Professional Documents
Culture Documents
DSEPower
ELECTRO-MAGNETIC COMPATIBILITY
display, analoge meters and 9460-12 24v 5A (LCD & Meters) 9461-12 24v 10A (LCD & Meters)
1ph
12V
N
DSE9460/DSE9461
7
OTHER
PT1000 ONLY
1 1
ISSUE 1
®
DSEPower
DSE9460/9461 SPECIFICATION
AC SUPPLY
DC OUTPUT RATING
DSE9460 OUTPUT
FEATURES 5 A DC at 12 V & 24 V DC
DSE9461 OUTPUT
10 A DC at 12 V & 24 V DC
EFFICIENCY
ADVANCED FEATURES >86%
• Intelligent two, three and four stage charging
profiles AUXILIARY OUTPUT
100 mA DC at 12 V
• Configurable to suit most battery types
(12V/24V) REGULATION
• Adjustable current limit LINE
<0.5%
• Can be used as a battery charger, power supply
or both at the same time LOAD
• Automatic or Manual boost and storage charge 2%
functions to help maintain battery condition TEMPERATURE SENSOR INPUT
• Digital Microprocessor Technology PT1000
• Temperature compensation for battery charging
PROTECTIONS
• Low Output Ripple and superb line regulation Short Circuit
• Available in a number of display variants (LEDs, DC Over Voltage
Analogue Meters, LCD display) DC Over Current
Reverse Polarity
Full Protection Over Temperature
• AC input Under voltage AC Under & Over Voltage
• AC input Over voltage
CHARGE FAILURE RELAY
• Battery charger output Over voltage 3 A at 30 V DC volt free relay
• Battery charger output Over current
• Battery temperature compensation with over DIMENSIONS
OVERALL
temperature protection 165 mm x 305 mm x 110 mm
• Output short circuit and Inversion polarity with 6.5” x 12” x 4.3”
auto recovery
WEIGHT
• Automatic power de-rating at high ambient 2.3 kg
temperatures
Automatic Boost Mode KEY BENEFITS OPERATING TEMPERATURE RANGE
-30 oC to +55 oC
• Boosts and equalises cell charge improving • Fully flexible to maximise the life of the battery
battery performance and life • Suitable for a wide range of battery types STORAGE TEMPERATURE RANGE
Power Save Mode -40 oC to +85 oC
• Switched mode design
• Once the battery is fully charged the chargers • Fault output
switch to Eco-Power to save energy • Minimum 86% efficiency throughout full
Communication operating range
• Can be integrated into external systems through • No external intervention for boost mode
MODBUS RTU using RS485 • Multiple chargers can be linked together to
• Fully configurable via DSE Configuration Suite provide larger current output
PC Software • Can be permenantly connected to battery and
• External remote LCD option mains supply. No need to disconnect through
high load conditions.
RELATED MATERIALS
TITLE PART NO’S
DSE9000 Configuration Suite PC Software Manual 057-159
DSE Configuration Suite Installation & Operator Manual 057-151
DSE9460/DSE9461 Series Installation Instructions 053-148
DSE9460/DSE9461 Series Operator Manual 057-176
DSE2541 Data Sheet 055-160
DSE2541 Installation Instructions 053-154
Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-153/11/12 (2)
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457