITH STRAIN 2%
Temperature of reinforcement, °C 0 400 800 1200
k θ2 1.0 1.0 0.1 0.0
NOTE: Linear interpolation between values is permissible.
TABLE 5.4.2.1(B)
TENSION REINFORCEMENT WITH STRAIN 2%
OR COMPRESSION REINFORCEMENT
Temperature of reinforcement, °C 0 100 500 700 1200
k θ2 1.0 1.0 0.6 0.1 0.0
NOTE: Linear interpolation between values is permissible.
TABLE 5.4.2.2
MODULUS OF ELASTICITY FACTOR
Temperature of reinforcement, °C 0 100 500 700 1200
k θ3 1.0 1.0 0.6 0.13 0.0
NOTE: Linear interpolation between values is permissible.
TABLE 5.4.3.1
MINIMUM TENSILE STRENGTH FACTOR
Temperature of tendon, °C 0 100 700 1000
k θ4 1.0 1.0 0.05 0.0
NOTE: Linear interpolation between values is permissible.
TABLE 5.4.3.2
MODULUS OF ELASTICITY FACTOR
Temperature of tendon, °C 0 100 400 700 1000
k θ5 1.0 1.0 0.8 0.1 0.0
NOTE: Linear interpolation between values is permissible.
6.1 GENERAL
6.1.1 Basis for structural analysis
Analysis of concrete structures shall take into account the following:
(a) The strength and deformational properties of the member materials.
(b) The equilibrium requirements for all forces acting on and within the structure.
(c) The requirements of compatibility of deformations within the structure.
(d) The support conditions and, where appropriate, interaction of the structure with the
foundation and other connecting or adjacent structures.
6.1.2 Interpretation of the results of analysis
Irrespective of the method chosen for structural analysis, the simplifications, idealizations
and assumptions implied in the analysis shall be considered in relation to the real, three-
dimensional nature of the structure when the results of the analysis are interpreted.
NOTE: Users of software packages for analysis should ensure the package is appropriate for the
analysis being undertaken.
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
The effect of haunching and other variations of cross-section along the axis of a member
shall be considered and, where significant, taken into account in the determination of the
member stiffness.
Any assumptions regarding the relative stiffness of members shall be applied consistently
throughout the analysis. Particular account shall be taken of the effect of cracking on
torsional stiffness, which, in the absence of additional information, shall be not greater than
20% of the uncracked torsional stiffness at the strength ULS when checking for flexure of
slabs and beams.
NOTES:
1 For strength design of a regular rectangular framed structure, the cross-sectional stiffness of
the flexural members and columns may be taken as 0.4Ec If and 0.8EcI c respectively.
2 When modelling single cell box girders, account should be taken of the effect of torsion on
the distribution of shear between the webs (for example, adding the torsion divided by the
distance between the webs to the shear in one web).
6.2.4 Deflections
Deflection calculations shall take into account the effects of cracking, tension stiffening,
shrinkage, creep, thermal effects, relaxation of tendons, elastic shortening and settlement of
supports. Calculations in accordance with the requirements of Clauses 8.5 and 9.3 shall be
deemed to satisfy this requirement for beams and slabs respectively. Consideration shall be
given to any deformations that may result from construction staging and any deflection or
settlement of supporting temporary works.
6.2.5 Secondary bending moments and shears resulting from prestress
The secondary bending moments and shears and the associated deformations that are
produced in an indeterminate structure by prestressing shall be taken into account in the
design calculations for fatigue and serviceability.
The secondary bending moments and shears due to the effects of prestress may be
determined by elastic analysis of the unloaded uncracked structure.
(a) All of the main reinforcement in the member shall be Ductility Class N, which
includes stainless steel specified in Clause 3.2.1.
(b) The bending moment distribution before redistribution shall be determined in
accordance with elastic analysis.
(c) Where the neutral axis parameter, ku, is less than or equal to 0.2 in all peak moment
regions, the redistribution of the moment at a support shall not exceed 30%.
(d) Where ku exceeds 0.2 in one or more peak moment regions, but does not exceed 0.4,
the redistribution shall not exceed 75 (0.4 ku)%.
(e) The positive bending moment shall be adjusted to maintain equilibrium.
(f) Where ku exceeds 0.4 in any peak moment region, no redistribution shall be made.
(g) Static equilibrium of the structure after redistribution of the moments shall be used to
evaluate all action effects for strength design.
(h) At column supports, the out of balance moment ( M v* ) shall not be varied during
moment redistribution.
NOTES:
1 The values of ku are calculated for cross-sections that have been designed on the basis of the
redistributed moment diagram.
2 The amount of redistribution is measured as a percentage of the bending moment before
redistribution.
3 Extra checks should be made on ductility and the possibility of punching shear failures.
BENDING MOMENTS
6.3.1 General
This Clause (6.3) applies to the elastic analysis of frames not restrained by bracing or shear
walls, or both, for which the relative displacement at the ends of compressive members is
less than Lu/250 under the design load for strength.
6.3.2 Analysis
An elastic analysis incorporating secondary bending moments shall comply with the
requirements of Clause 6.2 and the following:
(a) The effect of lateral joint displacements shall be taken into account.
(b) For very slender members, the change in bending stiffness of a member due to axial
compression shall be considered.
also be designed to satisfy the fatigue and serviceability requirements of the structure.
6.7.2 Methods for beams and frames
Plastic methods of analysis may be used for the strength design of continuous beams and
frames, provided it is shown that the high-moment regions possess sufficient moment-
rotation capacity to achieve the plastic redistribution implied in the analysis.
6.7.3 Methods for slabs
6.7.3.1 Lower-bound method for slabs
The design bending moments obtained using lower-bound theory shall satisfy the
requirements of equilibrium and the boundary conditions applicable to the slab.
6.7.3.2 Yield line method for slabs
A yield line analysis for strength design of a slab shall satisfy the following requirements:
(a) The design bending moments shall be obtained from calculations based on the need
for a mechanism to form over the whole or part of the slab at collapse.
(b) The mechanism that gives rise to the most severe design bending moments shall be
used for the design of the slab.
7.1 GENERAL
It shall be permissible to use strut-and-tie models to represent the conditions at overload
and at failure in non-flexural members and in non-flexural regions of members, as a basis
both for strength design and for evaluating strength.
A strut-and-tie model shall consist of compression elements (struts) and tension elements
(ties) that are connected together at nodes to form a load-resisting structural system.
Strut-and-tie models shall satisfy the following requirements:
(a) Loads shall be applied at nodes, and the struts and ties shall be subjected only to axial
force.
(b) The model shall provide load paths to carry the loads and other actions to the supports
or into adjacent regions.
(c) The model shall be in equilibrium with the applied loads and the reactions.
(d) In determining the geometry of the model, the dimensions of the struts, ties, and
nodal zones shall be taken into account.
(e) Ties shall be permitted to cross struts.
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
B ur st i n g for c e s
(c) B ot t l e - s ha p e d c o m pre s s i o n fi e l d
A x i s of str ut
A x i s of t i e
θ
T
. . . 7.2.3
where
Ac = smallest cross-sectional area of the concrete strut at any point along its length
and measured normal to the line of action of the strut
s = strut efficiency factor given in Clause 7.2.2
The value of the strength reduction factor (st) shall be obtained from Table 2.3.4.
Longitudinal reinforcement may be used to increase the strength of a strut. Such
reinforcement shall be placed parallel to the axis of the strut, located within the strut and
enclosed in ties or spirals satisfying Clause 10.7. The longitudinal reinforcement shall be
properly anchored. The strength of a longitudinally reinforced strut may be calculated as for
a prismatic, pin-ended short column of similar geometry.
7.2.4 Bursting reinforcement in bottle-shaped struts
The design bursting force at both the SLS Tb.s*
and ULS Tb* shall be calculated using an
equilibrium model consistent with the bottle shape shown in Figure 7.2.4(A). The
divergence angle () for the bottle-shaped strut shall be assessed for each situation but shall
be not less than—
(a) tan = 0.5 ................................................................................ for serviceability; and
(b) tan = 0.2 ............................................................................................... for strength.
The bursting force across the strut at cracking shall be taken as—
Tb.cr 0.7bl b f ct . . . 7.2.4(1)
where
b = width of rectangular cross-section or member
lb = length of the bursting zone [see Figure 7.2.4(A)]
If the calculated bursting force Tb* is greater than 0.5Tb.cr with tan taken as 0.5,
transverse reinforcement shall be provided in either—
(i) two orthogonal directions at angles 1 and 2 to the axis of the strut
[see Figure 7.2.4(B)]; or
(ii) one direction at an angle 1 to the axis of the strut, where 1 shall be not less than 40°
and shall satisfy—
where
Asi = area of reinforcement in directions 1 and 2 crossing a strut at an angle
1 to the axis of the strut [see Figure 7.2.4(B)]
fsi = serviceability limit stress in the reinforcement as specified in
Clause 12.7
The transverse reinforcement shall be evenly distributed throughout the length of the
bursting zone (lb), which shall be calculated from the following equation:
lb z 2 a 2 d c . . . 7.2.4(4)
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
where
a = shear span [see Figure 7.2.4(A)]
dc = width of the idealized strut [see Figure 7.2.4(A)]
z = projection of the inclined compressive strut normal to the shear span, [see
Figure 7.2.4(A)]
a
Id ealize d parallel - s i d e d
str ut
CCC N o d e
Tb
/2
/2
C dc
D z
/2
Tb
α C
/2
θ
CCT N o d e B ot t l e - s ha p e d str ut
L
) a
dc
+
(I b w w
2 5
0.
Ω Ω
d
c /2
d c /4
Tb
/2
/2
C d c /4
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
D z
/2
Tb
α C
/2
Ib
Ω
w dc = w2 + Ω 2
d c /4
d c /4
A S1
A x i s of
str ut
γ1
γ2 S tr u t
A S2
7.3 TIES
7.3.1 Arrangement of ties
Ties shall consist of reinforcing steel and/or prestressing tendons. The reinforcement and/or
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
tendons shall be evenly distributed across the nodal regions at each end of the tie, and
arranged such that the resultant tensile force coincides with the axis of the tie in the strut-
and-tie model.
7.3.2 Design strength of ties
The design strength of a tie shall be taken as st [Astfsy + Ap(p.ef + p)] where ( p.ef + p)
shall not exceed fpy. The value of st shall be obtained from Table 2.3.4.
7.3.3 Anchorage of ties
To provide adequate anchorage at each end of the tie, the reinforcement or tendon shall be
extended beyond the node to achieve the design strength of the tie at the node and anchored
in accordance with Clause 13.1. At least 50% of the development length (Lst) shall extend
beyond the nodal zone.
NOTE: Alternatively, anchorage of reinforcement may be achieved by a welded or mechanical
anchorage, located entirely beyond the nodal zone.
7.3.4 Design stress of reinforcement
The maximum stress in tie reinforcement at SLS shall be not greater than fscr given in
Table 8.6.1(A) for the largest nominal diameter (d b) of the bars in the tie.
7.4 NODES
7.4.1 Types of nodes
Three types of node are distinguished by the arrangement of the entering struts and ties, and
the confinement thus provided, as follows:
(a) CCC—there are only struts entering the node.
(b) CCT—there are two or more struts and a single tension tie entering the node.
(c) CTT—there are two or more tension ties entering the node.
When strut-and-tie modelling is used for strength design, the requirements of Clause 2.3.4
shall be satisfied.
7.6.2 Serviceability checks
When design for strength is based on strut-and-tie modelling, separate checks shall be
undertaken to ensure that the design requirements for serviceability are satisfied.
7.6.3 Specific non-flexural members
In addition to the requirements of Section 7, the design of specific non-flexural members
such as deep beams, end zones, nibs, and corbels shall also comply with the requirements of
Section 12.
Sections with kuo greater than 0.36 and M* > 0.6Muo shall be used only when—
(a) the structural analysis is carried out in accordance with Clauses 6.2 to 6.6; and
(b) compressive reinforcement of at least 0.01 times the area of concrete in compression
is used and restrained by fitments as specified in Clause 10.7.4.
8.1.6 Minimum strength requirements
8.1.6.1 General
The ultimate strength in bending (Muo), without axial force, at critical cross-sections shall
be not less than (Muo)min, the minimum required strength in bending at a critical cross-
section, and calculated using the following equation:
M uo min 1.2 [ Z f ct.f
Pe / Ag Pe e] . . . 8.1.6.1(1)
where
Z = section modulus of the uncracked cross-section, referred to the extreme fibre
at which flexural cracking occurs
= characteristic flexural tensile strength of concrete at 28 days
f ct.f
Pe = total effective prestress force allowing for all losses of prestress
e = eccentricity of the prestressing force (Pe), measured from the centroidal axis
of the uncracked section
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
where
For rectangular sections:
b = 0.20
For T-sections and L-sections with the web in tension:
1/ 4
b D b
b 0.20 ef 1 0.4 s 0.18 0.20 ef
bw D bw
For T-sections and L-sections with the flange in tension:
2/3
b D b
b 0.20 ef 1 0.25 s 0.08 0.20 ef
bw D bw
8.1.6.2 Prestressed beams at transfer
The strength of a prestressed beam at transfer shall be checked using the load combinations
specified in AS 5100.2 and a capacity reduction factor () for the section of 0.6.
This requirement shall be deemed to be satisfied if the maximum compressive stress in the
concrete, under the loads at transfer, does not exceed 0.5fcp for a rectangular distribution of
stress or 0.6fcp for a triangular distribution of stress, and flexural cracking is controlled in
accordance with Clause 8.6.2.
if f py f pb 0.9 ,
k1 = 0.28;
k2
1
bef d p f c
Apt f pb Ast Asc f sy . . . 8.1.7(2)
Compressive reinforcement may be taken into account only if dsc, the distance from the
extreme compressive fibre of the concrete to the centroid of compressive reinforcement, is
not greater than 0.15dp, in which case k2 shall be taken as not less than 0.17.
8.1.8 Stress in tendons not yet bonded
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
Where the tendon is not bonded, the stress in the tendon at the strength ULS (pu) shall be
determined from the following equation, but in no case shall pu be greater than fpy:
d p ku d
pu p.cf 6200 . . . 8.1.8(1)
L
pc
where
p.cf = effective stress in the tendon (after losses)
kud = neutral axis depth
Ap f py Ast Asc f sy 0.85 b bw d f f c
= for a T-section . . . 8.1.8(2)
0.85 bw f c
k2 d p
= for a rectangular section . . . 8.1.8(3)
0.85
df = thickness of the compression flange
k2 = as given in Equation 8.1.7(2)
Lpa
Lpe = . . . 8.1.8(4)
1 s
n
2
Lpa = length of the tendons
ns = number of support hinges crossed by the tendon (draped tendons only)
To ensure that as a result of curvature a tendon cannot break through into an ungrouted
duct, the spacing shall be such that—
0.73
sd . . . 8.1.9.3
r
where
sd = centre-to-centre distance between lines of ducts in the plane of the curvature
Pi = prestressing force after initial losses
r = radius of curvature of the duct
At all other locations where tendons curve or deviate, the adequacy of the concrete to carry
the lateral force shall be assessed and, where necessary, the lateral load shall be carried by
reinforcement designed in accordance with Section 12.
8.1.9.4 Out-of-plane forces
Curved tendons with multiple strands or wires also induce out-of-plane forces perpendicular
to the plane of the tendon curvature. The distributed splitting force along the line of the
tendon may be estimated as 0.16P/r in addition to any bursting forces calculated in
accordance with Clause 7.2.4.
