DESCRIPTION Unit Qut Rate Amount


1. ELECTRICAL INSTALLATION
Electrical wiring should be color coded and labeled
1.1 DISTRIBUTION BOARDS

Supply and install surface mounted metal enclousures type tested


Main distribution board MDB GROUND FLOOR factory built,
including busbars of 150A rating & 10KA/1sec, all other connecting
and fixing accessories for the system , all tested and wired torelevant
1.1.1
IEC standard, use DIN rail mounted terminal blocks with end
brackets and marking tags for all outgoings. 1pc factory made
drawing pocket, Himel PP-A4 or equivalent. all complete with 25%
Nº 1 19000
reserve spaces, and consisting of:-

1 Pc main RCBO of 125A, 3ph, 4poles - Ground Floor


2 Pc main RCBO of 20A, 3ph, 4poles - Ground Floor
1 Pc main RCBO of 32A, 3ph, 4poles - Ground Floor
1 Pc main RCBO of 50A, 3ph, 4poles - Ground Floor
1 Pc main RCBO of 63A, 3ph, 4poles - Ground Floor

Supply and install surface mounted metal enclousures type tested


Sub distribution board for GROUND FLOOR OFFICE factory built,
including busbars of 50A rating & 10KA/1sec, all other connecting
and fixing accessories for the system , all tested and wired torelevant
1.1.2
IEC standard, use DIN rail mounted terminal blocks with end
brackets and marking tags for all outgoings. 1pc factory made
drawing pocket, Himel PP-A4 or equivalent. all complete with 25% Nº 1 6000
reserve spaces, and consisting of:-

1 Pc main RCBO of 20A/3p, 4poles


4 Pcs RCBO of 16A/1p,3 pole
6 Pcs RCBO of 10A/1p,2 pole

Supply and install surface mounted metal enclousures type tested


Sub distribution board for FIRST FLOOR OFFICE factory built,
including busbars of 50A rating & 10KA/1sec, all other connecting
and fixing accessories for the system , all tested and wired torelevant
1.1.3
IEC standard, use DIN rail mounted terminal blocks with end
brackets and marking tags for all outgoings. 1pc factory made
drawing pocket, Himel PP-A4 or equivalent. all complete with 25% Nº 1 6000
reserve spaces, and consisting of:-

1 Pc main RCBO of 20A/3p, 4poles


4 Pcs RCBO of 16A/1p,3 pole
6 Pcs RCBO of 10A/1p,2 pole
Supply and install surface mounted metal enclousures type tested sub
distribution board for COLD ROOM 1 factory built, including
busbars of 50A rating & 10KA/1sec, all other connecting and fixing
accessories for the system , all tested and wired torelevant IEC
1.1.4
standard, use DIN rail mounted terminal blocks with end brackets
and marking tags for all outgoings. 1pc factory made drawing
pocket, Himel PP-A4 or equivalent. all complete with 25% reserve Nº 1 7500
spaces, and consisting of:-
1 Pc main RCBO of 32A/3p, 4poles
2 Pcs RCBO of 10A/3p,4 pole
3 Pcs RCBO of 16A/1p,3 pole
1 Pcs RCBO of 10A/1p,2 pole

Supply and install surface mounted metal enclousures type tested


Sub distribution board for COLD ROOM 2 factory built, including
busbars of 100A rating & 10KA/1sec, all other connecting and
fixing accessories for the system , all tested and wired torelevant IEC
1.1.5
standard, use DIN rail mounted terminal blocks with end brackets
and marking tags for all outgoings. 1pc factory made drawing
pocket, Himel PP-A4 or equivalent. all complete with 25% reserve Nº 1 9000
spaces, and consisting of:-

1 Pc main RCBO of 50A/3p, 4poles


2 Pcs RCBO of 10A/3p,4 pole
5 Pcs RCBO of 16A/1p,3 pole
1 Pcs RCBO of 10A/1p,2 pole

Supply and install surface mounted metal enclousures type tested


Sub distribution board for WAREHOUSE factory built, including
busbars of 100A rating & 10KA/1sec, all other connecting and
fixing accessories for the system , all tested and wired torelevant IEC
1.1.6
standard, use DIN rail mounted terminal blocks with end brackets
and marking tags for all outgoings. 1pc factory made drawing
pocket, Himel PP-A4 or equivalent. all complete with 25% reserve Nº 1 10000
spaces, and consisting of:-

