Data Summary

Slab = 1,00 ft Contents ft m


t plywood = 12,00 mm L joist 3,00 0,91
Density of Concrete = 150,00 PCF L strenger 3,00 0,91
Plywood Sheathing = 1,00 ft L shore 5,00 1,52
Joist = 1,3" x 1,8"
Stringers = 1,3" x 1,8" Control Capcity
Shores = 1,5" Between Joist & Stringer SAFE
Fb = 1.400,00 psi Between Stringer & Shores SAFE
Fv = 160,00 psi Check Shore Strength SAFE
E = 1.300.000,00 psi
Fc = 1.000,00 psi
Bearing Capacity (Fcꓕ) = 425,00 psi

A. Design of Sheating (Joist Spacing)


1). Design Load
W1 = W x ts (6/12) psf 75 psf
W2 = 10 - 15 Psf 15 psf
W3 = 50 Psf (manual) or 75 Psf (Motorized) 50 psf
Wt 140 psf
Sheating Load = Wt x 1 ft (lb/ft) 140 lb/ft

2). Sheating type surface finish b = 12,00 in


1). 1" Board d = 0,75 in
a. Sec parameters A = 9,00 in2
b = 12" d = 0,75" S = 1,13 in3
A=bxd I = 0,42 in4
S = (b x d)/6 (in3) Fb = 1.204,00 psi
I = (b x d)/12 (in4) Fv = 155,20 psi
E = 1.261.000,00 psi

3). Check
Support Condition (3 and more)
L bending = 4,46 x d x ((Fb x b)/w)^1/2
= 33,98 in
L shear = 13,3 x (Fv x A)/W)+2 x d
= 134,20 in
L deflection = ∆ = 1/360 --> L=1,69 x (Ei/W)^1/3
= 26,37 in
L joist = 2,20
= 3,00 ft
B. Design of Joist (Stringer Spacing)
Joist Load (W) = Design Load x (L joist / 12) = lb/ft
= 420,00 lb/ft
Sec. Parameter = 1,3" x 1,8"
b = 1,50 in *Strength Par.
d = 3,50 in Fb= 1400 psi, Fv=160 psi, E=1,3x10^6 psi
Sec Par. =
A = 5,25 in2
S = 3,01 in3
I = 5,36 in4

L bending = 10,95x((Fb x S)/W)^1/2)


= 34,66 in
L shear = 13,3x((Fv x A)/W)+ 2d
= 33,60 in
L deflection = 1,69 x ((EI/W)^1/3
= 43,10 in
L stringer = 2,80 ft (choose the smallest)
= 3,00 ft

C. Design of Stringer (Shores Spacing)


Stringer load (W) = Design Load x (L stringer/12) = lb/ft
= 420,00 lb/ft
Sec. Parameter = 1,3" x 1,8" *Strength Par.
b = 3,50 in Fb= 1400 psi, Fv=160 psi, E=1,3x10^6 psi
d = 5,50 in
A = 8,25 in2
S = 7,56 in3
I = 20,80 in4

L bending = 10,95x((Fb x S)/W)^1/2)


= 54,98 in
L shear = 13,3x((Fv x A)/W)+ 2d
= 52,80 in
L deflection = 1,69 x ((EI/W)^1/3
= 67,73 in
L shore = 4,40 ft (choose the smallest)
= 5,00 ft
D. Check shore strength
a). P = Design Load x (L joist/12)*(L stringer/12) = lb
b). A = Bsh x Bsh
c). Actual Stress = P/A =lb/in2 < Fcꓕ
Between Joist & Stringer
P = 1260 lb
A = 5,25 in2
Actual Stress = 240 lb/in2

Control = SAFE

Between Stringer & Shores


P = 2100 lb
A = 5,25 in2
Actual Stress = 400 lb/in2

Control = SAFE

Check Shore Strength


P = 2100 lb
A = 12,25 in2
Actual Stress = 171,429 lb/in2

Control = SAFE