The out-of-plane splitting force shall be deemed to be resisted over a distance dsp from the
duct, that is, towards the centre of curvature, equal to the lesser of—
(a) twice the distance between the centre-line of the duct and the closest outer layer of
non-prestressed reinforcement parallel to the plane of curvature of the duct; and
(b) the clear distance between two ducts in the same or similar planes of curvature.
The splitting force may be resisted by the concrete in tension or by reinforcement designed
in accordance with Section 12. The concrete tensile capacity may be taken as f ct , where ϕ
is equal to 0.6. Transverse reinforcement, if required, shall be spaced at no greater than the
lesser of 300 mm and dsp.
NOTE: For guidance, see EN 1992-2.
and
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
where
s = centre-to-centre spacing of shear reinforcement, measured parallel to the
longitudinal axis of the member
cot v cot v
= kc 0.85 f cp bv d v Pv , at transfer . . . 8.2.3.3(2)
1 cot v
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
2
where
Vu.max= ultimate shear strength limited by web crushing failure
1
3
kc = 0.55 30 0.55 ; or . . . 8.2.3.3(3)
f c
1
30 3
0.55 0.55 at transfer . . . 8.2.3.3(4)
0.85 f
cp
dv = effective shear depth (see Clause 8.2.1.8)
and
v = angle between the axis of the concrete compression strut and the longitudinal
axis of the member (see Clause 8.2.4.2)
αv = angle between the inclined shear reinforcement and the longitudinal tensile
reinforcement
8.2.4 Ultimate shear strength of a beam excluding transverse shear reinforcement
(Vuc)
8.2.4.1 General
The shear strength may be determined by any of the following, provided all requirements
for use of the chosen model are satisfied:
(a) Vuc k v f cbv d v
0 .4 1300
kv . . . 8.2.4.2(1)
1 1500 x 1000 k dg d v
where
32
k dg but not less than 0.80
16 d g . . . 8.2.4.2(2)
M * d v V * Pv 0.5 N * Apt f po
x . . . 8.2.4.3(1)
2 Es Ast Ep Apt
M * d v V * Pv 0.5 N * Apt f po
x . . . 8.2.4.3(2)
2 Es Ast Ep Apt Ec Act
(c) Ast and Apt are the areas of reinforcing bars and prestressing tendons in the half-depth
of the section containing the flexural tension zone.
NOTES:
1 fpo may be taken as 0.7fpu for bonded tendons outside the transfer length and fpe for
unbonded tendons.
2 In calculating Ast, the area of bars that terminate less than their development length from
the section under consideration shall be reduced in proportion to their lack of full
development.
NOTE: For sections closer than d o to the face of the support, the value of ε x calculated at d o from
the face of the support may be used in evaluating and kv.
If the axial tension is large enough to crack the flexural compression face of the section, the
resulting increase in εx shall be taken into account. In lieu of more accurate calculations, εx
calculated from the equation shall be doubled.
v and kv may be determined from Clause 8.2.4.2 using a value of εx that is greater than that
calculated from the equation in this Clause. εx shall be not greater than 3.0 10-3.
8.2.4.4 Determination of εx for combined shear and torsion
In lieu of more accurate calculations, the longitudinal strain (εx) in the concrete at the mid-
depth of the section subjected to shear and torsion shall be calculated as follows:
2
0.9T *uh
M d v V Pv
2
0.5 N Apt f po
* * *
2 Ao . . . 8.2.4.4(1)
x
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
2 Es Ast Ep Apt
2 A o . . . 8.2.4.4(2)
x
2 Es Ast Ep Apt Ec Act
NOTES:
1 fpo may be taken as 0.7fpu for bonded tendons outside the transfer length and fpe for
unbonded tendons.
2 In calculating Ast, the area of bars that terminate less than their development length from
the section under consideration may be reduced in proportion to their lack of full
development.
If the value of εx is negative, it shall be taken as zero or εx shall be recalculated with the
denominator replaced by 2(EsAst + EpApt + EeAct), where Act = area of concrete on flexural
tension side of member.
NOTE: For sections closer than d o to the face of the support, the value of ε x calculated at d o from
the face of the support may be used in evaluating v and β.
If the axial tension is large enough to crack the flexural compression face of the section, the
resulting increase in εx shall be taken into account. In lieu of more accurate calculations, εx
calculated from the equation shall be doubled.
v and β may be determined from Clause 8.2.4.2 using a value of εx that is greater than that
calculated from the equation in this Clause. However, εx shall be not greater than
+3.0 103.
8.2.4.5 Web crushing due to combined shear and torsion
The wall thickness (tw) to avoid crushing from combined shear and torsion shall be
calculated as follows:
(a) For box sections:
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
where
Ic = second moment of area of concrete section
y = distance from the centroidal axis to the section under consideration
Sc(y) = first moment area above y and about the centroidal axis
bv(y) = width of the cross-section at a y from the centroidal axis
σcp(y)= concrete compressive stress at y from centroidal axis due to prestressing, and
1 Yc y . . . 8.2.4.7(2)
cp y Fp l x
Ac Ic
where
Yc = height of concrete centroidal axis
1
Ac y S c y Yc Ypt dPt l x . . . 8.2.4.7(3)
cp(y) =
bv y Ac
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
Ic dx
αl = lx/(1.2Lpt)
where
lx = distance from end of beam to location shown on Figure 8.2.4.7
Lpt = transmission length
Ypt = height of centroidal axis of prestressing steel
Po int of failure
4 5°
ℓx
2 Ao
or
(b) Shear without torsion:
Ftd = 0.5N* + (V* 0.5Vus Pv)cot(v) . . . 8.2.7(2)
* *
where V is the absolute value of shear force and N is positive for axial tension and
negative for axial compression.
Additional reinforcement and tendons shall be fully anchored and proportioned such that
the following is satisfied:
Asfsy + Apfpy Ftd/ϕ . . . 8.2.7(3)
where
ϕ = 0.7 [see Table 2.3.2(c)]
NOTE: For reinforcement and tendons that are not fully anchored, see Clauses 13.1.2.3 and 13.3.
8.2.8 Proportioning longitudinal reinforcement on the flexural compression side
Additional longitudinal reinforcement on the flexural compression side of the beam section
shall be proportioned such that the additional force is greater than or equal to the force
Fcd, calculated as follows:
(a) Shear with torsion:
2
0.45T *u h
Fcd 0.5 N *
V *
0.5Vus Pv
2
cot v . . . 8.2.8(1)
2 Ao
or
(b) Shear without torsion:
Fcd = 0.5N* + (V* 0.5Vus Pv)cot(v) . . . 8.2.8(2)
where V* is the absolute value of shear force and N* is positive for axial tension and
negative for axial compression.
Additional reinforcement shall be fully anchored and proportioned such that the following
is satisfied:
Asfsy Fcd/ϕ
where
ϕ = 0.7 [see Table 2.3.2(c)]
NOTE: Where the reinforcement is not fully anchored, see also Clause 13.1.2.3.
8.2.9 Extension of longitudinal reinforcement and tendons
8.2.9.1 General
At every section, the longitudinal reinforcement and tendons shall be designed to resist the
flexural design tension force determined in Clause 8.1.5, and additional tensile forces
caused by shear and torsion as specified in Clause 8.2.7, Clause 8.2.8 and Figure 8.2.9.1.
For members not subjected to significant direct tension or torsion, these requirements may
be satisfied by extending the flexural tension reinforcement and tendons to develop the
flexural tensile force beyond the location required by flexure alone as follows:
(a) Where transverse reinforcement is not required, a distance D.
(b) Where transverse reinforcement is required, a distance docot(v).
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
LEGEN D:
A
A = Enve l o p e of M */z + N */2
B = Ac t i n g te n s i l e for c e Δ F t d
C = R e s i s t i n g te n s i l e for c e ØT u
B Δ F td
C
d 0 c ot(θ v )
d 0 c ot(θ v ) A
Δ F td
C B
(c) Stirrups are provided to give an area of shear reinforcement of Asv + Asv.min for a
distance equal to the overall depth of the cross-section (D) along the terminated bar
beyond the cut-off point, where Asv.min and Asv are determined in accordance with
Clause 8.2.1.7 and Clause 8.2.5.2 respectively.
8.3.2.3 Extent
The shear reinforcement required at the critical cross-section shall be carried to the face of
the support.
Shear reinforcement of area not less than that calculated as being necessary at any cross-
section shall be provided for a distance (D) from that cross-section in the direction of
decreasing shear. The first fitment at each end of a span shall be positioned not more than
50 mm from the face of the adjacent support.
Shear reinforcement shall extend as close to the compression face and the tension face of
the member as cover requirements and the proximity of other reinforcement and tendons
will permit.
8.3.2.4 Anchorage of shear reinforcement
The anchorage of shear reinforcement transverse to the longitudinal flexural reinforcement
may be achieved by a hook or cog complying with Clause 13.1.2.7 or by lapped splices.
Where lapped splices are used, the lap lengths shall be calculated in Clause 13.1.2, except
that for stirrups or fitments adjacent to the cover concrete a hook shall be provided at the
end of each lapped bar, and the lap length calculated in Clause 13.1.2 shall be multiplied by
1.3.
Shear reinforcement shall be deemed to be anchored provided the following criteria are
met:
(a) Bends in bars used as fitments shall enclose a longitudinal bar with a diameter not
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
less than the diameter of the fitment bar. The enclosed bar shall be in contact with the
fitment bend.
Where a fitment hook is located in the compression zone of the structural member,
where anchorage conditions are most favourable, the stirrup spacing shall comply
with Clause 8.3.2.1. Provided the hook complies with Clause 13.1.2.7, anchorage
shall be deemed to be satisfied.
(b) Where a fitment hook is located in the tension zone, the anchorage specified in
Item (b) shall be deemed to be satisfied, provided the stirrup spacing calculated in
accordance with Clause 8.2.5.1 is multiplied by 0.8 and the maximum spacing
specified in Clause 8.3.2.1 is multiplied by 0.8.
(c) Fitment cogs shall not be used when the anchorage of the fitment is solely in the outer
layer of reinforcement. In this case fitment hooks shall be used.
NOTE:The type of anchorage used should not induce splitting or spalling of the concrete cover.
8.3.2.5 End anchorage of mesh
Where mesh is used as shear reinforcement, the ends shall be anchored—
(a) in accordance with Clause 8.3.2.3, if the wires are bent at least to the dimensions of a
standard fitment hook; or
(b) by embedding two or more transverse wires at least 25 mm within the compressive
zone.
8.3.2.6 Horizontal curvature of tendons
The designer shall assess the bursting and/or splitting capacity of the beam due to forces
generated by the horizontal curvature of tendons.
TABLE 8.4.3
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
where
tf = thickness of topping or flange anchored by the shear reinforcement
8.4.5 Minimum thickness of structural components
The thickness of structural components subject to interface shear shall be not less than
70 mm.
*
cs = design shrinkage strain of concrete, at the time when
deflection is to be calculated
NOTE: If the short-term portion of the final long-term deflection
is to be calculated, cs is the final long-term shrinkage strain
determined in accordance with Clause 3.1.7.
Where appropriate, cs shall be increased to account for axial tension
induced by restraint to shrinkage by the support to the beams.
8.5.3.2 Long-term deflection
For reinforced and prestressed beams, that part of the deflection that occurs after the short-
term deflection shall be calculated as the sum of—
(a) the shrinkage component of the long-term deflection, determined from the design
shrinkage strain of concrete (cs) (see Clause 3.1.7) and the principles of mechanics;
and
(b) the additional long-term creep deflections, determined from the design creep
coefficient of concrete ( cc) (see Clause 3.1.8) and the principles of mechanics.
(b) The distance from the side or soffit of a beam to the centre of the nearest longitudinal
bar shall not exceed 100 mm. Bars with a diameter less than half the diameter of the
largest bar in the section shall be ignored. The centre-to-centre spacing of bars near a
tension face of the beam shall not exceed 300 mm. For T-beams and L-beams, the
reinforcement required in the flange shall be distributed across the effective width.
(c) Load effects shall be considered for the following two cases:
(i) SLS load combinations.
(ii) For beams designed for exposure classifications B2, C1, C2 and U only,
permanent effects at the SLS.
(d) For beams primarily subject to tension, the calculated steel stress (scr) shall not
exceed the maximum steel stress given in Table 8.6.1(A) for the largest nominal
diameter (db) of the bars in the section.
(e) For beams primarily subject to flexure, the calculated tensile steel stress (scr) shall
not exceed the larger of the maximum steel stresses given in—
(i) Table 8.6.1(A) for the largest nominal diameter (db) of the bars in the tensile
zone; and
(ii) Table 8.6.1(B) for the largest centre-to-centre spacing of adjacent parallel bars
in the tensile zone.
Bars with a diameter less than half the diameter of the largest bar in the section shall
be ignored when determining spacing.
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
NOTE: Design bending moments M s* at the SLS are typically estimated using elastic analysis.
Significant errors may result if they are determined from the design bending moments M* at the
strength limit state when the amount of moment redistribution is unknown; for example, if plastic
methods of analysis are used for strength design.
TABLE 8.6.1(A)
MAXIMUM STEEL STRESS FOR TENSION OR FLEXURE
Loading case specified in Loading case specified in
Nominal bar diameter (db ) Item (c)(i) Item (c)(ii)
mm Maximum steel stress (f scr )
MPa
10 360 275
12 330 250
16 280 215
20 240 185
24 210 160
28 185 140
32 160 125
36 140 110
40 120 95
NOTES: Values for other bar diameters may be calculated using the appropriate equations, as
follows:
(a) f scr = [760 – 173log e (d b )] MPa for loading case specified in Item (c)(i).
(b) f scr = [575 – 130log e (d b )] MPa for loading case specified in Item (c)(ii).
TABLE 8.6.1(B)
MAXIMUM STEEL STRESS FOR FLEXURE
Loading case specified in Loading case specified in
Centre-to-centre spacing Item (c)(i) Item (c)(ii)
mm Maximum steel stress (f scr )
MPa
50 360 280
100 320 240
150 280 200
200 240 160
250 200 120
300 160 80
NOTES: Values for other centre-to-centre spacings may be calculated using the appropriate
equation, as follows:
(a) f scr = [400 (0.8 centre-to-centre spacing)] MPa for loading case specified in
Item (c)(i).
(b) f scr = [320 (0.8 centre-to-centre spacing)] MPa for loading case specified in
Item (c)(ii).
combinations, the resulting maximum tensile stress in the concrete does not exceed 0.25 f c
and 0.25 f cp , or, if this stress is exceeded, by providing reinforcement or bonded tendons,
or both, near the tensile face with a centre-to-centre spacing not exceeding 200 mm and
limiting either—
(a) the calculated maximum flexural tensile stress under SLS load combination, including
transfer limited to 0.5 f c and 0.5 f cp ; or
(b) the increment in steel stress near the tension face to that given in Table 8.6.2.1, as the
load increases from its value when the extreme concrete tensile fibre is at zero stress
to the SLS load combinations values.
TABLE 8.6.2.1
MAXIMUM INCREMENT OF STEEL STRESS
FOR FLEXURE IN PRESTRESSED BEAMS
Nominal reinforcement Maximum increment
bar diameter (d b ) of steel stress
mm MPa
12 330
16 280
20 240
24 210
28 200
All bonded tendons 200
unit.
NOTES:
1 Typical cross-sections of composite members are depicted in Figure 8.10.1.
2 For standard precast prestressed concrete beam sections, see Appendix D.
A continuous composite member can consist of a succession of simply supported
prestressed concrete beams made continuous by the provision of non-prestressed
reinforcement in the cast-in-place concrete over the intermediate supports.
