DOCUMENT / DESIGN REVIEW - Any special purpose power outlet for IT racks to be supplied from a dedicated
circuit, i.e one circuit per equipment.
A - Approved - Construction / Fabrication / installation may be undertaken. - The panel form, IP, IK and SC ratings shall be as per project specs.
B - Approved as noted - Approval does not authorize changes in contract sum or contract time.
- Panel mounting and cable entry shall be as per approved power layout.
C - Revise and Resubmit - Construction / Fabrication / installation may not be undertaken. - Refer and comply with project specs and tender requirements.
D - Rejected - In resubmitting, limit corrections to the items marked.
#-a. Lighting: DF=1.0 as per tender documents.
- Dar Al Riyadh approval of submitted item is not required or the submittal is not
E - Not reviewed complying with contract requirements b. Sockets: DF=0.5 this factor can be adjusted based on the type of building.
Architecture Interior Design Civil Electrical Survey c. HVAC to be divided to two subcategories (A/C: DF=0.7 and Ex. Fan: DF=1.0).
Squad Checking:
Mechanical Structural Telecom Landscape d. EWH: DF=0.65 as proposed in tender documents.
Reviewed By : A.M Date: 06-12-2023 e. Kitchen and laundry equipment: DF=0.65 as proposed in tender documents.
Disclaimer: f. LC systems: DF=0.90.
1. Review and approval are for conformance with the information given and the design concept of the Project as
expressed in the Contract Documents. #- Contract should be correct some missing and errors in calculation.
îX˘„oZ]LjZ„˚À]˚Ávˆ››„}Ào}(ıZ˚}vı„ı}„[’’µu]ııo’’Zoov}ı„˚o]˚À˚ıZ˚}vı„ı}„(„}uvÇ}o]Pı]}v #- All EAF. shall be controlled thru contactor to BMS connection
contained in the Contract Documents.
Consider the following lengths as a guidance and revise the PB sch accordingly:-
3. No responsibility is assumed for accuracy or completeness of submittal dimensions, quantities or details.
4. The Contractor is responsible to field verify all dimensions prior to fabrication, Construction or installation. #- For 16A, C type MCB (50 m for 2.5 mm2, 80 m for 4 mm2, 120m for 6 mm2)
5. Coordinate with all adjacent and/or related contractors, disciplines, other equipment and materials. #- For 20A, C type MCB (40 m for 2.5 mm2, 65 m for 4 mm2, 95m for 6 mm2)
6. Respond to and address all previous comments from Dar Al Riyadh.
7. Comply with the requirements of all required approving authorities and obtain timely approval/consent as necessary.
FOC tagging to be done in accordance
#- For 32A, C type MCB (25 m for 2.5 mm2, 40 m for 4 mm2, 60m for 6 mm2)
#-Any power circuit shall not less than 4 mm2, for AC shall not less than 6 mm2.
with DCIT Standard for labeling.
#-Minimum cable CSA to feed the final distribution panel should not less than
4x10mm2.
Revise ;All load is single load #-Any special purpose socket outlet to be supplied from a dedicated circuit, i.e one
circuit per equipment.
#-All indicated ratings of the electromechanical equipment is a contractor
responsibility and shall be as per approved material.
Revise ;All load is single load #-Any change in DB schedule (circuit no.) shall be reflected to circuit .layout.
#-K- curve shall be used for all motor loads
#Coordinate with other disciplines.
#-Follow project technical documents.
#-Follow previous comments.
RCD
RCD
RCD
RCD
2-1x6+6mm2
RCD
RCD
RCD RCD
RCD RCD
RCD RCD
RCD
RCD
RCD
ü
☐ B - Approved as noted
☐ C - Revise and Resubmit
- Approval does not authorize changes in contract sum or con