Professional Documents
Culture Documents
Modify Design
No
Proposed Design Procedure of Earthing Systems for Low-voltage Installations
Start
Yes
End
Earthing Resistance Calculations based on BS 7430
Step 1. Select the type of earthing from the drop-down list below:
Three rods at the vertices of an equilateral triangle
Step 2. Enter the values of the parameters below in the highlighted cells:
ρ the resistivity the soil (assumed uniform), in ohm metres (Ωm)
1.5
0.016
2.00
1.80
3
Value: Resistance
ohm (Ω)
BS-7430 Conductor Selection
Select the
maximum
Temperature
value
Enter for
thethevalue
(fixed value)
conductor
of average RMS
Size of the Earthing Conductor This
It table
should
value is only
be
of fault
applicable
Select
currentthe
verified that
in forthe
(A)
the case of
material 1the
is likely
second
conductor
to be in the
The average fa 1000 This
Is theislocation
same a fixed as
initial
Fault current 1 value
temperature
the conductorof
Metal MateriaCopper the
will conductor
not be =
Maximum Tempe 350 30°C
damaged ? or
R.M.S Current density for201
1 second duration,
present a fire
initial conduc NO risk at the
T1 the initia 38 temperature
T2 the final 69 Ensure
selected. that you
select the nearst
new k value 71.78783223
standard value
which is higher
than this
Type of joint sWelded or Brazed calculated value
Corresponding 13.92993727
Select the
Select
material thetype of
Select
duration the(in
The average value of fault currentthe
in strip
(kA)
maximum
seconds) of the
temperature
fault current (in
Select the
°C) of the
Material of theCopper conductor
Duration of fau 1 conductor size
Maximum cond 200
Size of conduc38 x 6
36.3
The average val
Enter the
Enter thevalue
duration valueof
of the soil
Current density at the surface of earth
earth faults
electrode
resistivity in
in s
ohm-m
t the durat 10
p the resi 50
Page 10
Select the
configuration of
the earthing
BS-7430 Conductor Selection conductor
Allowable
tolerance: −3%
Configuration Solid round
Page 11
BS-7430 Conductor Selection
Select the
maximum
Temperature
value
Enter for
thethevalue
(fixed value)
conductor
of average RMS
This
It table
should
value is only
be
of fault
applicable
Select
currentthe
verified that
in forthe
(A)
the case of
material 1the
is likely
second
conductor
to be in the
This
Is theislocation
same a fixed as
initial
value
temperature
the conductorof
the
will conductor
not be =
30°C
damaged ? or
present a fire
risk at the
temperature
Ensure
selected. that you
select the nearst
standard value
which is higher
than this
calculated value
Select the
Select
materialthetype of
Select
durationthe
the strip (in
maximum
seconds) of the
temperature
fault current (in
Select the
°C) of the
conductor
conductor size
Enter the
Enter thevalue
duration valueof
of the soil
of earth
earth faults
electrode
resistivity in
in s
ohm-m
Select the
material
Select theof the
earthing
configuration of
n earthing conductor with respect to corrosion and mechanical strength
conductor
the earthing
conductor
Allowable
tolerance: −3%
Page 12
Select the
configuration of
the earthing
conductor
Allowable BS-7430 Conductor Selection
tolerance: −3%
diameter) may be reduced to 28 mm² (6 mm diameter) in certain applications where mechanical strength is not an essential requirement.
ir termination rods only. For applications where mechanical stress such as wind loading is not critical, a 10 mm diameter, 1 m long maximu
Page 13
BS-7430 Conductor Selection
ength is not an essential requirement. Consideration should in this case, be given to reducing the spacing of the fasteners.
l, a 10 mm diameter, 1 m long maximum air termination rod may be used. Applicable for earth lead-in rods only.
Page 14
BS-7430 Conductor Selection
Page 15
39.3999
Earthing Resistance Calculations based on IEEE Green Book
Step 1. Select the type of earthing from the drop-down list below:
Three-point star
Step 2. Enter the values of the parameters below in the highlighted cells: input values
p the soil resistivity, in ohm metres (Ωm) 1000
a the radius of the rod, in metres (m) 0.025
L the rod length, in metres (m) 1.5
d the depth of burial, in metres (m) 0.5
0.0001
3
Number of rods 3
Minimum Size
Remarks
Corrosion Protection
Material
Mechanical Protection
Protective conductors
A) Method 1
B) Method 2
In case where the risk of corrosion and mechanical damage is extremely low, 16-mm² can be used. An earth electrode is consi
electrode when installed at a depth not exceeding 0.5m
25 mm²
g Conductor
Two (2) Exposed– conductive– parts
Sheathed or Mechanically Protected
25
NO
Copper
226
Copper
bare protective conductors in contact with cable covering but not bunched with other cables
70 °C PVC
NO
PVC
Normal conditions
70 °C PVC
143
115
159
141
22.7421
1000
Copper
7.6639
Common Earthing Practices in Malaysia
Step 1. Select the type of earthing from the drop-down list below:
Step 2. Select the values of the parameters below in the highlighted cells:
Output Data:
Total length of rod required in metres (m)
2m - 4m
1.5
*
*
*
*
The Use of Concrete Enclosed Reinforcing Rods as Grounding Electrodes
Step 2. Enter the values of the parameters below in the highlighted cells:
ρₒ the resistivity of surrounding medium (Ω-m)
L the length of rod in (m)
r the radius of the rod (m)
r1 the outer radius of rod (m)
ρ1 the higher resistivity of (earth) in (Ω-m)
r the radius of equivalent hemisphere
d the spacing of electrodes
N the total number of rods
k given in graph
M multiplier to obtain array resistance from single electrode reistance
r resistivity (Ω-cm)
h depth of burial (cm)
L total length (cm)
d diameter of the rod (cm)
70.3748
D TURBINE
300
0.4
4
0.1
1.85
3.82
43.99515
60
5
4.5
0.5
94.14621
42.3
0.025
1
25.00071
100
0.016
10
1.5
15
3.8353748
Satisfactory, continue with initial design
1000
180
150
0.016
19.31793
3000
2000
80
60
0.5
33.33333
174.5266
Three Parallel aligned rods
Copper Plate
Copper Strip