Monolithic action of composite beams up to the strength ULS in bending of the member
shall be deemed to comply where—
(a) longitudinal shear at the contact surface can be transferred without excessive slip;
(b) separation of the elements normal to the contact surface is prevented.
NOTE: The transfer of shear can be achieved by a combination of bond, roughness, steel ties and
shear keys.
Ca st- in - p l ac e
c o n c rete
Ca st- in - p l ac e
c o n c rete
8.10.2.2 Analysis
The following assumptions shall be applied:
(a) The effective width of the concrete slab shall be used in the design of a concrete
member and shall be determined in accordance with Clause 8.8.
(b) The effective cross-sectional area of the concrete slab shall be transformed to an
equivalent area of beam concrete by applying the modular ratio factor (αc) of the slab
concrete and the beam concrete in the composite member.
8.10.3 Design for applied loads
8.10.3.1 General
All components and composite members shall be designed in accordance with this Section
for all loads to which they are subjected.
NOTE: Particular attention should be given to the validity of any assumptions about concrete
stress-strain relationships being adopted when high compression stresses occur at SLS.
8.10.3.2 Effects due to residual creep and differential shrinkage
8.10.3.2.1 General
Residual creep is that portion of the creep that occurs in the precast element after
establishing composite action.
The procedures in Clauses 8.10.3.2.2 and 8.10.3.2.3 shall be used to determine the effects
of residual creep in a composite member subject to dead load and prestress only, and the
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
(b) Continuous members Stresses in a continuous composite member due to dead load,
prestress after all losses and creep shall be calculated by considering the continuous
member separated into simply supported spans, and then restoring continuity by
applying restraint moments at the supports. The final stresses at any section shall be
the sum of the stresses occurring in each simply supported span calculated in
accordance with Item (a) above and those stresses caused by 1 e cc.j the continuity
restraint moments resulting from the application of both the dead load and prestress to
the continuous composite section [described in Item (a)(ii)].
The restraint moments may be calculated by any method using elastic analysis. The restraint
moment calculation shall be based on the assumption that continuity and composite action
are established in all spans simultaneously at time (tj). A minimum and maximum estimated
value of tj shall be used in the calculation of creep and shrinkage effects.
NOTE: In a composite member, creep occurring in the precast beam results in a redistribution of
stresses between the beam and the cast-in-place concrete slab. The magnitude of these stresses
depends on the age of the precast beam when composite behaviour is established. If a large
proportion of the creep in the beam has taken place by the time the slab is cast, the effect of
subsequent creep will be small.
8.10.3.2.3 Effect of differential shrinkage
Differential shrinkage effects between the precast beam and the cast-in-place concrete shall
be evaluated as follows:
(a) Simply supported members Stresses and deformations in the composite member, due
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
1 e cc.j
differential shrinkage force = Ec Acscs.j . . . 8.10.3.2.3
cc.j
where
Acs = area of cast-in-place concrete
TABLE 8.10.3.2.3
FACTORS USED FOR RESIDUAL CREEP AND DIFFERENTIAL SHRINKAGE
CALCULATIONS IN COMPOSITE MEMBERS
cc.j
1 e 0 0.393 0.632 0.865 0.950 0.982 0.993
cc.j
1 e
1.0 0.787 0.632 0.432 0.317 0.245 0.199
cc.j
L
(Minimum 30%)
(b) Main reinforcement perpendicular to traffic:
3500
Percentage = . . . 9.1.2(2)
L
(Minimum 30%)
For main reinforcement perpendicular to traffic, the amount of distribution
reinforcement in the outer quarters of the span may be reduced by a maximum of
50%.
For rail bridges, the distribution reinforcement for slabs shall be based on a rational
analysis using rail traffic loading as specified in AS 5100.2.
9.1.3 Edge stiffening
Edge stiffening of slabs shall be considered as follows:
(a) Longitudinal Edge beams shall be provided for all slabs having main reinforcement
parallel to traffic. An edge beam may consist of a kerb section, a beam integral with
the slab, or a slab edge additionally reinforced or extended.
(b) Transverse Transverse edges at the ends of the bridge and at intermediate points
where the continuity of the slab is disrupted shall be additionally reinforced or
supported by edge beams or diaphragms designed for the full effects of the wheel
loads.
The need for longitudinal or transverse edge stiffening of slabs shall be based on a rational
analysis of the slab using the specified loadings plus any other loading that may be applied
to the edge of the slab during the life of the structure.
The design shear strength of a slab shall be taken as ϕVu, where Vu shall be determined in
accordance with Clause 8.2, Clause 9.2.3 or Clause 9.2.4 as appropriate.
9.2.3 Shear strength of slabs without moment transfer
The ultimate shear strength of a slab with no moment transfer (Vuo) shall be taken equal to
Vu and shall be calculated as follows:
(a) Where no shear reinforcement or fabricated shear head is provided—
Vuo
ud om f cv 0.3 cp . . . 9.2.3(1)
where
u = length of the critical shear perimeter as defined below
dom = mean value of do, averaged around the critical shear perimeter (u)
fcv = concrete shear strength, given by
2 . . . 9.2.3(3)
0.171 f c 0.34 f c
h
σcp = average intensity of effective prestress in the concrete
h = ratio of the longest overall dimension of the effective loaded area (Y) to the
shortest overall dimension (X) measured perpendicular to Y (see
Figure 9.2.3)
For the purpose of this Clause, the critical shear perimeter (u) is defined by a line
geometrically similar to the boundary of the effective area of a support or load and located
at a distance of dom/2 from the boundary as shown in Figure 9.2.3. The effective area of a
support or load shall be that area totally enclosing the actual support or load for which the
perimeter is a minimum.
That part of the critical shear perimeter that is enclosed by radial projections from the
centroid of the support or load to the extremities of any critical opening shall be regarded as
ineffective.
An opening shall be regarded as critical if it is located at a clear distance of less than 2.5bo
from the critical shear perimeter, where bo is the width of the critical opening as shown in
Figure 9.2.3(b).
bo
Cr it i c al s h ear
p er i m eter
Cr it i c al s h ear
p er i m eter In ef fe c t i ve
< 2 . 5b o portion
dom
2
dom dom
In ef fe c t i ve
X 2 2 portion
Y
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
Y < 2 . 5b o
dom
2
B o u n d ar y of ef fe c t i ve X
area s of su p p or t or l oad dom bo
B o u n d ar y of ef fe c t i ve
area s of su p p or t or l oad 2
zone; and
(ii) Table 9.4.1(B) for the largest centre-to-centre spacing of adjacent parallel bars
in the tensile zone and, when determining spacing, bars with a diameter less
than half the diameter of the largest bar in the section shall be ignored.
For areas of slabs fully enclosed within a building except for a brief period of weather
exposure during construction and, where it is assessed that crack control is not required,
only Item (a) and Item (b) shall be satisfied.
NOTE: Design bending moments M s* at the SLS are typically estimated using elastic analysis.
Significant errors may result if they are determined from the design bending moments M* at the
strength limit state when the amount of moment redistribution is unknown; for example, if plastic
methods of analysis are used for strength design.
TABLE 9.4.1(A)
MAXIMUM STEEL STRESS FOR FLEXURE
IN REINFORCED SLABS—NOMINAL DIAMETER
TABLE 9.4.1(B)
MAXIMUM STEEL STRESS FOR FLEXURE
IN REINFORCED SLABS—CENTRE-TO-CENTRE SPACING
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
(b) the increment in steel stress near the tension face to that given in Table 9.4.2, as the
load increases from its value when the extreme concrete tensile fibre is at zero stress
to the SLS load combination value.
For prestressed members in exposure classifications B2, C1, C2 or U, the concrete at the
level of each tendon shall be in compression under the SLS load combinations that
comprises permanent effects plus 50% of the transient serviceability load(s).
TABLE 9.4.2
MAXIMUM INCREMENT OF STEEL STRESS
FOR FLEXURE IN PRESTRESSED SLABS
Nominal reinforcement Maximum increment of steel stress f c MPa
bar diameter (d b )
mm D s 300, mm D s > 300, mm
10 320 360
12 300 330
16 265 280
20 240
24 210
28 200
All bonded tendons 200
concrete decks on concrete or steel girders, in the restrained direction shall be not less
than—
(8.0 2.5σcp)bDeff 103 . . . 9.4.3
NOTE: Reinforcement provided for structural reasons may be considered as contributing to
this requirement.
(b) The reinforcement calculated using Equation 9.4.3 shall be placed equally with half
on each face of the slab and located as close to each face as cover and detailing
permit. Deff shall be taken as—
(i) D, where D is less than 500 mm; or
(ii) 500 + 0.2(D 500), where D is greater than 500 mm.
9.4.4 Crack control at openings and discontinuities
For crack control at openings and discontinuities in a slab, additional, properly anchored,
reinforcement shall be provided.
9.4.5 Crack control in the vicinity of restraints
In the vicinity of restraints, special attention shall be paid to the internal forces and cracks
which may be induced by prestressing, shrinkage or temperature.
10.1 GENERAL
10.1.1 Design strength
The design strength of a column shall be determined by its ability to resist the axial forces
and bending moments caused by the design loading for strength and any additional bending
moments produced by slenderness effects.
10.1.2 Minimum bending moment
At any cross-section of a column, the design bending moment about each principal axis
shall be taken to be not less than N* times 0.05D, where D is the overall depth of the
column in the plane of the bending moment.
10.1.3 Definitions
For the purpose of this Section the definitions below apply.
10.1.3.1 Braced column
Column in a structure for which the lateral actions applied at the ends in the direction under
consideration are resisted by components such as shear walls or lateral bracing.
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
Short columns shall be designed in accordance with this Clause and Clauses 10.6 and 10.7,
with additional bending moments due to slenderness taken to be zero. Alternatively, for
short columns with small axial forces, the design may be in accordance with Clause 10.3.2.
A column shall be deemed to be short where—
(a) for a braced column—
Le/r 25; or
c 38 f c / 15 1 M 1* / M 2* . . . 10.3.1(1)
c 1 / 3.5 N * / 0.6 N uo for N*/0.6Nuo < 0.15
The additional end moments calculated from moment magnification may be distributed to
the members of the joint in proportion to their stiffness.
10.4.2 Moment magnifier for a braced column
The moment magnifier () for a braced column shall be taken to be equal to b given by—
b = km/(1N*/Nc) 1 . . . 10.4.2
where
Nc = buckling load given in Clause 10.4.4
km = 0.6 0.4M *
/ M 2* but shall be taken as not less than 0.4, except that if the
1
column is subjected to significant transverse loading between its ends and in
the absence of more exact calculations, k m shall be taken as 1.0
10.4.3 Moment magnifier for an unbraced column
The moment magnifier () for an unbraced column shall be taken as the larger value of b or
s where—
(a) b for an individual column is calculated in accordance with Clause 10.4.2, assuming
the column is braced; and
(b) s for each column in a bent is calculated as—
1/(1N*/N c) . . . 10.4.3(1)
where the summations include all columns within the storey and Nc is calculated for
each column in accordance with Clause 10.4.4.
As an alternative to Item (b), s may be calculated from a linear elastic critical buckling
load analysis of the entire frame, where s is taken as a constant value for all columns given
by the following equation:
s 1 /1 1 d / s uc . . . 10.4.3(2)
where
d = N G* N * and taken as zero when Le/r 40 and N* M*/2D
10.5 SLENDERNESS
10.5.1 General
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
The slenderness ratio (Le/r) of a column shall not exceed 120, unless a rigorous analysis has
been carried out in accordance with Clauses 6.4, 6.5 or 6.6 and the column is designed in
accordance with Clause 10.2.3.
Where the forces and moments acting on a column have been obtained from a linear elastic
analysis, as specified in Clause 6.2, the influence of slenderness shall be taken into account
using a radius of gyration (r) specified in Clause 10.5.2 and an effective length (Le), in
accordance with Clause 10.5.3.
10.5.2 Radius of gyration
The radius of gyration (r) shall be calculated for the gross concrete cross-section.
NOTE: For a rectangular cross-section, r may be taken as 0.3D, where D is the overall dimension
in the direction in which stability is being considered and for a circular cross-section, r may be
taken as 0.25D.
10.5.3 Effective length of a column
The effective length of a column (Le) shall be taken as kLu, where the effective length factor
(k) is determined from Figure 10.5.3(A) for columns with simple end restraints, or more
generally from Figure 10.5.3(B) or 10.5.3(C), as appropriate.
The end restraint coefficients (1 and 2) shall be determined—
(a) where the column ends at a footing, in accordance with Clause 10.5.5;
(b) for all other structures, including non-rectangular framed structures or structures
where the axial forces in the restraining members are large, in accordance with
Clause 10.5.4.
Alternatively, the effective length of a column may be determined from the elastic critical
buckling load of the frame, as calculated by analysis.
Br ac e d c o lum n Un br ac e d c o lum n
Buckled
shape
Ef fe c t i ve l e n g t h
0.70 0.8 5 1.0 0 1.3 0 1. 20 2. 20 2. 20
fac tor (k)
FIGURE 10.5.3(A) EFFECTIVE LENGTH FACTOR (k) FOR COLUMNS WITH SIMPLE
END RESTRAINTS
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
∞
50
0.
10
95
6
0.
90
3
0.
2
85
EN D RESTR AINT COEFFICIENT γ 1
γ2
1. 5
0.
1. 2
80
1.0 k
0.
75
γ1
0.
70
0. 5
0.
65
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
0.
60
0.
55
0 ∞
0 0. 5 1.0 1. 2 1. 5 2 3 4 6 10 5 0
∞
50
4
3
10
2.
5
6
2.
0
4
1.
3
8
1.
6
2
EN D RESTR AINT COEFFICIENT γ 1
γ2
1.
5
1. 5
1.
4
1. 2 k
1.0
1.
3
1.
25
γ1
1.
20
1.
0. 5
15
1.
10
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
1.
05
0 ∞
0 0. 5 1.0 1. 2 1. 5 2 3 4 6 10 5 0
TABLE 10.5.4
FIXITY FACTOR ()
Fixity factor ( )
Fixity conditions at far end
of a column, beam or slab Beam or slab or both, Beam or slab or both,
in a braced frame in an unbraced frame
Pinned 1.5 0.5
Rigidly connected to a column 1.0 1.0
Fixed 2.0 0.67
Calculations for the strength of cross-sections in bending, combined with axial forces, shall
incorporate equilibrium and strain-compatibility considerations and be consistent with the
following assumptions:
(a) Plane sections normal to the axis remain plane after bending.
(b) The concrete has no tensile strength.
(c) The distribution of stress in the concrete and the steel is determined using a stress-
strain relationship determined from Clauses 3.1.4 and 3.2.3 respectively (see Note 1).
(d) The strain in compressive reinforcement does not exceed 0.003.
(e) Where the neutral axis lies outside of the cross-section, consideration is given to the
effect on strength of spalling of the cover concrete.
NOTE: If a curvilinear stress-strain relationship is used then—
(a) Clause 3.1.4 places a limit on the value of the maximum concrete stress; and
(b) the strain in the extreme fibre may be adjusted to obtain the maximum bending strength for a
given axial load.
The provisions in Items (c) and (d) above shall not be used to assess the flexural strength at
plastic hinge zones for seismic design (see Clause 10.2.4.3).
Columns subject to axial force with bending moments about each principal axis may take
into account the concessions given in Clauses 10.6.3 and 10.6.4.
