Professional Documents
Culture Documents
1
Contents
ANSWER Q1 .................................................................................................................................................. 2
ANSWER Q 2.................................................................................................................................................. 4
ANSWER Q3 .................................................................................................................................................. 6
ANSWER Q4 .................................................................................................................................................. 7
Answer Q5................................................................................................................................................... 11
Answer Q 6 .................................................................................................................................................. 14
ANSWER Q 7................................................................................................................................................ 18
ANSWER Q1
GIVEN
𝒅𝒄𝟏
𝒅𝒑𝟏
=IFC1=30+0.12P1 RS/MWh 30≤P1≤150MW
𝒅𝒄𝟐
=IFC2=40+0.20P2 RS/MWh 20≤P2≤100 MW
𝒅𝒑𝟐
𝒅𝒄𝟑
=IFC3=10+0.16P3 RS/MWh 50≤P3≤250 MW
𝒅𝒑𝟑
2
And also the total load of the system is:
PD=P1+P2+P3=310
19.58λ=822.3
λ=41.9969 RS/MWh
These values satisfy the load demand of 310 MW but not the individual power limits of
each plant. P2<P2min.therefore P2 is set at the min. value of 20MW.
Then P1+P3=310-20=290MW. This power has to be scheduled between unit 1 and unit 3.
Hence:
30+0.12P1=λ 10+0.16P3=λ
( λ -30)/0.12 + (λ-10)/0.16=290