1 Pc main RCBO of 63A/3p, 4poles


2 Pcs RCBO of 25A/3p,4 pole
3 Pcs RCBO of 16A/1p,3 pole
11 Pcs RCBO of 10A/1p,2 pole
1.2 LIGHT POINTS
For Flush installation in thermoplastic conduit of diammeter 16mm
1.2.1 fed through PVC conductors of 2 x 2.5sq.mm color coded and m 640 350
labeled with complete connecting and fixing accessories.
Supply and Install different colored lighting wires having 2*2.5mm2
1.2.2 size. Rating of 10 and 0.5killo wat loads capacity per phase. It shall
includes: PCS 60 520
Junction Boxes
Connectors
1.2.3 Switches
swiches 10A or 16A/1ph for flush/surface mounting
b) One way double gang - multi circuit switch,10A - flush mounted Nº 20 160
c) Two way single circuit switch, 10A - flush mountedwitch,220V 1 Nº 4 380
d) Thumbler single circuit switch, 16A - flush mountedwitch,220V 1 Nº 10 500
1.3 SOCKET OUTLETS POINTS
It. DESCRIPTION Unit Qut Rate Amount
For Flush installation in thermoplastic conduit of diammeter 16mm
1.3.1 fed through PVC conductors of 3x 2.5sq.mm color coded and m 610 350
labeled with complete connecting and fixing accessories.
Supply and Install different colored Power (socket) wires having
1.3.2 2*2.5mm2 size. Rating of 10 and 0.5killo wat loads capacity per
phase. It shall includes: PCS 40 770
Junction Boxes
Connectors
Suply and fix different Socket outlets with all accessaries according
1.3.3
to the designs
a) 16A single phase socket outlet point with wire 3 x 2.5mmsq, fixed
Nº 55 420
300mm above finshed floor level, flush
b) Surface/Flush Mounted 16A/3ph three phase Socket outlet Nº 6 500
1.4. LIGHT FIXTURES
1.4.1 Light fittings as specified below or approved equivalent
a. Type 1 - MODUS BE140K1 /1 x 40W LAMP
White painted (RAL 9003) metal sheet
Nº 35 1300
id Power LED CRI 80 (CRI 90 on request
Surface mounting
b. Type 2 -PHILIPHS TCS 098 236 C3 with 2 x 36W lamp.
Philips tms 012/236 I with 2xTld 36w/33 lamps'[0] 974
Lighting Control Panel With Coil, 120V, 60Hz, 3 Pole 480 Nº 24 1800
Philips TMS012/236 I with 2xTld 36w/33 lamps 401
PHILIPS TTCS 097 2xTL-D 36W/ 230 1071
PHILIPS TTCS 097 2xTL-D 36W/ 230 50 /50/C O. 96535893 Luminaires-Fluorescent 483
c. Type 3 -HIGH BAY LIGHT 200 W /6500 K SYM 100 BK
Lighting Color: Pure White
Led Model: SSK-UFO-80W
Nº 47 2500
Lighting Type: LED
Features: Lower Consumption & Energy Saving Replacement for
High Voltage CFL & HD Lamps Wide Operating Volta
1.5. Power cables - Tenitative measurement
1.5.1 Actual mesurement shoud be on site - for all floor
a) 2 x 2.5 mm sq., 10A m 350
b) 3*2.5 mm sq., 16A m 340
c) 4*2.5 mm sq., 3*10A m 100
d) 4*4 mm sq., 3*20A m 130
e) 4*6 mm sq., 3*32A m 65
f) 4*10 mm sq., 3*50A m 47
g) 4*16 mm sq., 3*63A m 10
h) 4*70/35 mm sq., 3*125A m 75
1.6. CABLE WAYS - Tenitative measurement
It. DESCRIPTION Unit Qut Rate Amount
1.6.1 actual mesurement shoud be on site
a) Rigid PVC pipe for heavy duty and of Dia 50mm m 426 450
b) Rigid PVC pipe for heavy duty and of Dia 32mm for all floor m 184 400
c) Rigid PVC pipe for heavy duty and of Dia 110mm m 130 550
1.7. Earthining
Equipotential (Earthining) bonding copper bar 1500*50*10mm size
1.7.1
with bolted terminal
RHS 4*20*20*2mm
Electrode
Bolt and Nuts pcs 6 420
Install 4*6 aq.mm sized Earthing cable, But the Actual mesurement
1.7.2 ml 51 600
shoud be on site - for all floor
1.8. Man Holes
Construct manholes on specified locations having 60*60cm
crossectional area and 70cm depth. The price shall includes
1.8.1 pcs 9 12500
excavation, manhole retailing wall (brick or block) construction,
basing and toping concrete works all necessary materials