10.6.2 Strength of cross-sections calculated using the rectangular stress block
10.6.2.1 General
This Clause shall not apply to the assessment of flexural strength at plastic hinge zones for
seismic design.
It shall be permissible to represent the strength of a cross-section in combined bending and
compression using a strength interaction diagram as shown in Figure 10.6.2.1 defined as
given in Clauses 10.6.2.2 to 10.6.2.5.
Decompression
p o int (Cl au s e 10.6. 2. 3)
A XIAL LOAD
B a l an c e d
p o int
C l au s e 10.6. 2. 5
Pure b e n d in g
p o int (Cl au s e 8 .1)
M O M ENT
D
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
0.1D
b 0. 2 D
0.1b
0. 2 b
M 2*
(i) 0.4 L ; and
M 1* M 2*
φN u o
Re g i o n w h ere t h e d e s i g n ac t i o n
ef fe c t s of c o m b in e d a x i al for c e
DESIG N A XIAL FORCE
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
an d b e n d in g o n a se c t i o n
0.75φN u o require c o nfinement to the c ore
(φM u , φN u)
φN u
(0.6φM u , φN u)
φ 0.3 A g f ’c
0.6φM u φM u o
DESIG N M O M ENT
M 1*
Special confinement
1.2D region
0.6φM u
0.6φM u
Special confinement
1.2D region
M *2
D
0.6φM u
A
i 1
b.fit f sy.f sin
. . . 10.7.3.3(2)
fr
ds s
where
Ab.fit = cross-sectional area of one leg of the fitment
fsy.f = yield stress of the reinforcement used as fitment (not greater than 500 MPa)
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
where
Ac = cross-sectional area bounded by the centre-line of the outermost fitments
n = number of laterally restrained longitudinal bars [see Clause 10.7.4.2(a)]
w = average clear spacing between adjacent tied longitudinal bars
bc = core dimension measured between the centre-lines of the outermost
fitments measured across the width of the section
dc = core dimension measured between the centre-lines of the outermost
fitments measured through the depth of the section
(b) For circular sections:
2
s
k e 1 . . . 10.7.3.3(4)
2d s
Alternatively, for rectangular or circular columns, the effective confining pressure applied
to the core of a column may be calculated as follows:
fr.eff = 0.5kes fsy.f . . . 10.7.3.3(5)
where
s = volumetric ratio of the fitments relative to the volume of the core calculated
as
Ab.fit total perimeter of fitments crossing the section
s
Ac s
bc
fr A b.f i t f s y.f
ds
fr A b.f i t f s y.f
(a) (b)
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
bc y
Y
A b.f i t f s y.f
dc f r.y y
A b.f i t f s y.f x
fr Y
bc
A b.f i t f s y.f (s in θ)
2 A b.f i t f s y.f (s in θ)
fr = X X
bcs
f r. x x A b.f i t f s y.f
f r = m in.(f r. x x , f r.y y)
(c) (d)
where
n = number of laterally restrained longitudinal bars [see Clause 10.7.4.2(a)]
(b) For circular sections:
100 Ab. fit f sy.f
. . . 10.7.3.4(2)
d s f c
10.7.4 Restraint of longitudinal reinforcement
10.7.4.1 General requirements
The following longitudinal bars in columns shall be laterally restrained in accordance with
Clause 10.7.4.2:
(a) Single bars—
(i) each corner bar;
(ii) all bars, where bars are spaced at centres of more than 150 mm; and
(iii) at least every alternate bar, where bars are spaced at 150 mm or less.
Where N* 0.5 Nu the requirements of Items (ii) and (iii) do not apply.
(b) Bundled bars, each bundle of longitudinal bars.
10.7.4.2 Lateral restraint
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
(a) The bar diameter of the fitment and helical reinforcement shall be not less than that
given in Table 10.7.4.3.
(b) The spacing of fitments, or the pitch of a helix, shall not exceed the smaller of—
(i) 0.4Dc and 15db for single bars; or
(ii) 0.4Dc and 7.5db for bundled bars,
where
Dc = smaller column cross-sectional dimension if rectangular or the
column diameter if circular
db = diameter of the smallest bar in the column
(c) One fitment, or the first turn of a helix, shall be located not more than 100 mm
vertically above the top of a footing, or the top of a slab. Another fitment, or the final
turn of a helix, shall be located not more than 50 mm vertically below the soffit of the
member except that in a column with a capital, the fitment or turn of the helical
reinforcement shall be located at a level at which the area of the cross-section of the
capital is not less than twice that of the column.
Where beams or brackets frame from four directions into a column and adequately
restrain the column in all directions, the fitments or helical reinforcement may be
terminated 50 mm below the highest soffit of such beams or brackets.
TABLE 10.7.4.3
BAR DIAMETERS FOR FITMENTS AND HELICES
Longitudinal bar diameter Minimum bar diameter
of fitment and helix
mm mm
Single bars up to 20 6
Single bars 24 to 28 10
Single bars 28 to 36 12
Single bars 40 16
Bundled bars 12
(d) Helical reinforcement shall be spliced within its length either by welding or
mechanical means or by lapping the helix one turn and bending the helix end into the
column core for an extension of 25 the helix bar diameter.
(e) Where hooks or cogs are specified in combination with bundled bars, the internal
diameter of the bend shall be increased sufficiently to accommodate the bundle.
(f) A rectangular fitment shall not be anchored by welding to longitudinal reinforcement.
10.7.5 Splicing of longitudinal reinforcement
10.7.5.1 General
Longitudinal reinforcement in columns shall be spliced in accordance with Clauses 10.7.5.2
to 10.7.5.5. The splices shall comply with Clause 13.2.
10.7.5.2 Minimum tensile strength
At any splice in a column, a tensile strength in each face of the column of not less than
0.25fsyAs shall be provided, where As is the cross-sectional area of longitudinal
reinforcement in that face.
10.7.5.3 Where tensile force exceeds the minimum tensile strength
At any splice in a column where tensile stress exists and the tensile force in the longitudinal
bars at any face of the column, due to strength design load effects, exceeds the minimum
tensile strength requirements specified in Clause 10.7.5.2, the force in the bars shall be
transmitted by—
(a) a welded or mechanical splice in accordance with Clause 13.2.6; or
(b) a lap-splice in tension in accordance with Clause 13.2.2 or Clause 13.2.5, as
appropriate.
NOTE: This Clause does not apply to bridge structures in earthquake design category BEDC-1;
however, compliance with this Clause is recommended for all structures.
Unless demonstrated by analysis that plastic hinges will not form in columns during the
design earthquake, as specified in AS 5100.2, ductile seismic detailing in accordance with
this Clause shall apply.
In this application, non-prestressed reinforcement shall be Ductility Class E or Ductility
Class N only.
10.7.6.2 Column core confinement
10.7.6.2.1 General
Deformed bars shall be used for all lateral (confinement) reinforcement, including stirrups,
ties, helices and hoops.
10.7.6.2.2 Lateral reinforcement inside plastic hinge zones
Where N* > 0.2Nuo, confinement reinforcement shall be provided as follows:
The lateral (confinement) reinforcement in plastic hinge zones shall restrain the
longitudinal reinforcement against buckling, confine the core concrete in the event that
cover spalling occurs, and ensure that shear failure will not occur during the design seismic
event, as follows:
(a) Where helices or circular fitments are used, the volumetric ratio of confinement (ρs),
shall be—
0.0075 f ce
s 0.005 . . . 10.7.6.2.2(1)
f sy.f
where
f ce = expected compressive strength of the concrete (may be taken as 1.3 f c )
fsy.f = yield strength of the reinforcement used as fitments
(b) Where rectangular fitments are used, the total cross-sectional area of the ties (Asv),
including supplementary cross-ties, shall be not less than—
Asv 0.055sy1 f ce f sy.f 0.006 ; and . . . 10.7.6.2.2(2)
s 0.006 . . . 10.7.6.2.2(3)
where
s = centre-to-centre spacing of ties along the longitudinal axis of the
member
y1 = core dimension of a closed rectangular tie in the direction under
consideration, as illustrated in Figure 10.7.6.4
Where N* < 0.2Nuo at least half the reinforcement specified in Items (a) and (b) shall be
provided.
10.7.6.2.3 Minimum lateral reinforcement
The volumetric ratio of the lateral reinforcement (ρs) shall be not less than 0.0025 for
circular columns and 0.003 for rectangular columns in locations where:
N* > 0.2Nuo and category BEDC-4 applies
N* > 0.2Nuo and category BEDC-3 applies and µ 3
10.7.6.3 Spacing of lateral reinforcement at plastic hinge
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
(c) The lateral reinforcement required within the predicted and plastic hinge zones shall
extend into the footing, pile cap or superstructure, as applicable, for a length not less
than half the maximum dimension of the column or 400 mm, whichever is greater
(see Figure 10.7.6.4).
≥ t h e l ar g er of 4 0 0 m m
M1 ma x. and ½ pile d i ameter
≥ t h e l ar g er of p il e
Bending d i a m e te r a n d r e g i o n w i t h
m o m e nt m o m e nt ≥ 8 0% of M 1 m a x
S e i s m i c c o nfi n m e nt
8 0%
of M 1 m a x .
Lo n g i t u d i n a l b ar s
L of p il e
N o r m a l c o nfi n e m e nt
C
S e i s m i c c o nfi n e m e nt
8 0% of M 2 m a x .
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
Bending
m o m e nt ≥ t h e l ar g er of p il e
d i a m e te r a n d r e g i o n w i t h
m o m e nt ≥ 8 0% of M 1 m a x
M2 max.
≥ t h e l ar g er of p il e
d i ameter and with
m o m e nt ≥ 8 0% of M 2 m a x .
8 0% of M 2 m a x .
N o r m a l c o nfi n e m e nt
10.7.6.5 Splicing and anchoring of lateral reinforcement within plastic hinge zones
The following applies for splicing and anchoring of lateral (confinement) reinforcement:
(a) Splicing of helices shall be by welding or mechanical splicing in accordance with
Clause 13.2.6.
(b) Closed ties shall not be anchored by welding to the longitudinal reinforcement.
Closed ties shall end with 135° hooks in accordance with Clause 13.1.2.7.
(c) Internal fitments used as seismic confinement in predicted plastic hinge zones in
columns with rectangular cross-sections shall comprise a straight bar with a 135°
seismic hook at one end and fully anchored at the other end.
11.1 GENERAL
This Section applies to the following:
(a) Braced walls (as defined in Clause 11.3) that are subject to in-plane load effects,
which shall be designed in accordance with Clauses 11.2 to 11.7.
(b) Braced walls that are subject to simultaneous in-plane and out-of-plane load effects
and unbraced walls, which shall be designed in accordance with Section 9, Section 10
and Section 11, as appropriate.
Where the maximum compressive stress at the mid-height section of a wall due to
factored in-plane bending and axial forces does not exceed the lesser of 0.03 f c and
2 MPa, the wall may be designed as a slab in accordance with Section 9, provided—
(i) second-order deflections due to in-plane loads and long-term effects are
considered in the calculation of bending moments; and
(ii) the ratio of effective height to thickness does not exceed 50.
Braced walls where in-plane horizontal forces, acting in conjunction with the axial forces,
are such that where a horizontal cross-section of the wall—
(a) is subject to compression over the entire section, in-plane bending may be neglected
and the wall designed for horizontal shear forces in accordance with Clause 11.6 and
for the vertical compressive forces either—
(i) in accordance with the simplified method of Clause 11.5; or
(ii) as columns in accordance with Section 10 where vertical reinforcement is
provided in each face, except that Clause 11.7.4 may override the requirements
of Clause 10.7.4; or
(b) is subject to tension on part of the section, the wall shall be designed for in-plane
bending in accordance with Section 8 and for horizontal shear in accordance with
Clause 11.6 or, for in-plane bending and shear, in accordance with Section 12, if
appropriate.
11.2.2 Groups of walls
When two or more walls are directly inter-connected, or linked to each other by coupling
beams or the like, the distribution of in-plane load effects between the walls shall be
obtained by linear elastic analysis of the overall structure under the global vertical and
lateral loads. The analysis shall distribute in-plane load effects to the individual walls in
proportion to their relative stiffness, as determined by their gross cross-sectional properties.
The interconnected vertical edges of walls shall be designed to withstand the transmitted
vertical shear forces.
(b) 2.5% of the total vertical load the wall is designed to carry at the level of lateral
support, but not less than 2 kN per metre length of wall.
1
k where Hw L1 . . . 11.4(2)
1 H w / L1
2
L1
k where Hw > L1 . . . 11.4(3)
2H w
Walls supported laterally on four sides that contain one or more openings shall be
designed as follows:
(i) If the total area of the openings is less than 1/10 of the area of the wall and the
height of any opening, not vertically one above the other, is less than 1/3 of the
height of the wall, then the effect of the openings may be ignored.
(ii) In other cases—
(A) the area of the wall between the support and the opening shall be
designed as supported on three sides; and
(B) the area between the openings shall be designed as supported on two
sides.
NOTE: An intersecting wall with a minimum length of 0.2H w may be considered a lateral
restraint.
where
= 0.6
Nu = tw 1.2e 2ea 0.6 f c . . . 11.5(2)
where
Vu = Vuc + Vus
and Vuc and Vus shall be determined from Clause 11.6.3 and Clause 11.6.4
respectively, but in no case shall Vu be taken as greater than—
Vu.max. 0.2 f c 0.8 Lw t w
The value of shall be determined from Table 2.3.2.
11.6.3 Shear strength without shear reinforcement
The ultimate shear strength of a wall without shear reinforcement (Vuc) shall be taken as
follows:
(a) For Hw/Lw 1—
H
Vuc 0.66 f c 0.21 w f c 0.8 L w t w ; or . . . 11.6.3(1)
Lw
(b) For Hw/Lw > 1, the lesser of the values calculated from Item (a) above; and—
0.1 f c
Vuc 0.05 f c 0 .8 L w t w . . . 11.6.3(2)
Hw
1
Lw
2tw En d re g i o n s 2tw
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
tw
15 0 15 0 2tw ma x. 2tw ma x.
max. max.
12.2 DESIGN
12.2.1 Design for strength
The design for strength shall be carried out using one of the following:
(a) Linear elastic stress analysis and the checking procedure given in Clause 2.3.3.
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
(b) Strut-and-tie analysis, and the checking procedure given in Clause 2.3.4.
(c) Non-linear stress analysis and the checking procedure given in Clause 2.3.6.
The value of the capacity stress and strength reduction factor shall be determined according
to Clauses 2.3.3, 2.3.4 and 2.3.6 as appropriate, for the analysis and checking procedure
adopted.
12.2.2 Design for serviceability
Design for serviceability shall be in accordance with Clause 2.4 and Clause 12.7.
For Type II models, the force carried by the secondary struts shall be within the limits
0 Tw P, where Tw is the vertical component of the force carried by the secondary struts
and P is defined in Figure 12.3.2.
a P P
w
z d z
D
θ θ
T T
P P
(a) S tr ut- an d -t i e (b) S im p lifi e d
T YPE I
a P
P
a /2 a /2
w
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
Tw
z d z
D
T T
P P
(a) S tr ut- an d -t i e (b) S im p lifi e d
T YPE II
a P P
w
Tw
D d
z z
θ θ
T T
P P
(a) S tr ut- an d -t i e (b) S im p lifi e d
T YPE III
NOTE: Where no bearing pad is provided, the line of action may be taken at the
commencement of any edge chamfer, or at the outside face of the corbel or nib as appropriate.