λ =41.31438
= (41.31438-30)/0.12 = (41.31438-10)/0.16
P1 =94.2865MW P3 =195.714875MW
These values satisfy both the load demand of 310 MW and the individual power limits of
each plant.
3
ANSWER Q 2
Given
df1/dp1=IFR1=0.000284P1+7.2
df2/dp2=IFR2=0.00388P2+7.33
df3/dp3=IFR3=0.00964P3+7.97
Second we should calculate IFC(Incremental fuel cost) using the formula below
P1+P2+P3=850MW equation 1
From equation 2:
4
P1=1.82P2+305.48
P2=2.48P3+30.93
=850-4.5P3-56.3+305.48-2.4893+30.93
7.98P3=1130
P3=141.6
P2=2.48P3+30.93=2.48(141.6) +30.93=382.1
P2=382.1
P1=1.82P2+305.48=1.82(382.1) +305.48=998.9
P1=998.9
P2+P3=250, 2.4P3+30.93+P3=250
P3=62.95MW P2=187.046MW
5
ANSWER Q3
Using the equal incremental cost rule:
6
ANSWER Q4
𝒅𝒄𝟏
=IFC1=5.3+0.008P1 $/MWh 200≤P1≤450MW
𝒅𝒑𝟏
𝒅𝒄𝟐
=IFC2=5.5+0.012P2 $/MWh 150≤P2≤350 MW
𝒅𝒑𝟐
𝒅𝒄𝟑
=IFC3=5.8+0.018P3 $/MWh 100≤P3≤225 MW
𝒅𝒑𝟑
7
P1= (λ-5.3)/0.008 P2= (λ-5.5)/0.012 P3= (λ-5.8)/ 0.018
And also P1+P2+P3=750
From this (λ-5.3)/0.008 + (λ-5.5)/0.012 + (λ-5.8)/ 0.018 =750
λ =8.31 $/MWh
Substituting for λ
At P1 P1= (λ-5.3)/0.008
P1= (8.31-5.3)/0.008
P1 =376.3MW
At P2 P2= (λ-5.5)/0.012
P2= (8.31-5.5)/0.012
P2= 234.17MW
At P3 P3= (λ-5.8)/ 0.018
P3= (8.31-5.8)/ 0.018
P3= 139.44MW
Then to find the total cost CT=c1 (p1) +c2 (p2) +c3 (p3)
P1 at C1 C1=450+5.3(376.3) +0.004(376.3)2
C1=3010.8 $/h
C2=350+5.5(234.17) +0.006(234.17)2
c2=1966.95$/h
P3 at P3 c3=150+5.8(139.44)0.009(139.44)2
C3=1133.74$/h
CT=c1 (p1) +c2 (p2) +c3 (p3)
=3010.8 $/h+1966.95$/h+1133.74$/
CT
Then the total cost per hour is C =6111.5$/h
T
Then
𝟕𝟓𝟎
B) For equal sharing 𝑷𝟏 = 𝑷𝟐 = 𝑷 𝟑 = = 𝟐𝟓𝟎 𝑴𝑾
𝟑
Then 𝑪𝑻 = 𝑪𝟏(𝒑𝟏) + 𝑪𝟐(𝒑𝟐) + 𝑪𝟑(𝒑𝟑)
8
𝑪𝟏 = 𝟐𝟎𝟐𝟓 $/𝒉
𝑪𝟐 = 𝟑𝟓𝟎 + 𝟓. 𝟓(𝟐𝟓𝟎) + 𝟎. 𝟎𝟎𝟔(𝟐𝟓𝟎)𝟐
𝑪𝟐 = 𝟐𝟏𝟎𝟎 $/𝒉
