FIRE RPOTECTION SYSTEM

Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.


FIRE RPOTECTION SYSTEM

Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.


CONTENTS
- SCHEMATIC DIAGRAM
- FIRE PUMP
- PRE-ACTION SPRINKLERS
- WET SPRINKLERS
- FIRE HYDRANT & FIRE HOSE CABINET
- FIRE EXTINGUISHER

Confidential
Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.
2
FIRE PROTECTION SYSTEM Schematic Diagram
FM. Valve DATA HALL1A
FIRE DEPARTMENT (FDC) PRE ACTION VALVE ( DATA HALL 1A)
FIRE HOSE CABINET x12 Sets Nitrogen Gas

FIRE HYDRANT ELECTRICAL ROOM 1A


PRE ACTION VALVE ( DATA HALL 1B)
x7 Sets Nitrogen Gas MECHANICAL ROOM
AIR SUPPLY PLENUM
AIR INTAKE
PRE ACTION VALVE ( DATA HALL 2A) DATA HALL . HOAISE
Nitrogen Gas
Water tank DATA HALL1B
PRE ACTION VALVE ( DATA HALL 2B)
250 m³ Nitrogen Gas

PRE ACTION VALVE ( STORAGE RM) ELECTRICAL ROOM 1B


Nitrogen Gas AIR SUPPLY PLENUM
AIR INTAKE
DATA HALL
DFP-01 (Engine) PRE ACTION VALVE ( MMR) Nitrogen Gas
HOT AISE

Nitrogen DATA HALL2A


PRE ACTION VALVE ( FER 2)
Gas
FM. Valve
Nitrogen ELECTRICAL ROOM 2A
PRE ACTION VALVE ( FER 3)
Gas MECHANICAL ROOM
AIR SUPPLY PLENUM
AIR INTAKE
DATA HALL . HOAISE

DATA HALL2B
FER2
JP-01 (Jockey)
WET TYPE VALVE
FER3 ELECTRICAL ROOM 2B
PUMP ROOM
Water tank AIR SUPPLY PLENUM
AIR INTAKE
GENERATOR HOUSE
250 m³ MMR DATA HALL
HOT AISE
OFFICE AREA
STORAGE ROOM FIRE EXTINGUISHER
WATER CO2
RAW WATER FROM WHA Total : 9 Zone , Pre Action 8 Zone , Wet Type 3 Zone x3 Sets x53 Sets
It is prohibited below, it is created without our permission copy of this document, Confidential
it is used for purposes other than, and it is publish this document to a third party Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.
3
FIRE PROTECTION SYSTEM FIRE PUMP
PUMP ROOM LAYOUT

JP-01

EFP-01

DFP-01

It is prohibited below, it is created without our permission copy of this document, Confidential
it is used for purposes other than, and it is publish this document to a third party Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.
4
FIRE PROTECTION SYSTEM FIRE PUMP
ENGINE TYPE

Horizontal Type
Capacity :1000GPM
Pressure : 160PSI
Jockey Pump
Capacity : 25 GPM
Pressure max : 25Bar

Made in USA

It is prohibited below, it is created without our permission copy of this document, Confidential
it is used for purposes other than, and it is publish this document to a third party Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.
5
FIRE PROTECTION SYSTEM FIRE PUMP
ELECTRIC TYPE

Electrical Type
Capacity : 1000 GPM
Pressure : 160 PSI

Made in USA

It is prohibited below, it is created without our permission copy of this document, Confidential
it is used for purposes other than, and it is publish this document to a third party Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.
6
FIRE PROTECTION SYSTEM FIRE PUMP
OPERATION PRESSURE OF SYSTEM

- Jockey pump
Pump start at 160 Psi
Pump stop at 170 Psi

- Electric Fire pump


Pump start at 155 Psi
Pump stop by manual
- Engine Fire pump
Pump start at 145 Psi
Pump stop by manual

It is prohibited below, it is created without our permission copy of this document, Confidential
it is used for purposes other than, and it is publish this document to a third party Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.
7
FIRE PROTECTION SYSTEM PRE-ACTION SPRINKLERS
PROTECTION AREA