(f) Where a flexural member is being supported, the outside face of a nib shall be
protected against spalling.
those regions beyond the anchor plates around anchorage recesses, and the outer
corners of cantilever slabs at the ends of post-tensioned members. Nominal
longitudinal or diagonal reinforcement detailed to cross the planes of potential
cracking shall be provided to secure these corners to the member.
(b) Internal anchorages Where internal anchorages (either dead end or stressing end)
are cast into a member at intermediate locations (see Figure 12.6.7), tensile zones can
develop behind the anchorage with tensile stresses parallel to the tendons, which
depend on the following:
(i) The magnitude of the anchored prestress forces.
(ii) The magnitude of the compressive stress in the longitudinal direction.
(iii) The ratio of the area of the anchorage to the total cross-sectional area of the
prestressed member.
Special reinforcement, designed to resist from 20% to 50% of the prestress force in
the tendon shall be provided to control these tensile stresses and shall be detailed as
shown in Figure 12.6.7. Such reinforcement shall extend at least over a length of 2D
as shown in Figure 12.6.7 and, have sufficient length to develop the yield stress (fsy)
of the reinforcing bar at the anchorage.
(c) External anchorages Where external anchorages (i.e. anchorages located on a
protruding bracket on the member) are used, reinforcement in addition to that
provided to resist the bursting tensile forces shall be designed, where applicable to—
(i) resist tension caused by curvature of tendons;
(ii) provide a shear connection to the main member and cater for the distribution of
the prestress force into the main member;
(iii) resist the forces as described in Item (b); and
(iv) resist tension caused by local eccentricity of prestress force.
S p e c i al B ur st i n g
r e i nfor c e m e nt reinforc ement
D = D e pt h of
m e m b er
C e nt r i o d
of te n d o n
L s y.t ≥ D L s y.t ≥ D
A n c h or ag e
200 MPa.
(b) For bursting or spalling forces, where the reinforcement forms the surface layer of
reinforcement on any face, the stress for this surface reinforcement is not greater than
150 MPa. Reinforcement shall be adequately anchored to develop this stress.
(c) For prestressed concrete, the change in stress in the tendons after the point of
decompression does not exceed the limits given by Item (a), or (b) as appropriate.
where
A2 = largest area of the supporting surface that is geometrically similar to and
concentric with A1
A1 = a bearing area
Where bearing areas are subject to high edge loading by the bearing plate, the design
bearing stress shall be not greater than 0.7 times the value specified above.
In the case of a bearing surface where the supporting structure is sloped or stepped, it shall
be permissible to take A2 as the area of the base of the largest frustum of a right pyramid or
cone—
(a) having for its opposite end the bearing area A1;
(b) having side slopes of 2 transversely to 1 longitudinally, with respect to the direction
of the load; and
(c) contained wholly within the supporting structure.
NOTE: This Clause is not applicable to the design of nodes within a strut-and-tie model.
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
where
k1 = 1.3 for a horizontal bar with more than 300 mm of concrete cast below the bar;
or
= 1.0
k2 = (132 – db )/100; and
k3 = 1.0 0.15(cd db ) / db (within the limits 0.7 k3 1.0);
where
db = diameter of the deformed bar developing stress
cd = a dimension, as shown in Figure 13.1.2.2
The value of f c used in Equation 13.1.2.2 shall not be taken to exceed 65 MPa.
The value of Lsy.tb calculated as above shall be multiplied by 1.3 for all structural elements
built with slip forms.
NOTE: A smaller value of L sy.t may be possible using the provisions of Clause 13.1.2.3.
C1
a a
c c
C1
(a) S tr ai g ht bar s (b) C o g g e d or h o o ke d bar s (c) Lo o p e d bar s
c d = m in (a /2, c 1, c) c d = m in (a /2, c 1) cd = c
(i) N ar r ow e l e m e nt s o r m e m b er s (e.g. b e a m we b s a n d c o l u m n s)
a a
c c
a
a
L s y.t L s y.t
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
db
(i i i) Pl a n ar v i ew of s t ag g er e d d eve l o p m e nt l e n g t h s of e q u i - s p a c e d b ar s
www.standards.org.au
TABLE 13.1.2.3
VALUES OF K FOR TYPICAL ARRANGEMENTS OF TRANSVERSE REINFORCEMENT FOR DIFFERENT MEMBER TYPES
Member type Examples of potential splitting cracks at a tensile face nf n bs K (see Note 2)
Circular column
1 1 0.10
A t r = A b.f i t
Rectangular
column
n f = 2, n b s = 2 n f = 2, n b s = 3
K= 0.10 K= 0.0 8 3 1 1
A t r = A b.f i t
Beam
161
0.05 K 0.10
n f = 2, n b s = 4
A t r = A b.f i t 1 1
K= 0.075
Slab or wall
(with fitments) n f= n bs
A t r = A b.f i t 1 1
K= 0.10
Slab or wall
(without fitments) A tr
1 per main 0.05
0
bar spacing (see Note 3)
LEGEND:
n bs = total number of bars being anchored at the location under consideration
n f = numbered of anchored bars at the location under consideration adjacent to, and restrained by, a transverse bar or fitment
Standards Australia
NOTES:
1 Fitments are a type of transverse reinforcement.
AS 5100.5:2017
2 The same value of K shall apply to all of the longitudinal bars being either anchored or lap spliced, i.e. it is a weighted average value.
3 To be effective, the transverse reinforcement shall be located between the longitudinal bars and the concrete tensile face as shown, otherwise K = 0.
AS 5100.5:2017 162
0. 5L s y.t
or 0. 5L s t
0. 5L s y.t
or 0. 5L s t
(a) S t an d ar d h o o k (b) S t an d ar d c o g
The headed bar shall be considered to have a development length (Lsy.hb ) measured from the
inside face of the head equal:
when Ahead/Abar = 4 Lsy.hb = 0.5Lsy.t . . . 13.1.4(1)
when Ahead/Abar 10 Lsy.hb = 6db . . . 13.1.4(2)
For values of Ahead/Abar between 4 and 10, the headed bar development length Lsy.hb shall be
obtained by linear interpolation.
Where the tensile force in a headed bar could give rise to bearing forces directed towards or
adjacent to a free concrete surface, failure of the concrete cone between the head of the bar
and the free concrete surface shall be investigated.
13.1.5 Development length of deformed bars in compression
13.1.5.1 Development length to develop yield strength
The development length in compression (Lsy.c) to develop the characteristic yield strength
(fsy) of a deformed bar in compression shall be calculated from either Clause 13.1.5.2 or
Clause 13.1.5.3, but shall be not less than 200 mm.
13.1.5.2 Basic development length
The development length in compression (Lsy.c) shall be taken as the basic development
length of a deformed bar in compression (Lsy.cb ) calculated from the following equation:
0.22 f sy
Lsy.cb d b 0.0435fsydb or 200 mm, whichever is the greater . . . 13.1.5.2
f c
NOTES:
1 A smaller value of L sy.c may be obtained using the provisions of Clause 13.1.5.3.
2 L sy.c for mesh may be calculated as for deformed bar.
The development length for plain bars in compression shall be twice the calculated value of
Lsy.c or Lsy.cb for a deformed bar.
NOTE: L sy.c for mesh may be calculated as for plain bar.
13.1.7 Development length of bundled bars
The development length of a unit of bundled bars shall be based on the development length
required for the largest bar within the bundle increased by—
(a) for a 3-bar bundle ......................................................................................... 20%; and
(b) for a 4-bar bundle ................................................................................................ 33%.
13.1.8 Development length of welded plain or deformed mesh in tension
13.1.8.1 Development length to develop yield strength
The development length (Lsy.t) of welded plain or deformed mesh, measured from the
critical section to the end of the bar or wire, shall be calculated in accordance with
Clause 13.1.8.2, Clause 13.1.8.3 or Clause 13.1.8.4, as appropriate.
13.1.8.2 Two or more cross-bars within development length
The yield strength of deformed bars of welded mesh shall be deemed to be developed by
embedding at least 2 cross-bars spaced at not less than 50 mm within the development
length, with the first cross-bar located not less than 50 mm from the critical section. For
plain bars, the 2 cross-bars shall be spaced at not less than 100 mm within the development
length.
13.1.8.3 One cross-bar within development length
When only one cross-bar is located within the development length, the minimum length
measured from the critical section to the outermost cross-bar shall be not less than Lsy.tb
calculated from—
Ab f sy
Lsy.tb 3.25 . . . 13.1.8.3
sm f c
but not less than 150 mm for plain mesh and not less than 100 mm for deformed mesh,
where
Ab = area of the individual bar being developed
s m = spacing of bars being developed
13.1.8.4 No cross-bars within development length
When no cross-bars are located within the development length, the development length of
welded mesh shall be determined in accordance with Clauses 13.1.2 and 13.1.3, as
appropriate.
13.1.8.5 Development length to develop less than the yield strength
The development length (Lst ) to develop a tensile stress ( st ) less than the yield strength (fsy)
shall be calculated from the development length determined from Clause 13.1.8.3 or
Clause 13.1.8.4, using the following equation:
st
Lst Lsy.tb . . . 13.1.8.5
f sy
Lst shall be not less than 150 mm for plain mesh and not less than 100 mm for deformed
mesh.
In narrow elements or members (such as beam webs and columns), the tensile lap length
(Lsy.t.lap) shall be not less than the larger of 29k1db , k7 Lsy.t and Lsy.t + 1.5sb , where sb is the
clear distance between bars of the lapped splice as shown in Figure 13.2.2. Provided sb does
not exceed 3db , then sb may be taken as zero for calculating Lsy.t.lap.
PL ANAR VIE W
(S e e N ote 1)
sL a sb
db
L s y.t . l a p c d = m in (a /2,c)
≥ 0.3L s y.t . l a p
sL
sb
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
L s y.t . l a p
c d = m in (a /2,c)
(ii) 5 0% st ag g ere d s p li c e s
NOTES:
1 For the purposes of determining c d , dimension a shall be taken equal to (s L d b ) irrespective of the value
of s b .
2 For the purposes of determining c d , dimension a shall be taken equal to 2s L irrespective of the value of s b .
s2 s2
s1 s1
TABLE 13.3.2.1
MINIMUM TRANSMISSION LENGTH
FOR PRETENSIONED TENDONS
In absence of test data, the bonded length to develop the stress in seven-wire pretensioned
strand at ultimate strength shall be taken as not less than—
Lp = 0.145(pu 0.67p.ef)db 60db . . . 13.3.2.2
where
p.ef = effective stress in the tendon after allowing for all losses
pu and p.ef are in megapascals.
Embedment less than the development length shall be permitted at a section of a member,
provided the design stress in the strand at that section does not exceed the values obtained
from the bi-linear relationship defined by this Clause and Clause 13.3.2.1.
The development length of de-bonded strand shall be taken to be 2Lp where the design
includes tension in accordance with Clauses 8.6.2 and 9.4.2 in the development length.
13.3.2.3 Development length of pretensioned wire
Pretensioned indented and crimped wire tendons shall be bonded beyond the critical section
for a length sufficient to develop the design stress in the wire but not less than 2.25 times
the value for the transmission length in Table 13.3.2.1 as appropriate.
13.3.2.4 Development length of untensioned strand or wire
Where strand or wire is untensioned, the development length shall be taken as not less than
2.5 times the value of the appropriate transmission length of a stressed tendon given in
Table 13.3.2.1 for a tendon stressed to the tensile strength (fpb) in Table 3.3.1.
13.3.3 Stress development in post-tensioned tendons by anchorages
Anchorages for tendons shall be capable of developing in the tendon the minimum tensile
strength (fpb).
In addition, anchorages for unbonded tendons shall be capable of sustaining cyclic loading
conditions.
14.1 JOINTS
14.1.1 General
A joint in a structure or member shall be designed and constructed so the load-carrying
capacity and serviceability of the structure or member is maintained while serving its
intended function. Joints shall be for construction purposes (construction joint) or to control
movement (movement joint), as appropriate.
14.1.2 Construction joints
14.1.2.1 General
Construction joints shall be designed and installed to satisfy intended construction practice
for the specific application. Construction joints shall be designed to produce a well-bonded
interface between hardened concrete and freshly placed concrete.
14.1.2.2 Joint spacing
Construction joints shall be located to facilitate the placement of concrete in accordance
with Clause 17.3.3 and to meet concrete placement restrictions and finishing requirements.
They shall be located in regions of minimal shear force and, where possible, in unobtrusive
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
locations. The spacing shall be determined by the rate of concrete placement and finishing
on site or as a result of any unplanned interruption to placement operations.
Where an interruption to the placing of concrete occurs such that the requirements of
Clause 17.3.3(c) or Clause 17.3.3(d) or Clause 17.3.3(e) cannot be fulfilled, a construction
joint shall be made at an appropriate location.
14.1.3 Movement joints
14.1.3.1 General
Movement joints shall be designed and constructed to—
(a) control movement at a joint;
(b) control cracking at design locations; or
(c) provide articulation and separation between concrete members in a structure and meet
their intended function without impairing the load-carrying capacity or serviceability
of either the structure or member.
Movement joints shall be formed between two concrete members to allow movement to
occur, typically as a result of shrinkage, creep, diurnal effects and differential settlement
(see Note 2).
NOTES:
1 For bearings and deck joints, see AS 5100.4.
2 Generally, movement joints will extend throughout the member depth imparting complete
discontinuity between adjoining concrete members; however, joints for shrinkage are not
necessarily formed through the depth of the member.
14.1.3.2 Joint spacing
In reinforced concrete members, the spacing of movement joints shall take into account
effects such as shrinkage, temperature movement, moisture change, creep and other relevant
factors. The level of prestress and subsequent member shortening shall also be considered
in prestressed concrete members.
serviceability of the member is satisfied, and the durability requirements of Clause 4.14.3.8
are met.
14.2.2 Pipes
Embedded conduits and pipes shall comply with the relevant Standards.
NOTE: Relevant Standards are—
(a) for electrical purposes .............................................................................. AS/NZS 3000; and
(b) for plumbing purposes .......................................................................... AS/NZS 3500 series.
Pipes intended to contain liquid, gas or vapour under pressure or extremes of temperature
may be embedded in structural concrete, provided the maximum pressure to which any
piping or fitting is intended to be subjected will not exceed 2000 kPa, and the effect that
inclusion of the pipe has on the strength and serviceability behaviour of the member is
taken into account.
14.2.3 Spacing
The minimum clear distance between embedded items, and between embedded items and
bars (including bundled bars), tendons or ducts, shall be sufficient to ensure the concrete
can be placed and compacted to comply with Clause 17.3.3.
14.3 FIXINGS
Fixings, including holding-down bolts, inserts and ferrules, shall comply with the
following:
(a) A fixing shall be designed to transmit all forces, acting or likely to act on it.
(b) Forces on fixings used for lifting purposes shall include an impact factor in assessing
the load.
(c) Fixings shall be designed to yield before ultimate failure in the event of overload.
(d) The anchorage of any fixings shall be designed in accordance with Section 13, as
appropriate. The design strength of this anchorage shall be taken as times the
ultimate strength, where = 0.6. In the case of shallow anchorages, cone-type failure
in the concrete surrounding the fixing shall be investigated taking into account edge
distance, spacing, the effect of reinforcement, if any, and concrete strength at time of
loading.
(e) In the absence of calculations, the strength of a fixing shall be determined by load
testing of a prototype to failure in accordance with Paragraph A4, Appendix A. The
design strength of the fixing shall be taken as times the ultimate strength where the
ultimate strength is taken as the average failure load divided by the appropriate factor
given in Table A4.3, Appendix A and = 0.6.
