You are on page 1of 4

Part 1 – Parameter Estimation

S No Parameter Location#1 Location#2 Location#3 Location#4

ANDAR MOR UP MORE NAGAN DISCO MOR


1 Location SHADMAN CHOWRANGI

TUBULAR TOWER TOWER TOWER


2 Type of Conductor support
POLE
(Tower/Pole)

3
Height of Tower 18 m 15m 15m 15m
(approx. m/ft)

4 Voltage level (AC/DC) AC AC AC AC

5
Line Voltage (kV) 132 KV 132 KV 132 KV 132 KV

6 Arcing Horn
(present/absent) ABSENT ABSENT ABSENT ABSENT

7 Line Configuration (horizontal


VERTICAL VERTICAL VERTICAL
or vertical parallel) VERTICAL

8
Conductor cross sectional area 300 mm2 300mm2 300mm2 300mm2
(approx.)

9 Spacing between phase 2.5 m 2.5 m 3m 2.5m


conductors

10
Type of Circuit DOUBLE DOUBLE DOUBLE DOUBLE
(single/double/multiple)

11 Earth Wire (present/absent) PRESENT PRESENT PRESENT ABSENT

Page 1 of 8
S No
Parameter Location#1 Location#2 Location#3 Location#4

12
Types of conductors SINGLE SINGLE SINGLE SINGLE
(single/bundled)

13
Bundled Conductors N/A N/A N/A N/A
(triangular/rectangular
spaced)

14 Spacing between bundled N/A N/A N/A N/A


conductors

15 Types of insulators STRAIN AND STRAIN STRAIN AND SUSPENSION


(suspended/strain/both/others) SUSPENSION SUSPENSION

16
Number of insulator discs in 14 14 14 14
one string

2 2 2
17 Sag (approx., m/ft) 2.5 ft. ft. ft. ft.

18 Ground clearance (m/ft) 10 m 8.5 m 8.5 m 8.5 m

19
Conductor support Level EQUAL EQUAL EQUAL EQUAL
(equal/unequal)

20 Distance
between 250 m 200 m 200 m 200 m
towers/length of span
(approx., m/ft)
21 YES (WIND) YES(WIND) YES(WIND) YES(WIND)
Loading Factors (yes/no)

22
Vibrations (resonant/galloping/
RESONANT RESONANT RESONANT RESONANT
dancing)

23 STOCK- STOCK-
Type of dampers BRIDGE BRIDGE ABSENT ABSENT

Page 2 of 8
S No Parameter Location#1 Location#2 Location#3 Location#4

24
Length of cross arms 5m ,6m,5m 4m 4m 4m
(approx., m/ft)
25
Distance between cross arm 2.5m,3m,2.5m 1.5m 1.5m 1.5m
and tower (if applicable)

26
Total number of spacers N/A N/A N/A N/A
between two towers.

27
Guard Ring/Corona Ring ABSENT PRESENT ABSENT ABSENT

28
Temperature (°𝐶) 30 0 C 30 0 C 30 0 C 30 0 C

29
Wind pressure (MPa) 0.1012 0.1012 0.1012 0.1012

30
Wind Velocity (kmph) 15 20 18 18

31
Humidity (%) 50 50 50 50

Page 3 of 8
Part 2 – Attributes and Recommendations

Location# Attributes Recommendations


If flash-over occur at insulator then it may
1-) Arcing horn (absent) damage the insulator. So pair of arcing horn
1 2-) Guard ring (absent) protect the insulator from damage. But if
arcing horn and guard ring pair is used then it
gives two benefits; protect insulator also
prevent leakage current.

1-) Arcing horn (absent) The tree below the transmission


2 line is one of the cause of
2-) tree
corona loss. After 1 year or 2
years its height may reach near
to the lowest conductor; tree
provide the path to ground the
current. So audit after every 6
months is necessary.

Location# Attributes Recommendations

The vibration in conductor due to wind and


1-) Arcing horn (absent) storm may damage the conductor. So
3 2-) damper (absent) damper must be there to protect the
3-) Earth wire (absent) conductor.

1-) Earth wire (absent) Earth wire protect the


4 2-) Arcing horn (absent) phase conductor from
damage when flash-over
occur. Therefore it is
recommended to use
earth wire

Page 4 of 8