1. ELECTRICAL INSTALLATION Electrical wiring should be color coded and labeled 1.1 DISTRIBUTION BOARDS
Supply and install surface mounted metal enclousures type tested
Main distribution board MDB GROUND FLOOR factory built, including busbars of 150A rating & 10KA/1sec, all other connecting and fixing accessories for the system , all tested and wired torelevant 1.1.1 IEC standard, use DIN rail mounted terminal blocks with end brackets and marking tags for all outgoings. 1pc factory made drawing pocket, Himel PP-A4 or equivalent. all complete with 25% Nº 1 19000 reserve spaces, and consisting of:-
1 Pc main RCBO of 125A, 3ph, 4poles - Ground Floor
2 Pc main RCBO of 20A, 3ph, 4poles - Ground Floor 1 Pc main RCBO of 32A, 3ph, 4poles - Ground Floor 1 Pc main RCBO of 50A, 3ph, 4poles - Ground Floor 1 Pc main RCBO of 63A, 3ph, 4poles - Ground Floor
Supply and install surface mounted metal enclousures type tested
Sub distribution board for GROUND FLOOR OFFICE factory built, including busbars of 50A rating & 10KA/1sec, all other connecting and fixing accessories for the system , all tested and wired torelevant 1.1.2 IEC standard, use DIN rail mounted terminal blocks with end brackets and marking tags for all outgoings. 1pc factory made drawing pocket, Himel PP-A4 or equivalent. all complete with 25% Nº 1 6000 reserve spaces, and consisting of:-
1 Pc main RCBO of 20A/3p, 4poles
4 Pcs RCBO of 16A/1p,3 pole 6 Pcs RCBO of 10A/1p,2 pole
Supply and install surface mounted metal enclousures type tested
Sub distribution board for FIRST FLOOR OFFICE factory built, including busbars of 50A rating & 10KA/1sec, all other connecting and fixing accessories for the system , all tested and wired torelevant 1.1.3 IEC standard, use DIN rail mounted terminal blocks with end brackets and marking tags for all outgoings. 1pc factory made drawing pocket, Himel PP-A4 or equivalent. all complete with 25% Nº 1 6000 reserve spaces, and consisting of:-
1 Pc main RCBO of 20A/3p, 4poles
4 Pcs RCBO of 16A/1p,3 pole 6 Pcs RCBO of 10A/1p,2 pole Supply and install surface mounted metal enclousures type tested sub distribution board for COLD ROOM 1 factory built, including busbars of 50A rating & 10KA/1sec, all other connecting and fixing accessories for the system , all tested and wired torelevant IEC 1.1.4 standard, use DIN rail mounted terminal blocks with end brackets and marking tags for all outgoings. 1pc factory made drawing pocket, Himel PP-A4 or equivalent. all complete with 25% reserve Nº 1 7500 spaces, and consisting of:- 1 Pc main RCBO of 32A/3p, 4poles 2 Pcs RCBO of 10A/3p,4 pole 3 Pcs RCBO of 16A/1p,3 pole 1 Pcs RCBO of 10A/1p,2 pole
Supply and install surface mounted metal enclousures type tested
Sub distribution board for COLD ROOM 2 factory built, including busbars of 100A rating & 10KA/1sec, all other connecting and fixing accessories for the system , all tested and wired torelevant IEC 1.1.5 standard, use DIN rail mounted terminal blocks with end brackets and marking tags for all outgoings. 1pc factory made drawing pocket, Himel PP-A4 or equivalent. all complete with 25% reserve Nº 1 9000 spaces, and consisting of:-
1 Pc main RCBO of 50A/3p, 4poles
2 Pcs RCBO of 10A/3p,4 pole 5 Pcs RCBO of 16A/1p,3 pole 1 Pcs RCBO of 10A/1p,2 pole
Supply and install surface mounted metal enclousures type tested
Sub distribution board for WAREHOUSE factory built, including busbars of 100A rating & 10KA/1sec, all other connecting and fixing accessories for the system , all tested and wired torelevant IEC 1.1.6 standard, use DIN rail mounted terminal blocks with end brackets and marking tags for all outgoings. 1pc factory made drawing pocket, Himel PP-A4 or equivalent. all complete with 25% reserve Nº 1 10000 spaces, and consisting of:-