(f) The spacing between, and cover to, fixings shall be in accordance with Clause 14.2.3.
The cover for fixings shall be in accordance with Section 4. The cover for fire
resistance shall be in accordance with Section 5.
Where an item is not readily accessible for maintenance or replacement, it shall be designed
so that it will function for the life of the structure without maintenance.
15.1 GENERAL
Plain concrete shall be used only for members in which cracking will not induce collapse.
The provisions of this Section apply to—
(a) plain concrete pedestals, provided the unsupported height of the member is not
greater than three times the least lateral dimension;
(b) plain concrete footings supported by the ground;
(c) gravity retaining walls; and
(d) bored piles.
The value of throughout this Section shall be determined from Table 2.3.2.
15.2 DESIGN
15.2.1 Basic principles of strength design
Members shall be designed in accordance with the following:
(a) Design of members for flexure shall be based on a linear stress-strain relationship in
both tension and compression.
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
= 0.1uD1 2 / h f c 0.2uD f c
16.1 GENERAL
This Section shall apply where steel fibres are used to improve the performance and
capacity of reinforced and prestressed concrete structures.
The design of steel fibre reinforced concrete (SFRC) at both the ultimate and serviceability
limit states shall be based on the stress ( ) ≠ strain () relationships for SFRC as specified
in Clause 16.3.3.
NOTE: When using brittle fibres that rely on a fibre pullout failure mechanism to obtain member
ductility, care is required for cases where a significant number of fibres fracture or where fibres
result in local crushing of the concrete due to the local forces imposed on the matrix by the fibres.
Fibre fracture may occur where the bond between the fibre and the matrix is high, and this is
more likely in a high strength concrete combined with fibres of high bond capacity and of lower
strength steels. In assessing the suitability of a given fibre for a given application, bond-strength
gain in time and the resulting potential loss of ductility should be considered.
Steel fibres shall not be relied upon for strength under reverse cyclic loading, unless supported by
test data.
Steel fibres shall not be relied upon at constructions joints for either serviceability or
strength requirements.
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
Design procedures in this Section are for steel-fibre-reinforced concrete with a softening
classification only (see Figure 16.3.3.1). Hardening SFRC and the use of synthetic fibres is
beyond the scope of this Standard.
16.2 DEFINITIONS
For the purposes of this Section, the definitions below apply:
16.2.1 Crack mouth opening displacement (CMOD)
The width of a crack measured at its mouth in a flexural tensile test undertaken in
accordance with EN 14651.
16.2.2 Crack opening displacement (COD)
The width of a single localized crack, taken as an average on four sides, for a direct tensile
test on a strain softening SFRC dog-bone shaped specimen in accordance with
Clause 16.3.3.7.
16.2.3 Steel fibre reinforced concrete (SFRC)
A mixture of concrete and steel fibres.
16.2.4 Hardening behaviour
A material that displays an enhanced strength with increasing crack widths beyond that
measured at the point of initial cracking of the cementitious matrix.
16.2.5 Softening behaviour
A material that exhibits a loss of strength upon cracking.
16.2.6 Target dosage
The specified quantity of fibres in kilograms per cubic metre of concrete (kg/m3).
σ
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
ƒc t
ƒ0.5
ƒ 1. 5
ε
0 ε cr
COD
0 0. 5 m m 1. 5 m m
σ
Cr ac k l o c aliz at i o n
ƒ c t ≥ 1.1 ƒ c t m
ƒc t m
Cr ac k for m at i o n
ε
0 ε cr
COD
0 ≥ 0.3 m m
Alternatively, where matched direct and indirect testing has been undertaken in accordance
with Clause 16.3.3.6 for similar SFRC mixtures, the characteristic residual tensile may be
determined as—
f1.5 k R, 4 f R, 4 . . . 16.3.3.4
The stress results obtained from the test shall be multiplied by the three-dimensional
orientation factor k1, where—
1
k1 1 . . . 16.3.3.7
0.94 0.6lf / b
and lf is the length of the steel fibre and b is taken as the average of the width and depth of
the specimen taken at the critical section.
NOTES:
1 The factor k1 removes the influence of the boundaries on the fibre distribution and converts
the results of the test to a state where the fibres can be considered to be randomly orientated
in three-dimensional space.
2 Testing should be undertaken in a laboratory accredited by the National Association of
Testing Laboratories (NATA).
Univer sal
j o i nt
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
≥125
≥ 25
125
5
R 14
125
215
Ep ox y g lu e
≥125
(o ptional)
All dimensions ±5 mm
where
b = width of the specimen, in millimetres
hsp = distance between tip of the notch and top of cross-section, in millimetres
L = span
FRj = load recorded at CMODj (see Figure 16.3.3.9)
NOTE: Testing should be undertaken in a laboratory accredited by the National
Association of Testing Laboratories (NATA).
F
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
FL
F R .1
FR.2
FR.3
F R .4
CMOD (m m)
C
0. OD
C
M
M
05
O
D1
D 4
2
3
L
=
=
=
0.
3.
1.
2.
5
5
5
5
16.4.2 Strength of beams in bending and combined bending and axial force
Calculations for strength of cross-sections in bending shall incorporate equilibrium and
strain-compatibility considerations and be consistent with the following assumptions:
(a) Plane sections normal to the axis shall remain plane after bending.
(b) The stress in the SFRC in that part of the cross-section in tension shall be taken to be
f1.5 , where f1.5 is the characteristic residual tensile stress determined in accordance
with Clause 16.3.3.3.
(c) The distribution of compressive stress shall be determined from a stress-strain
relationship for the concrete in accordance with Clause 3.1.4.
The strength of a section in bending, or in combined bending and axial force, shall be
determined using rectangular stress blocks for the concrete in compression and concrete in
tension, as shown in Figure 16.4.2.
α 2 f c´
Cs
γdn Cc
dn
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
N. A .
d
D
f 1.´ 5 Tf
Ts
α 2 f c´
Cs
γdn Cc
dn
d N. A .
do
D
f 1.´ 5 Tf
Ts
0.6bv d o
16.4.5 Design for serviceability limit states
16.4.5.1 General
When an SRFC cross-section is uncracked, the full cross-section shall be assumed to be
active and both concrete and steel assumed to be elastic in tension as well as in
compression.
When an SRFC cross-section is cracked, the SFRC shall be assumed to be elastic in
compression, and capable of sustaining a tensile stress equal to 1.1 f1.5 .
Act = area of concrete within the tensile zone that is that part of the cross-section
calculated to be in tension just before formation of the first crack
fs.max = maximum stress permitted in the reinforcement immediately after formation
of the crack, given in either Table 8.6.1(A) or Table 9.4.1(A) as appropriate
fct.ef = tensile strength of the concrete effective at the time when the cracks may
first be expected to occur
Values of fct.ef shall be obtained from 0.6 f cm but shall be not less than
3.0 MPa, where fcm is the mean concrete compressive strength at the time
cracking is expected to occur
kc = coefficient that takes account of the nature of the stress distribution within
the section immediately prior to cracking
The relevant stress distribution is that resulting from the combined effects of
loading and restrained imposed deformations:
kc = 1.0 for pure tension (e = M/N = 0)
kc = 0.6 for pure bending
k1 = coefficient which allows for the effect of non-uniform self-equilibrating
stresses due to non-linear shrinkage or temperature profiles through the
member depth
In the absence of more detailed analysis, k1 may be taken as 0.8
kp = coefficient that takes account of the level of prestress and is given by:
cp e e
kp 1 1 k c 2 .4 6 k c . . . 16.4.5.3(2)
kk c f ct.ef D D
e/D = ratio of the eccentricity of the prestressing force on the cross-section (e)
measured from the centroidal axis of the uncracked section to the overall
depth of the cross-section in the plane of bending (D)
σcp = average intensity of the effective prestress (Pe/Ag)
16.4.5.4 Deflection control
16.4.5.4.1 General
The deflection of an SFRC member shall be calculated using the procedures outlined in
Clauses 16.4.5.4.2 and 16.4.5.4.3. Allowance shall be made for the expected load history,
the expected construction procedure and any anticipated deflections resulting from
deformation of forms or settlement of props.
16.4.5.4.2 Short-term deflection
The short-term deflections due to external loads and prestressing, which occur immediately
on their application, shall be calculated using the value of Ecj determined in accordance
with Clause 3.1.2 and the value of the effective second moment of area of the member (Ief).
The value of Ief may be determined from the values of Ief at nominated cross-sections as
follows:
(a) For a simply supported span, the value at midspan.
(b) In a continuous beam—
(i) for an interior span, half the midspan value plus one quarter of each support
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
value; or
(ii) for an end span, half the midspan value plus half the value at the continuous
support.
(c) For a cantilever, the value at the support.
For the purpose of the above determinations, the value of Ief at each of the cross-sections
nominated in Items (a) to (c) above shall be obtained from the instantaneous curvature
i M s* Ecj I ef calculated as the slope of the strain diagram in Figure 16.4.5.4.2(b) and
obtained by satisfying the requirements for rotational and horizontal equilibrium of the
stress distribution in Figure 16.4.5.4.2(c).
εo σ o= E cjε o
d n /3
dn Cc
(d+ d n)/2
D d d
ε s = ε o (d - d n)/d n
A st σ s= E sε s
1.1 f 1.
´5
16.5 DURABILITY
The minimum concrete grade and cover for SFRC in exposure classifications A, B1 and B2
shall be as for concrete without fibres and shall apply to the steel reinforcement only. SFRC
shall not be used in exposure classification C1 or C2.
NOTES:
1 Steel fibres do not require concrete cover as specified for steel reinforcement in Clause 4.14.
2 SFRC may not be suitable in some exposure classification U environments.
16.6 FIRE
The structural performance of SFRC for fire shall be determined in accordance with
Section 5 of this Standard.
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
The material properties for SFRC shall be as specified for concrete in Clause 5.4.1 except
that the characteristic residual tensile stress of SFRC at elevated temperatures ( f1.5θ ) shall
be either—
(a) taken as f1.5θ k θ1 f1.5 where kθ1 is given in Table 16.6; or
(b) determined statistically from tests.
TABLE 16.6
ELEVATED TEMPERATURE COEFFICIENT
FOR RESIDUAL TENSILE STRESS OF SFRC
Temperature of SFRC
0 100 500 700 1200
°C
k θ1 1.0 1.0 0.6 0.1 0.0
NOTE: Linear interpolation between values.
TABLE 16.7.3
PRE-CONSTRUCTION TESTS
Material Inspection/Test Purpose
Steel fibres Check delivery note Verify that the delivery is in
accordance with the order, and is
shipped from the correct source
Check CE label Verify that the fibres have the
correct CE-label which matches
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
TABLE 16.7.4
ROUTINE PRODUCTION CONTROL
Subject Inspection/Test Purpose Frequency
Equipment inspection
Automatic dosing Visual inspection Assure correct functioning Once per production day
equipment for steel of dosing device
fibres
Control of accuracy Avoid improper fibre On installation
dosage
Periodically
In case of doubt
Materials inspection
Steel fibres Check delivery note Verify that the delivery is in Each delivery
accordance with the order,
and is shipped from the
correct source
Check CE label Verify that the fibres have Each delivery
the correct CE-label which
matches the corresponding
Certificate of Conformity
Visual control, measure Compare the fibre geometry Each delivery
fibre dimensions with the fibres used for ITT
Production process inspection
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
Fibre content-record Record the quantity added Check the content Every batch
Fibre content in the Testing according to Conformity with the target Beginning of each day
fresh concrete EN 14721 and dosage and every
Clause 16.6.5 Verify homogeneous /50 m³ (manual dosing)
distribution of the steel /150 m³ (auto dosing)
fibres in the mix
Concrete mix Visual check Correct mixing with correct Daily
fibre type and even fibre
distribution without balling
Finished product inspection
Steel fibre Check limit of Check performance level of 2 beams every other day
Concrete proportionality, and post- the specification of production
Performance crack flexural strength in
accordance to EN 14651
TABLE 16.7.5
CRITERIA OF ACCEPTANCE FOR STEEL FIBRE DOSAGE
Test control Test control Criteria
Each sample Each partial test 0.80 of the specified target dosage
Average of 3 samples Each test 0.85 of the specified target dosage
from the batch
Continuous control: Continuous control: 0.90 of the specified target dosage
average of >3 tests average of >3 tests
17.1 GENERAL
This Section sets out the material and construction requirements for bridge design.
(d) completely fill the formwork to the intended level, expel entrapped air, and closely
surround all reinforcement, tendons, ducts, anchorages, embedments and fixings; and
(e) provide the specified finish to the formed surfaces of the member.
17.3.4 Finishing of unformed concrete surfaces
Unformed concrete surfaces shall be finished by appropriate methods, to achieve the
specified—
(a) dimensions, falls, tolerances, or similar details relating to the shape and uniformity of
the surfaces;
(b) cover from the surfaces to reinforcement, tendons, ducts and embedments; and
(c) texture of the surface.
17.3.5 Curing and protection of concrete
17.3.5.1 Curing
Concrete shall be cured continuously for a period of time so the design requirements for
strength, serviceability and stripping are satisfied. To satisfy durability, curing requirements
shall be not less than those specified in Clause 4.4.
Curing shall be achieved by the application of water to accelerate the curing of, or the
retention of water in, the freshly cast concrete, and shall commence as soon as practicable
after the finishing of any unformed surfaces has been completed. Where retention of water
in the fresh concrete relies on the application of sprayed membrane-forming curing
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
(ii) in addition to Item (a), the mean compressive strength of the representative
samples taken from the project shall be within the limits specified in AS 1379.
NOTES:
1 ‘Strength grade’ is defined in AS 1379 as ‘the specified value of the characteristic
compressive strength of the concrete at 28 days ( f c )’.
2 The compressive strength of the concrete sampled, tested and assessed in accordance with
AS 1379 indicates the potential strength of the supplied concrete, when placed,
compacted and cured under optimum conditions; the responsibility of demonstrating rests
on the supplier. The achievement of that potential on site is dependent upon the handling,
placing, compacting and curing techniques actually used; the responsibility for which
rests with the construction contractor (see Clauses 17.3.3 and 17.3.5).
17.3.6.3 Concrete specified by parameters other than strength grade
When concrete is specified by parameters other than strength grade, the method of
production control and, if required, project control shall be specified together with the
relevant compliance criteria.
The specified methods of control and assessment shall provide a reliable operating
characteristic curve so that—
(a) concrete with a proportion defective of 0.05 has a probability of acceptance of at least
50%; and
(b) concrete with a proportion defective of 0.30 has a probability of rejection of at least
98%.
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
(iv) For the sawn or machined end of a straight bar intended for use as an end-
bearing splice, the angular deviation from square, measured in relation to the
end 300 mm, shall be within .......................................................................... 2°.
(b) Bending of reinforcement shall comply with Clause 17.4.3.
(c) If required, welding shall comply with AS/NZS 1554.3. Locational tack welding shall
be used only when consumed by final welds compliant with AS/NZS 1554.3.
Welding of stainless steel shall be in accordance with AS/NZS 1554.3 and
AS/NZS 1554.6.
NOTE: Welding of stainless steel reinforcement is not recommended.
17.4.3 Bending
17.4.3.1 General
Reinforcement shall be bent either—
(a) cold, by the application of a force, around a pin of diameter complying with
Clause 17.4.3.2, so as to avoid impact loading of the bar and mechanical damage to
the bar surface; or
(b) hot, provided—
(i) the steel is heated uniformly through and beyond the portion to be bent;
(ii) the temperature of the steel does not exceed 600°C;
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
In addition to the requirements of AS/NZS 2425, sampling and testing, sample size and
frequency of routine testing for bar chairs and spacers shall be as approved by the relevant
authority.