𝑪𝟑 = 𝟏𝟓𝟎 + 𝟓. 𝟖(𝟐𝟓𝟎) + 𝟎. 𝟎𝟎𝟗(𝟐𝟓𝟎)𝟐
𝑪𝟑 = 𝟐𝟏𝟔𝟐. 𝟓 $/𝒉
C)
𝒅𝒄𝟏
=IFC1=5.3+0.008P1 $/MWh 200≤P1≤450MW
𝒅𝒑𝟏
𝒅𝒄𝟐
=IFC2=5.5+0.012P2 $/MWh 150≤P2≤350 MW
𝒅𝒑𝟐
𝒅𝒄𝟑
=IFC3=5.8+0.018P3 $/MWh 100≤P3≤225 MW
𝒅𝒑𝟑
Substituting for 𝛌
9
For 𝑷𝟏
𝟖.𝟗𝟕−𝟓.𝟑
𝑷𝟏 =
𝟎.𝟎𝟎𝟖
𝑷𝟏 = 𝟒𝟓𝟖. 𝟕𝟓𝑴𝑾
For 𝑷𝟐
𝟖. 𝟗𝟕 − 𝟓. 𝟓
𝑷𝟐 =
𝟎. 𝟎𝟏𝟐
𝑷𝟐 = 𝟐𝟖𝟗. 𝟏𝟕𝑴𝑾
For 𝑷𝟑
𝟖. 𝟗𝟕 − 𝟓. 𝟖
=
𝟎. 𝟎𝟏𝟖
𝑷𝟑 = 𝟏𝟕𝟔. 𝟏𝟏𝑴𝑾
Thus 𝑷𝟏 > 𝑷𝒎𝒂𝒙𝟏 (𝒊. 𝒆 𝒐𝒇 𝟐𝟎𝟎 ≤ 𝑷𝟏 ≤ 𝟒𝟓𝟎 𝑴𝑾) and𝑷𝟐 , 𝑷𝟑 are within the limits. In
such cases for optimal operation we set 𝑷𝟏 = 𝑷𝒎𝒂𝒙 𝟏 = 𝟒𝟓𝟎 𝑴𝑾 and hence the total
load to be shared only between the unit 2 and unit 3 is:
𝟗𝟐𝟓 𝑴𝑾 − 𝟒𝟓𝟎 𝑴𝑾 = 𝟒𝟕𝟓 𝑴𝑾
Now, for optimal operation,𝑰𝑪𝟐 = 𝑰𝑪𝟑 𝒊. 𝒆. , 𝟓. 𝟓 + 𝟎. 𝟎𝟏𝟐𝑷𝟐 = 𝟓. 𝟖 +
𝟎. 𝟎𝟏𝟖𝑷𝟑 𝒂𝒏𝒅 𝑷𝟐 + 𝑷𝟑 = 𝟒𝟕𝟓
P2= (λ-5.5)/0.012 P3= (λ-5.8)/ 0.018
And also P2+P3=475
(λ -5.5)/0.012 + (λ-5.8)/ 0.018=475
λ = 𝟗. 𝟎𝟒 $/𝑴𝑾𝒉
10
$
𝑪𝟐 = 𝟐𝟒𝟗𝟒. 𝟔𝟓
𝒉
𝑪𝟑 = 𝟏𝟓𝟎 + 𝟓. 𝟖(𝟏𝟖𝟎) + 𝟎. 𝟎𝟎𝟗(𝟏𝟖𝟎)𝟐
𝑪𝟑 = 𝟏𝟒𝟖𝟓. 𝟔 $/𝒉
𝑪𝑻 = 𝟐𝟖𝟑𝟓 $/𝒉 + 𝟐𝟒𝟗𝟒. 𝟔𝟓 $/𝒉 + 𝟏𝟒𝟖𝟓. 𝟔 $/𝒉
𝑪𝑻 = 𝟕𝟔𝟐𝟓. 𝟐𝟓 $/𝒉
Answer Q5
𝒅𝒄𝟏
=0.016p1+7:
𝒅𝒑𝟏
𝒅𝒄𝟐
=0.018p2+6.3:
𝒅𝒑𝟐
11
𝒅𝒄𝟑
=0.014p3+6.8:
𝒅𝒑𝟑
Equation 1:
0.016p1+7+ 𝛌 (0.00042p1) =λ
0.018p2+6.3+ 𝛌(0.000456p2) =λ
0.014p3+6.8+ 𝛌(0.000358p3) =λ
Given: Assume that take starting values of P1=40, P2=60 and P3=50.
𝝏𝑷𝒍𝒐𝒔𝒔
=0.00042p1=0.00042*40=0.0168
𝝏𝑷𝟏
𝝏𝑷𝒍𝒐𝒔𝒔
=0.000456p2=0.000456*60=0.02736
𝝏𝑷𝟐
𝝏𝑷𝒍𝒐𝒔𝒔
=0.000358p3=0.000358*50=0.0179
𝝏𝑷𝟑
By substituting in to equation 2:
(𝟎.𝟗𝟖𝟑𝟐𝛌−𝟕) (𝟎.𝟗𝟕𝟐𝟔𝟒𝛌−𝟔.𝟑) (𝟎.𝟗𝟖𝟐𝟏𝟏𝛌−𝟔.𝟖)
+ + =151.6171
𝟎.𝟎𝟏𝟔 𝟎.𝟎𝟏𝟖 𝟎.𝟎𝟏𝟒
Since the values obtained are found to be near from start values assumed, no
need for the second iteration to proceed with this new values of generations.
13
Answer Q 6
a)
For Optimal operation the IFC is calculated by differential equation as follows:
𝒅𝒄𝟏
=IFC1=40+0.54P1 birr/Mhr 25≤P1≤100MW
𝒅𝒑𝟏
𝒅𝒄𝟐
