Presentation Fire Protection System Mango-BKK062 Project R.00
Presentation Fire Protection System Mango-BKK062 Project R.00
Confidential
Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.
2
FIRE PROTECTION SYSTEM Schematic Diagram
FM. Valve DATA HALL1A
FIRE DEPARTMENT (FDC) PRE ACTION VALVE ( DATA HALL 1A)
FIRE HOSE CABINET x12 Sets Nitrogen Gas
DATA HALL2B
FER2
JP-01 (Jockey)
WET TYPE VALVE
FER3 ELECTRICAL ROOM 2B
PUMP ROOM
Water tank AIR SUPPLY PLENUM
AIR INTAKE
GENERATOR HOUSE
250 m³ MMR DATA HALL
HOT AISE
OFFICE AREA
STORAGE ROOM FIRE EXTINGUISHER
WATER CO2
RAW WATER FROM WHA Total : 9 Zone , Pre Action 8 Zone , Wet Type 3 Zone x3 Sets x53 Sets
It is prohibited below, it is created without our permission copy of this document, Confidential
it is used for purposes other than, and it is publish this document to a third party Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.
3
FIRE PROTECTION SYSTEM FIRE PUMP
PUMP ROOM LAYOUT
JP-01
EFP-01
DFP-01
It is prohibited below, it is created without our permission copy of this document, Confidential
it is used for purposes other than, and it is publish this document to a third party Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.
4
FIRE PROTECTION SYSTEM FIRE PUMP
ENGINE TYPE
Horizontal Type
Capacity :1000GPM
Pressure : 160PSI
Jockey Pump
Capacity : 25 GPM
Pressure max : 25Bar
Made in USA
It is prohibited below, it is created without our permission copy of this document, Confidential
it is used for purposes other than, and it is publish this document to a third party Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.
5
FIRE PROTECTION SYSTEM FIRE PUMP
ELECTRIC TYPE
Electrical Type
Capacity : 1000 GPM
Pressure : 160 PSI
Made in USA
It is prohibited below, it is created without our permission copy of this document, Confidential
it is used for purposes other than, and it is publish this document to a third party Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.
6
FIRE PROTECTION SYSTEM FIRE PUMP
OPERATION PRESSURE OF SYSTEM
- Jockey pump
Pump start at 160 Psi
Pump stop at 170 Psi
It is prohibited below, it is created without our permission copy of this document, Confidential
it is used for purposes other than, and it is publish this document to a third party Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.
7
FIRE PROTECTION SYSTEM PRE-ACTION SPRINKLERS
PROTECTION AREA
MMR
FER2 FER3
STORAGE
It is prohibited below, it is created without our permission copy of this document, Confidential
it is used for purposes other than, and it is publish this document to a third party Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.
9
FIRE PROTECTION SYSTEM WET SPRINKLERS
PROTECTION AREA
Maximum
Pipe size distance K Factor Cover
No. Area served Occupancies
(φmm.) between (gpm./psi½) area
sprinkler head
It is prohibited below, it is created without our permission copy of this document, Confidential
it is used for purposes other than, and it is publish this document to a third party Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.
10
FIRE PROTECTION SYSTEM WET SPRINKLERS
LAYOUT
GENERATOR HOUSE
OFFICE AREA
PUMP
ROOM
It is prohibited below, it is created without our permission copy of this document, Confidential
it is used for purposes other than, and it is publish this document to a third party Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.
11
FIRE PROTECTION SYSTEM FIRE HYDRANT & FIRE HOSE CABINET
PROTECTION AREA
FIRE HOSE
1 BUILDING 12 Sets 65A 25Ax30m. FHC
CABINET
FIRE
2 OUTSIDE BUILDING 7 Sets 100Ax2-65A - FH-OUT
HYDRANT
It is prohibited below, it is created without our permission copy of this document, Confidential
it is used for purposes other than, and it is publish this document to a third party Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.
12
FIRE PROTECTION SYSTEM FIRE HYDRANT & FIRE HOSE CABINET
LAYOUT
FH-OUT-01
FH-OUT-07
FH-OUT-03 FH-OUT-02
FHC-09 FHC-05
FHC-12
FHC-04 FHC-01
FHC-08
FH-OUT-06
FHC-03
FH-OUT-04 FH-OUT-05
It is prohibited below, it is created without our permission copy of this document, Confidential
it is used for purposes other than, and it is publish this document to a third party Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.
13
FIRE PROTECTION SYSTEM FIRE EXTINGUISHER
PROTECTION AREA
Horizontal
Time of
No. Area served Type Q’ty Capacity range of Classifications
discharge
stream
1 ALL AREA Carbon dioxide 53 Sets 2.5 gallon 30 to 40 ft. 60 Sec. 2-A
2 OFFICE AREA water 3 Sets 10 to 15 lb. 3 to 8 ft. 8 to 30 Sec. 2 to 10-B:C
It is prohibited below, it is created without our permission copy of this document, Confidential
it is used for purposes other than, and it is publish this document to a third party Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.
14
FIRE PROTECTION SYSTEM FIRE EXTINGUISHER
LAYOUT
It is prohibited below, it is created without our permission copy of this document, Confidential
it is used for purposes other than, and it is publish this document to a third party Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.
15
Copyright © Takasago Thermal Engineering Co., Ltd. All Rights Reserved.