Permeability testing for concrete bar chairs and spacers shall be as approved by the relevant
authority.
Wire used to tie stainless steel reinforcement shall be of stainless steel.
Bar chairs and spacers for stainless steel reinforcement shall not contain carbon steel.
17.4.6 Lightning protection by reinforcement
Where lightning protection is to be provided by the reinforcement, the reinforcement shall
comply with the relevant requirements of AS/NZS 1768.
(c) Prestressing bars shall be within manufacturing tolerances and not bent in the
threaded portion.
Small adjustments on site shall be carried out cold. If the bar temperature is lower than
10°C, the bar temperature shall be raised above this value by means of steam or hot water.
17.5.4.2 Protection
Before stressing, tendons shall be protected from stray current arcing and splashes from the
cutting operation of an oxy-acetylene torch or an arc-welding process.
The threaded ends of prestressing bars shall be provided with suitable protection, at all
times.
If tendons are to have a coating or wrapping, such coating or wrapping shall be inert with
respect to both the steel and the concrete.
After stressing and anchoring, all tendons and anchorages shall be protected from physical
damage and corrosion.
17.5.4.3 Surface condition
The surface condition of tendons shall be such as not to impair bond to the concrete or
grout, or performance in the member.
The presence of surface rust shall not be cause for rejection of ducts under this Clause
unless the steel is visibly pitted.
17.5.4.4 Fixing
All tendons shall be supported and maintained in position within the permissible tolerances
given in Clause 17.7.3 until the concrete has hardened.
17.5.4.5 Tensioning
Tensioning of tendons shall be carried out in a safe manner and in accordance with the
following:
(a) The stressing procedure shall ensure the force in a tendon increases at a uniform time
rate and that the force is transferred gradually to the concrete.
(b) The prestressing force applied to the tendon shall be measured at the jack by
measuring the jack pressure. The prestressing force shall be measured to an accuracy
of 3%.
(c) The tendon extension shall be measured.
(d) A check shall be made for each tendon, on the correlation between the measured
extension and the calculated extension derived from the prestressing force, using the
load-elongation curves for the tendons and assumed friction values for the cable. Any
disparity between the two figures greater than 10% of the calculated extension shall
be investigated.
(e) No stressing shall be carried out when the temperature of the surrounding air is lower
than 0°C.
17.5.4.6 Maximum jacking forces
The maximum force to be applied to a tendon during the stressing operation shall not
exceed—
(a) for pretensioned tendons ............................................................................... 0.80 fpbAp;
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
17.8 FORMWORK
17.8.1 General
The materials, design and construction of formwork shall comply with AS 3610.1.
17.8.2 Stripping of forms and removal of formwork supports
17.8.2.1 General
The stripping of forms and the removal of formwork supports shall comply with the
following:
(a) Forms shall not be stripped or any formwork supports removed until the part of the
member that will be left unsupported has attained sufficient strength to support, with
safety and without detriment to its intended use, its own weight and any
superimposed loads due to concurrent or subsequent construction works.
(b) Removal of formwork supports shall be carried out in a planned sequence so the
concrete structure will not be subject to any unnecessary deformation, impact, or
eccentric loading during the process.
17.8.2.2 Removal of formwork from vertical surfaces
Formwork shall not be removed from vertical surfaces unless the concrete in the member
has achieved sufficient strength to withstand potential damage to its surfaces.
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
APPENDIX A
TESTING OF MEMBERS AND STRUCTURES
(Normative)
A1 GENERAL
This Appendix sets out methods for testing a new structure or a prototype to demonstrate
compliance with the strength and serviceability requirements of this Standard. In addition, a
procedure is set out to demonstrate routine compliance for similar units manufactured
following prototype testing. Methods for testing hardened concrete in place are also
detailed.
All testing shall be undertaken by persons competent, and with appropriate expertise in,
performing such tests.
This Appendix shall not take precedence over AS 5100.7 unless approved by the authority.
NOTES:
1 This Appendix does not apply to testing for compliance of other limit states, such as for fire
or durability.
2 The capacity of an existing structure to carry repeated live loads can also be determined in
accordance with AS 5100.7. For testing of culverts, the capacity may be determined in
accordance with AS 1597.2.
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
A2 TESTING OF MEMBERS
A2.1 Purpose of testing
Structures designed by calculation in accordance with other parts of this Standard are not
required to be tested. Tests may be accepted as an alternative to calculation (prototype
testing), or may become necessary in special circumstances (proof testing), in order to
satisfy the requirements of Clause 2.3 with respect to strength and Clause 2.4 with respect
to serviceability.
Where testing is necessary, elements of structures or whole structures shall be either—
(a) proof-tested in accordance with Paragraph A3, to ascertain the structural
characteristics of an existing member or structure; or
(b) prototype-tested in accordance with Paragraph A4, to ascertain the structural
characteristics of a particular class of member, which are nominally identical to the
elements tested.
A2.2 Test set-up
All measuring equipment shall be chosen and calibrated to suit the range of measurements
anticipated, in order to obtain measurements of the required precision. Care shall be
exercised to ensure that no artificial restraints are applied to the test specimen. All
necessary precautions shall be taken such that in the event of collapse of any part of a
structure being tested, the risk to life is minimized and the collapse will not endanger the
safety of the structure being tested (for tests on members) and/or adjacent structures.
A2.3 Test load
The test load shall simulate 100% of the design loads for the limit states for strength and
serviceability, as appropriate. The test load shall be applied gradually at a rate as uniform as
practicable and without impact. The distribution and duration of forces applied in the test
shall be representative of those forces to which the structure is deemed to be subject under
the requirements of this Standard.
A3 PROOF TESTING
A3.1 Test procedures
A proof test shall be conducted as follows:
(a) Before applying any load, record the original position of the members involved.
(b) Apply the test load as determined from Paragraph A2.3, for the relevant limit state.
(c) Maintain the test load for the necessary period as stated in Paragraph A3.2.
(d) Remove the test load.
A3.2 Criteria for acceptance
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
TABLE A4.3
FACTOR TO ALLOW FOR VARIABILITY
IN PRODUCTION OF UNITS
(b) Acceptance for strength The test prototype shall be deemed to comply with the
requirements for strength if it is able to sustain the strength limit state test load for at
least 5 min without incurring any significant damage, such as spalling or excessive
cracking.
(c) Acceptance for serviceability The test prototype shall be deemed to comply with the
requirement for serviceability if it is able to sustain the serviceability test load for a
minimum period of 1 h without exceeding the serviceability limits appropriate to the
member. Deflection limits shall be determined using Clauses 2.4.2 and 2.4.3, taking
into account only short-term effects.
Qualitative indicators for the parameters affecting strength and serviceability shall be
determined for the expected variability during production. These indicators shall be
routinely monitored and measured in manufactured units and used to ensure the actual
coefficient of variation in production does not exceed the expected coefficient of variation.
Alternatively, manufactured units shall be routinely tested to failure, to determine the
coefficient of variation.
A4.6 Test report
A report shall be prepared in accordance with Paragraph A3.4, except that instead of the
requirement in the final sentence of Paragraph A3.4, the report shall contain a statement as
to whether or not the prototypes tested satisfied the relevant acceptance criteria in
Paragraph A4.5 as appropriate.
A5 QUALITY CONTROL
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
A5.1 General
This Paragraph (A5) applies to the assessment of a group of units that are part of a
production run of similar units. Paragraphs A5.2, A5.3 and A5.4 identify three methods to
routinely assess production. One of these methods shall be nominated by the manufacturer
as the means of demonstrating that the manufactured group is similar to the tested
prototypes. The nominal routine examination shall include the determination of the
variability in a production run by relating key indicators in the sample to the previously
performed prototype testing and the application of a test load to each sample, as
appropriate.
A5.2 Statistical sampling
A sampling plan, in accordance with AS 1199.1, shall be established for the routine
inspection and testing of a produced batch. Sampling shall be undertaken in accordance
with this plan and the selected specimens shall be routinely tested to ensure compliance
with this Appendix is maintained.
For concrete specified by strength, the methods of production and assessment, taken
together, shall provide a reliable operating characteristic curve so that—
(a) concrete with a proportion defective of 0.05 has a probability of acceptance of not
less than 50%; and
(b) concrete with proportion defective of 0.30 has a probability of rejection of not less
than 98%.
A5.3 Product certification
To ascertain whether a production run or application routinely complies with the
requirements of this Appendix, independent assurance of the claim by a manufacturer or
contractor of batch consistency shall be permitted.
NOTE: The certification should meet the criteria described in ISO/IEC TR 17026 in order that
effective quality planning to control production is achieved.
by coring or sawing.
A6.3 Non-destructive testing
Non-destructive testing (including impact or rebound hammer, ultrasonic pulse velocity,
pull-out and abrasion testing, or a combination of techniques) may be used to compare the
properties of concrete under investigation with that of a representative sample of known
quality. In particular, comparable concrete should be of similar maturity, curing history and
mix composition. Alternatively, where approved by the authority, values obtained by non-
destructive tests may be used directly to assess some properties of concrete.
The method of testing and assessment shall be specified and carried out in accordance with
internationally recognized procedures.
NOTE: Combined non-destructive techniques have been found to substantially improve the order
of accuracy of the estimated values compared with those obtained from testing by a single
method.
A6.4 Tests on samples taken from the structure
A6.4.1 Test requirements
Taking and testing of cores and beams from members and sample panels shall comply with
the following:
(a) Core and beam locations shall be selected so as to minimize any consequent reduction
of strength, durability and performance of the structure.
(b) The cores and beams shall be representative of the whole of the concrete concerned
and in no case shall less than three samples be tested.
(c) Cores and beams shall be examined visually before and after testing, to assess the
proportion and nature of any voids, cracks and inclusions present. These factors shall
be considered in the interpretation of the test results.
(d) Cores shall be taken and tested for compressive strength in accordance with
AS 1012.14 and beams shall be taken in accordance with ASTM C42. The beams
shall be tested for flexural strength in accordance with AS 1012.11, and shall be
tested dry unless the concrete concerned will be more than superficially wet in
service. The density of cores and beams shall be determined in accordance with
AS 1012.12, in the same condition as applicable to testing for compressive strength
using AS 1012.1 or AS 1012.2 by sealing or wrapping samples where appropriate.
A6.4.2 Interpretation of results
The strength of the concrete in the member shall be estimated—
(a) as 1.15 times the average strength of the cores and beams; or
(b) by using test data from cores or beams taken from another member for which the
strength of the concrete is known.
Inter l o c k in g bar s
S p ir al
r e i nfor c e m e nt
APPENDIX B
BEAM STABILITY DURING ERECTION
(Normative)
A beam being lifted either by vertical or inclined slings may collapse or be damaged by
excessive cracking due to tilting of the beam about a longitudinal axis through the lifting
points. This initial tilting may be initiated by imperfections in the beam geometry and in the
eccentric location of the lifting points.
The stability of a prestressed beam lifted at or near the ends by vertical slings, which allow
rotation about the longitudinal axis through the lifting points (see Figure B1), shall be
determined as follows:
(a) Calculate the factor of safety against lateral buckling (ψr) as follows:
eo
r . . . B1
0.64 h
where
eo = vertical eccentricity between the centre of gravity of a beam and the
longitudinal axis through the lifting points
= yt 0.67Δv . . . B2
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
y e x Ec c e ntr i c it y
www.standards.org.au
of lif t in g p o int
A e o = d y. s u p - 0.67Δ v
Lif t ing Lif t ing Lif t ing
p o int p o int p o int
d y. s u p
βv
Datum line
x Centre of grav it y
of beam in elevation Δv
207
A
x M aj or
axis ELE VATIO N Lif t ing
Lif t ing p o int
p o int
ex e x + 0.67 Δ h Δh
Datum line
CL of b eam
M i n or a x i s
y
C e ntre of gr av it y of
SECTIO N A-A beam in plan
PL AN
Standards Australia
AS 5100.5:2017
AS 5100.5:2017 208
APPENDIX C
DESIGN OF SEGMENTAL CONCRETE BRIDGES
(Normative)
C1 ANALYSIS
C1.1 Longitudinal analysis
Longitudinal analysis of segmental concrete bridges shall consider a specific construction
method and construction schedule, as well as the time-related effects of concrete creep,
shrinkage and prestress losses.
The effects of secondary moments due to prestress shall be included in stress calculations at
serviceability limit states. In calculating flexural and shear resistance requirements at the
strength ultimate limit states, the secondary moments or shears induced by prestress (with a
load factor of 1.0) shall be added to the moments and shears due to factored dead and live
loads.
C1.2 Transverse analysis
Consideration shall be given to the increase in web shear, transverse web flexure and other
effects on the cross-section resulting from eccentric loading or asymmetry of the structural
geometry.
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
C2 LOADS
C2.1 Erection loads
Erection loads comprise all loadings arising from the anticipated system of temporary
supporting works or special erection equipment, or both, to be used in accordance with the
assumed construction sequence and schedule. The assumed erection loads and acceptable
closure forces due to misalignment corrections shall be stated on the drawings. Allowance
shall be made for all effects of changes to the statical structural scheme during construction
and the application, changes or removal of the assumed temporary supports and special
equipment, taking into account residual ‘built-in’ forces, moments, deformations, secondary
post-tensioning effects, creep, shrinkage and any other strain-induced effects.
C2.2 Post-tensioning force
The structure shall be designed for both the initial and final post-tensioning forces. For
determining the final post-tensioning forces, prestress losses shall be calculated for the
proposed construction schedule stated on the plans. The final post-tensioning forces used in
serviceability limit state stress calculations shall be based on the most severe condition at
each location along the structure.
C3 SHEAR AT JOINTS
Interfaces between elements such as webs and flanges, between dissimilar materials,
between concretes cast at different times or at an existing or potential major crack shall be
designed for shear transfer in accordance with Clause 8.4.
Shear keys in webs of precast segmental bridges shall extend for as much of the web height
as is compatible with other detailing requirements. Alignment shear keys shall be provided
in top and bottom flanges.
The ultimate shear strength (Vu ) for structures utilizing dry joints shall equal the nominal
shear resistance (Vuj) at the joint and shall be calculated as follows:
A
Vuj 1.875 Ak f ct 1 0.205 cp p 0.45 Asm cp . . . C3
Ag
where
Ak = area of the base of all the keys in the failure plane, in millimetres square
f ct = principal tensile strength of the concrete
σcp = average intensity of effective prestress in concrete
Asm = area of contact between smooth surfaces on the failure plane, in millimetres
square
C5 SPECIAL PROVISIONS
C5.1 Precast segmental construction
C5.1.1 Age of segments at erection
To limit construction deflections to values consistent with design calculations, precast
segments shall be a minimum of 14 days old at the time of erection unless earlier erection is
specifically approved.
C5.1.2 Temporary stress on epoxy joints
A minimum compressive stress of 0.28 MPa shall be provided for the closure stress on an
epoxied joint until the epoxy has set.
C5.1.3 Dry joints
Dry joints shall not be used—
(a) for bridges with internal tendons; or
(b) in conjunction with external post-tensioning tendons in areas with exposure
classification B2 or C, or where freeze/thaw cycles occur.
C5.1.4 External tendons
At least three levels of corrosion protection of post-tensioning tendons shall be provided.
A waterproof membrane shall be provided on externally post-tensioned bridge
superstructures.