Pipe volume Nitrogen generator


Pipe (gallon) (gallon)
No. Area served size Occupancies
(φmm.) Pipe
volume SFx1.2 Model volume
(gallon)
1 Data Hall-1A 150A 747 896 NG-1 500 1120 Ordinary hazard
2 Data Hall-1B 150A 747 896 NG-1 500 1120 Ordinary hazard
3 Data Hall-2A 150A 636 763 NG-1 500 1120 Ordinary hazard
4 Data Hall-2B 150A 636 763 NG-1 500 1120 Ordinary hazard
5 MMR ROOM 65A 38 45 NG-1 100 540 Ordinary hazard
6 FER2 ROOM 40A 6 8 NG-1 100 540 Ordinary hazard
7 FER3 ROOM 40A 6 8 NG-1 100 540 Ordinary hazard
8 SIMULATION ROOM 40A 13.64 16 NG-1 100 540 Ordinary hazard
9 STORAGE ROOM 65A 38 45 NG-1 100 540 Ordinary hazard
It is prohibited below, it is created without our permission copy of this document, Confidential
it is used for purposes other than, and it is publish this document to a third party Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.
8
FIRE PROTECTION SYSTEM PRE-ACTION SPRINKLERS
LAYOUT

DATA HALL-1A SIM


DATA HALL-2B DATA HALL-2A DATA HALL-1B

MMR
FER2 FER3
STORAGE

It is prohibited below, it is created without our permission copy of this document, Confidential
it is used for purposes other than, and it is publish this document to a third party Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.
9
FIRE PROTECTION SYSTEM WET SPRINKLERS
PROTECTION AREA

Maximum
Pipe size distance K Factor Cover
No. Area served Occupancies
(φmm.) between (gpm./psi½) area
sprinkler head

1 OFFICE AREA 100A 4.6 m. 5.6 18.6 m² Light hazard


2 PUMP ROOM 65A 3.0 m. 5.6 8.4 m² Extra hazard
3 GENERATOR HOUSE 65A 3.0 m. 5.6 8.4 m² Extra hazard

It is prohibited below, it is created without our permission copy of this document, Confidential
it is used for purposes other than, and it is publish this document to a third party Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.
10
FIRE PROTECTION SYSTEM WET SPRINKLERS
LAYOUT

GENERATOR HOUSE

OFFICE AREA

PUMP
ROOM

It is prohibited below, it is created without our permission copy of this document, Confidential
it is used for purposes other than, and it is publish this document to a third party Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.
11
FIRE PROTECTION SYSTEM FIRE HYDRANT & FIRE HOSE CABINET
PROTECTION AREA

Pipe size Hose reel Equipment


No. Area served Type Q’ty
(φmm.) φmm.xL(m.) name

FIRE HOSE
1 BUILDING 12 Sets 65A 25Ax30m. FHC
CABINET
FIRE
2 OUTSIDE BUILDING 7 Sets 100Ax2-65A - FH-OUT
HYDRANT

FIRE HOSE CABINET FIRE HYDRANT

It is prohibited below, it is created without our permission copy of this document, Confidential
it is used for purposes other than, and it is publish this document to a third party Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.
12
FIRE PROTECTION SYSTEM FIRE HYDRANT & FIRE HOSE CABINET
LAYOUT

FH-OUT-01

FH-OUT-07

FH-OUT-03 FH-OUT-02

FHC-09 FHC-05
FHC-12

FHC-04 FHC-01
FHC-08

FHC-11 FHC-06 FHC-02


FHC-10 FHC-07

FH-OUT-06

FHC-03

FH-OUT-04 FH-OUT-05

It is prohibited below, it is created without our permission copy of this document, Confidential
it is used for purposes other than, and it is publish this document to a third party Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.
13
FIRE PROTECTION SYSTEM FIRE EXTINGUISHER
PROTECTION AREA

Horizontal
Time of
No. Area served Type Q’ty Capacity range of Classifications
discharge
stream

1 ALL AREA Carbon dioxide 53 Sets 2.5 gallon 30 to 40 ft. 60 Sec. 2-A
2 OFFICE AREA water 3 Sets 10 to 15 lb. 3 to 8 ft. 8 to 30 Sec. 2 to 10-B:C

CO₂ Type Water Type

It is prohibited below, it is created without our permission copy of this document, Confidential
it is used for purposes other than, and it is publish this document to a third party Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.
14
FIRE PROTECTION SYSTEM FIRE EXTINGUISHER
LAYOUT

It is prohibited below, it is created without our permission copy of this document, Confidential
it is used for purposes other than, and it is publish this document to a third party Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.
15
Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.