=IFC2=30+0.5P2 birr/Mhr 25≤P2≤100MW
𝒅𝒑𝟐
𝒅𝒄𝟑
=IFC3=35+0.7P3 birr/Mhr 25≤P3≤100MW
𝒅𝒑𝟑
14
Substituting for 𝛌
For 𝑷𝟏
P1= (λ-40)/0.54
P1= (85.99998-40)/0.54
P1=85.212MW
For 𝑷𝟐
P2= (λ-30)/0.5
P2= (85.99998-30)/0.5
P2=112.03MW
For 𝑷𝟑
P3= (λ-35)/0.7
P3= (85.99998-35)/0.7
P3=72.756MW
Thus 𝑷𝟐 > 𝑷𝒎𝒂𝒙𝟐 (𝒊. 𝒆 𝒐𝒇 𝟐𝟓 ≤ 𝑷𝟐 ≤ 𝟏𝟎𝟎 𝑴𝑾) and𝑷𝟏 , 𝑷𝟑 are within the limits. In
such cases for optimal operation we set 𝑷𝟐 = 𝑷𝒎𝒂𝒙
𝟐 = 𝟏𝟎𝟎 𝑴𝑾 and hence the total
load to be shared only between the unit 1 and unit 3 is:
𝟐𝟕𝟎 𝑴𝑾 − 𝟏𝟎𝟎 𝑴𝑾 = 𝟏𝟕𝟎 𝑴𝑾
Now, for optimal operation 𝑰𝒇𝑪𝟏 = 𝑰𝒇𝑪𝟑 40+0.54P1=35+0.7P3
And also P1+P3=170
(λ -40)/0.54+ (λ-35)/0.7=170
λ= 𝟖𝟗. 𝟔𝟓𝟕 𝑩𝑰𝑹𝑹/𝑴𝑾𝒉
Total cost 𝑪𝑻 = 𝑪𝟏 + 𝑪𝟐 + 𝑪𝟑
15
𝑪𝟏 = 𝟏𝟐𝟎 + 𝟒𝟎(𝟗𝟐. 𝟎𝟎𝟏) + 𝟎. 𝟐𝟕(𝟗𝟐. 𝟎𝟎𝟏)𝟐
𝑪𝟏 = 𝟔𝟎𝟖𝟓. 𝟑𝟔𝟗𝟔𝟖 𝒃𝒊𝒓𝒓/𝒉
𝑪𝟐 = 𝟏𝟓𝟎 + 𝟑𝟎(𝟏𝟎𝟎) + 𝟎. 𝟐𝟓(𝟏𝟎𝟎)𝟐
C2=5650 birr/h
𝑪𝟑 = 𝟏𝟒𝟎 + 𝟎. 𝟑𝟓(𝟕𝟕. 𝟗𝟖𝟒) + 𝟎. 𝟑𝟓(𝟕𝟕. 𝟗𝟖𝟒)𝟐
𝑪𝟑 = 𝟒𝟗𝟗𝟕. 𝟗𝟔𝟔𝟓 𝒃𝒊𝒓𝒓/𝒉
𝑪𝑻 = 𝟔𝟎𝟖𝟓. 𝟑𝟔𝟗𝟔𝟖𝒃𝒊𝒓𝒓/𝒉 + 5650 birr/h+𝟒𝟗𝟗𝟕. 𝟗𝟔𝟔𝟓 𝒃𝒊𝒓𝒓/𝒉
𝑪𝑻 = 𝟏𝟔𝟕𝟑𝟑. 𝟑𝟑𝟔𝟏𝟕 𝒃𝒊𝒓𝒓/𝒉
b)
When there is equal sharing between the units:
P1+P2+P3=270/3=90
Then the total cost is:
𝑪𝑻 = 𝑪𝟏 + 𝑪𝟐 + 𝑪𝟑
𝑪𝟏 = 𝟏𝟐𝟎 + 𝟒𝟎(𝟗𝟎) + 𝟎. 𝟐𝟕(𝟗𝟎)𝟐
𝑪𝟏 = 𝟓𝟗𝟎𝟕𝒃𝒊𝒓𝒓/𝒉
𝑪𝟐 = 𝟏𝟓𝟎 + 𝟑𝟎(𝟗𝟎) + 𝟎. 𝟐𝟓(𝟗𝟎)𝟐
C2=4875birr/h
𝑪𝟑 = 𝟏𝟒𝟎 + 𝟎. 𝟑𝟓(𝟗𝟎) + 𝟎. 𝟑𝟓(𝟗𝟎)𝟐
𝑪𝟑 = 𝟔𝟏𝟐𝟓 𝒃𝒊𝒓𝒓/𝒉
𝑪𝑻 = 𝟓𝟗𝟎𝟕𝒃𝒊𝒓𝒓/𝒉 + 4875birr/h +𝟔𝟏𝟐𝟓 𝒃𝒊𝒓𝒓/𝒉
𝑪𝑻 = 𝟏𝟔𝟗𝟎𝟕𝒃𝒊𝒓𝒓/𝒉
Then the annual saving between the optimal and equal sharing is:
CT saving annually= (cost of sharing-cost of optimal)*year
1 year=8760 h
CT saving annually= ( 𝟏𝟔𝟗𝟎𝟕𝐛𝐢𝐫𝐫/𝐡- 𝟏𝟔𝟕𝟑𝟑. 𝟑𝟑𝟔𝟏𝟕 𝒃𝒊𝒓𝒓/𝒉)*8760h
CT saving annually=1,521,295.2birr
P a g e | 16
16
17
ANSWER Q 7
Given
Therefore,
For 125MW of ,
By simplification
18
Let’s solve them by Newton-Raphson method
Where
To find the initial estimate: let’s solve the problem without loss
∆ PG0 = P0 + ∆ P0
19
20