1 Pc main RCBO of 63A/3p, 4poles
2 Pcs RCBO of 25A/3p,4 pole 3 Pcs RCBO of 16A/1p,3 pole 11 Pcs RCBO of 10A/1p,2 pole 1.2 LIGHT POINTS For Flush installation in thermoplastic conduit of diammeter 16mm 1.2.1 fed through PVC conductors of 2 x 2.5sq.mm color coded and m 640 350 labeled with complete connecting and fixing accessories. Supply and Install different colored lighting wires having 2*2.5mm2 1.2.2 size. Rating of 10 and 0.5killo wat loads capacity per phase. It shall includes: PCS 60 520 Junction Boxes Connectors 1.2.3 Switches swiches 10A or 16A/1ph for flush/surface mounting b) One way double gang - multi circuit switch,10A - flush mounted Nº 20 160 c) Two way single circuit switch, 10A - flush mountedwitch,220V 1 Nº 4 380 d) Thumbler single circuit switch, 16A - flush mountedwitch,220V 1 Nº 10 500 1.3 SOCKET OUTLETS POINTS It. DESCRIPTION Unit Qut Rate Amount For Flush installation in thermoplastic conduit of diammeter 16mm 1.3.1 fed through PVC conductors of 3x 2.5sq.mm color coded and m 610 350 labeled with complete connecting and fixing accessories. Supply and Install different colored Power (socket) wires having 1.3.2 2*2.5mm2 size. Rating of 10 and 0.5killo wat loads capacity per phase. It shall includes: PCS 40 770 Junction Boxes Connectors Suply and fix different Socket outlets with all accessaries according 1.3.3 to the designs a) 16A single phase socket outlet point with wire 3 x 2.5mmsq, fixed Nº 55 420 300mm above finshed floor level, flush b) Surface/Flush Mounted 16A/3ph three phase Socket outlet Nº 6 500 1.4. LIGHT FIXTURES 1.4.1 Light fittings as specified below or approved equivalent a. Type 1 - MODUS BE140K1 /1 x 40W LAMP White painted (RAL 9003) metal sheet Nº 35 1300 id Power LED CRI 80 (CRI 90 on request Surface mounting b. Type 2 -PHILIPHS TCS 098 236 C3 with 2 x 36W lamp. Philips tms 012/236 I with 2xTld 36w/33 lamps'[0] 974 Lighting Control Panel With Coil, 120V, 60Hz, 3 Pole 480 Nº 24 1800 Philips TMS012/236 I with 2xTld 36w/33 lamps 401 PHILIPS TTCS 097 2xTL-D 36W/ 230 1071 PHILIPS TTCS 097 2xTL-D 36W/ 230 50 /50/C O. 96535893 Luminaires-Fluorescent 483 c. Type 3 -HIGH BAY LIGHT 200 W /6500 K SYM 100 BK Lighting Color: Pure White Led Model: SSK-UFO-80W Nº 47 2500 Lighting Type: LED Features: Lower Consumption & Energy Saving Replacement for High Voltage CFL & HD Lamps Wide Operating Volta 1.5. Power cables - Tenitative measurement 1.5.1 Actual mesurement shoud be on site - for all floor a) 2 x 2.5 mm sq., 10A m 350 b) 3*2.5 mm sq., 16A m 340 c) 4*2.5 mm sq., 3*10A m 100 d) 4*4 mm sq., 3*20A m 130 e) 4*6 mm sq., 3*32A m 65 f) 4*10 mm sq., 3*50A m 47 g) 4*16 mm sq., 3*63A m 10 h) 4*70/35 mm sq., 3*125A m 75 1.6. CABLE WAYS - Tenitative measurement It. DESCRIPTION Unit Qut Rate Amount 1.6.1 actual mesurement shoud be on site a) Rigid PVC pipe for heavy duty and of Dia 50mm m 426 450 b) Rigid PVC pipe for heavy duty and of Dia 32mm for all floor m 184 400 c) Rigid PVC pipe for heavy duty and of Dia 110mm m 130 550 1.7. Earthining Equipotential (Earthining) bonding copper bar 1500*50*10mm size 1.7.1 with bolted terminal RHS 4*20*20*2mm Electrode Bolt and Nuts pcs 6 420 Install 4*6 aq.mm sized Earthing cable, But the Actual mesurement 1.7.2 ml 51 600 shoud be on site - for all floor 1.8. Man Holes Construct manholes on specified locations having 60*60cm crossectional area and 70cm depth. The price shall includes 1.8.1 pcs 9 12500 excavation, manhole retailing wall (brick or block) construction, basing and toping concrete works all necessary materials