KINGDOM OF BAHRAIN
CATHODIC PROTECTION
QUATERLY SURVEY REPORT
OCTOBER, 2019
(BATELCO,Hamala)QUATERLY CP SURVEY
REPORT Revision No. 0 P a g e |1 Date 30/10/2019
BATELCO-HAMALA CP SURVEY REPORT REV 0 30/10/2019
Dear Sirs
SYSTEM DESCRIPTION
From Newtech understanding there are Four Cathodic Protection systems operating
at BATELCO, Hamala
(BATELCO,Hamala)QUATERLY CP SURVEY
REPORT Revision No. 0 P a g e |2 Date 30/10/2019
IMPRESS CURRENT CATHODIC PROTECTION (ICCP)
(BATELCO,Hamala)QUATERLY CP SURVEY
REPORT Revision No. 0 P a g e |3 Date 30/10/2019
UNDERGROUND DIESEL TANK
TRANSFORMER RECTIFIER
Underground Diesel ground storage tank is provided with external cathodic protection
systems within the Batelco, Hamala facility.
System is monitored using portable Copper sulfate electrode and powered via air-cooled
rectifiers located in the electrical control room. The rectifiers are set to operate in constant
current mode.
(BATELCO,Hamala)QUATERLY CP SURVEY
REPORT Revision No. 0 P a g e |4 Date 30/10/2019
OVERALL CONCLUSIONS:
Findings:
This section is having Impressed Current cathodic protection system protecting the
Underground Diesel storage tank
Transformer Rectifier output was very low. We adjusted the TR output as required.
Off Potential measured above the tank are above -850 mV wrt portable copper sulphate
portable reference electrode which shows the tank is cathodically protected. (Refer the result
sheet)
Recommendations:
We consider that the tank is protected and no additional work is required. A typical shift in
potential of 300mV (negative) is accepted as the industry standard required to provide
cathodic protection to carbon steel. The results clearly demonstrate a negative potential shift
far in excess of this value.
(BATELCO,Hamala)QUATERLY CP SURVEY
REPORT Revision No. 0 P a g e |5 Date 30/10/2019
UNDERGROUND DIESEL TANK
AS FOUND
Tank location – INSIDE ELECTRICAL ROOM Serial No.-10-009-01 Setting :C1,F5
Manufacturer :CTS AC input – 240V 1ph 50HZ O/p Voltage(R): 25V O/p Current(R): 4A
Type – Air Cooled Control- Manual O/p Voltage(o) : 3.3V O/p Current(o) : 0.11A
AS LEFT
Tank location – INSIDE ELECTRICAL ROOM Serial No.-10-009-01 Setting :C3,F3
Manufacturer :CTS AC input – 240V 1ph 50HZ O/p Voltage(R): 25V O/p Current(R): 4A
Type – Air Cooled Control- Manual O/p Voltage(o) : 13V O/p Current(o) : 0.68A
Test Box: -
AS FOUND
Sl.no Potential Readings(mV)/SSC Result
1 -524 Not-Accepted
AS LEFT
Sl.no Potential Readings(mV)/CSE Result
On Off
1 -1124 -936 Accepted
Remarks:-
(BATELCO,Hamala)QUATERLY CP SURVEY
REPORT Revision No. 0 P a g e |6 Date 30/10/2019
ABOVE GROUND WATER TANKS
This section is having sacrificial cathodic protection system protecting three above ground
Water tanks.
1. Aboveground Domestic tank- Sacrificial Anodes
2. Aboveground Fire hydrant tank- Sacrificial Anodes
3. Aboveground Sprinkler tank- Sacrificial Anodes
(BATELCO,Hamala)QUATERLY CP SURVEY
REPORT Revision No. 0 P a g e |7 Date 30/10/2019
(BATELCO,Hamala)QUATERLY CP SURVEY
REPORT Revision No. 0 P a g e |8 Date 30/10/2019
(BATELCO,Hamala)QUATERLY CP SURVEY
REPORT Revision No. 0 P a g e |9 Date 30/10/2019
OVERALL CONCLUSIONS:
Findings:
This section is having sacrificial cathodic protection system protecting three above ground
Water tanks.
On Potentials measured at Domestic tank manholes are below -850 mV wrt silver chloride
portable reference electrode which shows the tanks are not cathodically protected. (Refer the
result sheet)
On Potentials measured at Fire Hydrant tank manholes are above -850 mV wrt silver chloride
portable reference electrode which shows the tanks are not cathodically protected. (Refer the
result sheet)
On Potentials measured at Sprinkler tank manholes are above -850 mV wrt silver chloride
portable reference electrode which shows the tanks are not cathodically protected. (Refer the
result sheet)
Roof-external coating for all the three tanks has been removed.
Recommendations:
It seems the sacrificial anodes for domestic tank are consumed/not delivering current ;we
recommend an inspection of the internal sections of the domestic water tank immediately to
check the dimensions of the sacrificial anodes and if required all the CP anodes to be
replaced with new anodes to avoid further corrosion of the tank internals.
Though Potential for fire hydrant and sprinkler tank internals are above -850 mv; we
would recommend an inspection of the anodes and tank internal sections.
It is anticipated that some degree corrosion will be observed and should be repaired before
replacing the anodes.
(BATELCO,Hamala)QUATERLY CP SURVEY
REPORT Revision No. 0 P a g e | 10 Date 30/10/2019
T1 -ABOVE GROUND DOMESTIC TANK
AS FOUND
Test Location Potential Result
Readings(mV)/SCE
1 Top -555 Not Accepted
Bottom -560 Not Accepted
2 Top -495 Not Accepted
Bottom -489 Not Accepted
AS FOUND
Test Location Potential Result
Readings(mV)/SCE
1 Top -872 Accepted
Bottom -880 Accepted
2 Top -907 Accepted
Bottom -921 Accepted