The bridge shall be detailed to allow for the inspection and replacement of external
prestressing tendons.
tolerances in the bearing levels, temporary bearing pad thickness, deck soffit profile and the
like. This requirement shall also apply to the casting bay and temporary piers.
C6 SPECIFICATIONS
The method of construction shall be taken into consideration when designing the permanent
works. Assumptions used in the design of the permanent works pertaining to the method of
construction shall be included in the drawings or specification. Tolerances shall be provided
regarding the construction equipment weights and variations in material properties to be
used.
Allowances shall be shown for variations in construction loads and construction stages. The
resultant camber information shall be given such that development of casting curves can be
achieved.
APPENDIX D
STANDARD PRECAST PRESTRESSED CONCRETE GIRDER
(Informative)
D1 GENERAL
The standard sections for precast, prestressed concrete bridge girders shown in
Figure D1(A) for I-girders and in Figure D1(B) for Super T-girders, have been adopted. For
the Super T-girder sections, the size of the internal void has not been detailed.
In addition, Figure D1(C) shows the earlier dimensions of Super T-girders used up until
mid-2001 when the width of the bottom flange was increased to enable the addition of a
deeper section to a common mould shape.
NOTE: Cover in excess of 25 mm required for durability may require increased width of the webs
of standard sections.
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
350
20 0
40
10 0
10 0 10 0
C e nt r o i d a l 15 0
120
axis
420 900 450
75 0
Yb
15 0
10 0
10 0
90
300
450
T YPE 1 T YPE 2
G ir d er Ag Z y. s u p Z y. s u p I d y. s u b H y p ot h et i c a l t h i c k n e s s, t h
type (m m 2 ) (m m 3 ) (m m 3 ) (m m 4) (m m) (g ir d er s o nly)(m m)
1 126 x 10 3 17.9 x 10 6 2 2.0 x 10 6 74 0 0 x 10 6 3 37 120
2 218 x 10 3 41.1 x 10 6 4 8.1 x 10 6 19 9 5 0 x 10 6 415 15 5
3 317 x 10 3 8 2.9 x 10 6 91.1 x 10 6 4 9 9 0 0 x 10 6 548 18 0
4 4 4 3 x 10 3 13 5.9 x 10 6 16 8.6 x 10 6 10 5 3 3 0 x 10 6 6 25 20 5
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
500
450
15 0
13 0
175
15 0
15 0 15 0
545 650
115 0 14 0 0
175
25 0
15 0
175
500
650
T YPE 3 T YPE 4
DIMENSIONS IN MILLIMETRES
A 10 27 A
10 27 75 m in.*
A A
75 m in.*
10 0 x 75
13 x 13 fillet (t y p)
* 10 0 x 75 c hamfer * 10 0 0
13 x 13 fillet (t y p) 75 0
c hamfer
= = tb 426 426 tb
899 N o m i n a l 10 r ad i u s 8 52 N o m i n a l 10 r ad i u s
or 13 x 13 c hamfer or 13 x 13 c hamfer
(a) Ty p e T1 - 2 (b) Ty p e T2 - 2
A 10 27 A
75 m in.*
A 10 27 A
75 m in.*
10 0 x 75
13 x 13 fillet (t y p)
c hamfer
10 0 x 75 *
13 x 13 fillet (t y p) 15 0 0
c hamfer
* 120 0
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
4 07 4 07 tb tb
814 N o m i n a l 10 r ad i u s 757 N o m i n a l 10 r ad i u s
or 13 x 13 c hamfer or 13 x 13 c hamfer
(c) Ty p e T3 - 2 (d) Ty p e T4 - 2
A 10 27 A
75 m in.*
10. 5 5 6
1
5.3 47
10 0 x 75 To p s l o p e of
13 x 13 fillet (t y p) b ot to m fl an g e
c hamfer 1
* We b s l o p e
18 0 0 25 x 25
re c e s s 25
25
70 0 N o m i n a l 10 r ad i u s LEGEN D:
or 13 x 13 c hamfer = D e n ote s d im e n s i o n ha s to b e in c rea se d
if fl an g e t hi c k n e s s > 75
(e) Ty p e T5 - 2 * = D e n ote s d i m e n s i o n s var i e s
DIMENSIONS IN MILLIMETRES
A 9 20 A
75 m in.*
A 9 20 A
75 m in.*
*
10 0 x 75
fillet (t y p)
* 10 0 0
10 0 x 75
75 0
fillet (t y p)
79 2 N o m i n a l 10 r ad i u s 74 4 N o m i n a l 10 r ad i u s
or 12 x 12 c hamfer or 12 x 12 c hamfer
(a) Ty p e T1 - 1 (b) Ty p e T2 - 1
A 9 20 A
75 m in.*
A 9 20 A
75 m in.*
*
10 0 x 75
fillet (t y p)
*
10 0 x 75
fillet (t y p) 15 0 0
120 0
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
353 353 tb 3 25 3 25 tb
70 6 N o m i n a l 10 r ad i u s 650 N o m i n a l 10 r ad i u s
or 12 x 12 c hamfer or 12 x 12 c hamfer
(c) Ty p e T3 - 1 (d) Ty p e T4 - 1
25 x 25
re c e s s 25
10. 5 5 6
1 25
5.0 0 0
1
To p s l o p e of We b s l o p e Detail A
b ot to m fl an g e
LEGEN D:
= D e n ote s d i m e n s i o n h a s to b e i n c r e a s e d
if fl an g e t hi c k n e s s > 75
* = D e n ote s d i m e n s i o n s var i e s
DIMENSIONS IN MILLIMETRES
TABLE D2
END BLOCK DIMENSIONS FOR POST-TENSIONED I-GIRDERS
Girder type End block length End block width Taper length
(see Note)
mm mm mm mm
1 750 200 70
2 900 350 170
3 1 150 450 260
4 1 400 500 300
NOTE: The taper length is the length of the tapered section between the end block and
the web of the beam.
D3 FLEXURAL PROPERTIES
Flexural moduli about the major axis of bending for standard precast prestressed concrete
I-girder sections are given in Table D3(A).
Flexural moduli about the major axis of bending are also given for a typical range of Super
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
T-girder sections that conform to the standard sections shown in Figure D1(B), with the
following dimensions:
(a) Width of webs: 100 mm (for girder types 1 to 4).
120 mm (for girder type 5).
(b) Thickness of top flange: 75 mm.
(c) Width of top flange: 2100 mm.
(d) Thickness of bottom Dimension tb [see Table D3(B)].
flange at centre-line:
Flexural moduli for the open top flange case in Figure D1(B) are given Table D3(B).
TABLE D3(A)
FLEXURAL MODULUS—PRECAST CONCRETE I-GIRDERS
Girder Ag Zt Zb I yb th
type (girders only)
mm 2 10 3 mm 3 10 6 mm 3 10 6 mm 4 10 6 mm mm
1 125 17.9 22.0 7 400 337 120
2 218 41.1 48.1 19 950 415 155
3 317 82.9 91.1 49 900 548 180
4 443 135.9 158.5 105 330 625 205
where
A g = gross sectional area of the member
Z t = section modulus about the centroidal axis at the top of an uncracked cross-section
Z b = section modulus about the centroidal axis at the bottom of an uncracked cross-section
I = second moment of area of the uncracked concrete cross-section
y b = depth from the centroidal axis to the extreme fibre at the bottom of the section
th = hypothetical thickness of the member
TABLE D3(B)
FLEXURAL MODULUS—PRECAST CONCRETE SUPER T-GIRDERS—
OPEN TOP FLANGE CASE
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
Girder tb Ag Zt Zb I yb th
type (girders only)
mm mm 2 10 3 mm 3 10 6 mm 3 10 6 mm 4 10 6 mm mm
T1-2 240 436.0 67.4 84.4 28 100 323 139
T2-2 240 472.1 104.6 132.1 58 390 442 131
T3-2 260 514.0 137.8 174.7 92 450 529 130
T4-2 260 555.8 193.0 234.8 158 860 677 124
T5-2 325 691.9 275.3 323.6 267 740 827 139
D4 TORSIONAL PROPERTIES
Torsional moduli (Jtb) of the standard precast prestressed concrete I-girder sections,
together with torsional moduli (Jtn) of the I-girder sections with a composite slab connected
above, taking into account the difference in elastic moduli of the girder and slab concretes,
as shown in Figure D4(A), are given in Table D4(A).
Torsional moduli are given for typical Super T-girder sections that conform to the standard
sections shown in Figure D1(B), with the following dimensions:
(a) Width of webs: 100 mm (for girder types 1 to 4).
120 mm (for girder type 5).
(b) Thickness of top flange: 75 mm.
(c) Width of top flange: 2100 mm.
(d) Thickness of bottom Dimension tb [see Table D3(B)].
flange at centre-line:
Torsional moduli (Jtb) of the standard precast prestressed concrete Super T-girder sections,
together with torsional moduli (Jtn) of the Super T-girder sections with a composite slab
connected above, taking into account the difference in elastic moduli of the girder and slab
concretes, shown in Figures D4(B)(1) and D4(B)(2), are given in Table D4(B)(1) for the
open top flange case and in Table D4(B)(2) for the closed top flange case.
For the application of the torsional moduli, the following considerations apply:
(i) Torsional moduli, given in Tables D4(A), D4(B)(1) and D4(B)(2) are based on elastic
theory and are equivalent to the Saint Venant’s torsional constants.
(ii) The value of torsional modulus (Jtn) for a composite section is the torsional modulus
for the girder plus the slab together with the junction effect between the girder and
the cast-in-place slab.
NOTE: The contribution to Jtn from the cast-in-place deck slab is reduced to one half of the
full amount because the continuity of the slab removes the effect of the vertical shear stresses
that would otherwise be present at the free ends of the slab.
(iii) Values of Jtn are given for modular ratios of 0.70 and 1.00 where αc is the modular
ratio factor of the cast-in-place concrete to the precast beam concrete in the
composite member. Intermediate values may be interpolated.
(iv) The width (bs) is the width of the flange in a composite member.
(v) The full torsional moduli are suitable for determining distribution of forces at applied
loads only, that is, while the section is uncracked. At ultimate load, considerable
reduction in the torsional stiffness may occur and the effect of using a torsional
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
modulus equal to 20% of the full value should be taken into consideration.
bs
ds
Ca st- in - p l ac e s l a b
S t an d ar d pre c a st
p r e s t r e s s e d I - g ir d er
TABLE D4(A)
TORSIONAL MODULI (J tb) AND (J tn) FOR SECTIONS USING STANDARD
PRECAST PRESTRESSED CONCRETE I-GIRDERS
Torsional modulus
mm 4 10 6
Girder For girders in composite section, J tn
type For girder
only, d s = 150 mm d s = 175 mm d s = 200 mm
J tb
α c = 0.70 α c = 1.00 α c = 0.70 α c = 1.00 α c = 0.70 α c = 1.00
1 800 1 100 1 200 1 200 1 300 1 300 1 400
2 2 400 3 500 3 800 3 800 4 100 4 100 4 500
3 5 000 7 100 7 700 7 700 8 300 8 200 9 000
4 10 000 13 000 14 000 14 000 15 000 15 000 16 000
S t a n d ar d p r e c a s t p r e s t r e s s e d
o p e n fl an g e Su p er T- g ir d er
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
bs
ds
Ca st- in - p l ac e s l a b
S t a n d ar d p r e c a s t p r e s t r e s s e d
o p e n fl an g e Su p er T- g ir d er
S t a n d ar d p r e c a s t p r e s t r e s s e d
c l o se d fl an g e Su p er T- g ir d er
bs
ds
Ca st- in - p l ac e s l a b
S t a n d ar d p r e c a s t p r e s t r e s s e d
c l o se d fl an g e Su p er T- g ir d er
TABLE D4(B)(1)
TORSIONAL MODULI (J tb) AND (J tn) FOR SECTIONS USING OPEN TOP
FLANGE STANDARD PRECAST PRESTRESSED CONCRETE SUPER T-GIRDERS
Torsional modulus
mm 4 10 6
Girder For For girders in composite section, J tn
type tb girder
d s = 150 mm d s = 175 mm d s = 200 mm
mm only,
J tb α c = 0.70 α c = 1.00 α c = 0.70 α c = 1.00 α c = 0.70 α c = 1.00
1 240 6 300 66 000 75 000 69 000 80 000 73 000 86 000
2 240 6 100 103 000 116 000 108 000 123 000 113 000 130 000
3 260 6 900 136 000 151 000 142 000 160 000 148 000 169 000
4 260 6 400 181 000 200 000 188 000 210 000 195 000 221 000
5 325 9 900 244 000 265 000 252 000 278 000 261 000 290 000
TABLE D4(B)(2)
TORSIONAL MODULI (J tb) AND (J tn) FOR SECTIONS USING CLOSED TOP
FLANGE STANDARD PRECAST PRESTRESSED CONCRETE SUPER T-GIRDERS
Torsional modulus
mm 4 10 6
Girder For For girders in composite section, J tn
type tb girder
d s = 150 mm d s = 175 mm d s = 200 mm
mm only,
J tb α c = 0.70 α c = 1.00 α c = 0.70 α c = 1.00 α c = 0.70 α c = 1.00
1 240 49 000 67 000 76 000 70 000 81 000 74 000 87 000
2 240 83 000 109 000 121 000 114 000 128 000 119 000 136 000
3 260 114 000 145 000 160 000 151 000 169 000 157 000 177 000
4 260 156 000 196 000 214 000 203 000 225 000 210 000 235 000
5 325 215 000 261 000 282 000 269 000 294 000 278 000 306 000
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
BIBLIOGRAPHY
AS
1012 Methods of testing concrete
1012.21 Method 21: Determination of water absorption and apparent volume of
permeable voids in hardened concrete
1141 Methods for sampling and testing aggregate
1141.60.1 Method 60.1: Potential alkali-silica reactivity—Accelerated mortar bar
method
1141.60.2 Method 60.2: Potential alkali-silica reactivity—Concrete prism method
1597 Precast reinforced concrete box culverts
1597.2 Part 2: Large culverts (exceeding 1200 mm span or 1200 mm height and
up to and including 4200 mm span and 4200 mm height
3735 Concrete structures retaining liquids
3735 Supp 1 Concrete structures retaining liquids (Supplement to AS 3735—2001)
3972 General purpose and blended cements
AS/NZS
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
AS 5100.5:2017
222
NOTES
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
223
NOTES
AS 5100.5:2017
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
AS 5100.5:2017
224
NOTES
Standards Australia
Standards Australia develops Australian Standards® and other documents of public benefit and national interest.
These Standards are developed through an open process of consultation and consensus, in which all interested
parties are invited to participate. Through a Memorandum of Understanding with the Commonwealth Government,
Standards Australia is recognized as Australia’s peak non-government national standards body.
Australian Standards®
Committees of experts from industry, governments, consumers and other relevant sectors prepare Australian
Standards. The requirements or recommendations contained in published Standards are a consensus of the views
of representative interests and also take account of comments received from other sources. They reflect the latest
Accessed by GRIFFITH UNIVERSITY LIBRARY on 11 Jun 2018 (Document currency not guaranteed when printed)
scientific and industry experience. Australian Standards are kept under continuous review after publication and are
updated regularly to take account of changing technology.
International Involvement
Standards Australia is responsible for ensuring the Australian viewpoint is considered in the formulation of
International Standards and that the latest international experience is incorporated in national Standards. This role is
vital in assisting local industry to compete in international markets. Standards Australia represents Australia at both
the International Organization for Standardization (ISO) and the International Electrotechnical Commission (IEC).