You are on page 1of 2

Classified as Confidential Internal by SEC - )‫داخل‬ ‫ر‬

( ‫الشكة السعودية للكهرباء مصنف مقيد‬


‫ي‬

INTERNAL CORRESPONDENCE

FACTS Projects Division Manager Office


Office Address: SEC HQ, Al-Arid, Riyadh, Tower C, Floor 3
Tel: 011-807-7447, E-mail: BMSsuhaibani@se.com.sa

Project: Installation of DRPC at Wadi Dawasir 380kV BSP

Contract No. 4400016409 Signed Date: 17-Feb-2022 TCC Date: 17-Apr-2024


Contractor: AL GIHAZ CONTRACTING CO.

Our Reference No. 12063501 - 1273 - 23 Date: 16-Apr-2023

TO: Projects Department - South

Attention: Engr. Saad H. Al Umar Mail


EHV Group Leader E-Mail 1: SHUmar@se.com.sa
E-Mail 2: SIElwan@se.com.sa

Your Ref. No. DTS- 235 REV-02


Date: 12-Apr-2023
Subject: Indoor & Outdoor lighting Single line diagram & Branch Cable Sizing
Received As: Original Copy FAX Copy E-mail Copy

Contractor Ref. No. AG-SEC-4400016049-DTS-235- Rev-02


Date: 12-Apr-2022
Submittal is: New Revised Revision No. 2
Including: Only Letter Hard Copy, No. of Folders Soft Copy, No. of CD

We received it on: 12-Apr-2023 and registered under ref. no. by

Kindly be informed that the received submittal has been reviewed and below is our conclusion for your information, record and futher necessary
action:
A_Acceptable

B_Acceptable as Noted (No need to Resubmit)

C_Uncompleted and need further data to be evaluated with the received submittal (Need to Resubmit)

D_Rejectedfor the attached mentioned reason(s)

E_No action needed from our Division

F_Need a meeting to discuss the attached agenda with: Manufacturer Contractor SEC/NG Departments
Review of this submittal is for general conformamnce with SoW/PTS of this project.
This review does not relieved the contractor from responsibility of full compliance with the contract documents.
If the status is "C" or "D" or "F" , We expect to received your positive response to this letter no later than Seven (7) days
from the received date to close this project technically together within the target date

If you need any further clarification on this subject, please call Mr. Mansoor Asif 013 82 89381

Regards,

Reviewed by: MAH/RSD


Basem M. Al-Suhaibani

Manager, FACTS Projects Division


cc: Project File

Form 1: General Response to Submittals_2023_R0


Classified as Confidential Internal by SEC - )‫داخل‬ ‫ر‬
( ‫الشكة السعودية للكهرباء مصنف مقيد‬
‫ي‬
Classified as Confidential Internal by SEC - ) ‫داخل‬ ‫ر‬
( ‫الشكة السعودية للكهرباء مصنف مقيد‬
‫ي‬

FACTS Projects Division


Attachment of Letter # 12063501 - 1273 - 23 Dated
16-Apr-2023
CN #: 4400016409
Subject: Indoor & Outdoor lighting Single line diagram & Branch Cable Sizing
Sr. FACTS Comments on Submittal (Rev. 00) Contractor's Response (Rev. 01) FACTS Comments on Submittal (Rev. 01) Contractor's Response (Rev. 02) FACTS Comments on Submittal (Rev. 02)
OUTDOOR LIGHTING & SMALL POWER SINGLE LINE
1 DIAGRAM.
DRAWING NO.SA-218547 REV-00 SHTS-01.
1.1 Mention MCCB rating of Q4.09. Complied & Updated, Kindly Refer to the revised Drawing. Noted.

Kindly Be informed that it will be as the manufacture recommendation & added to


1.2 Write rating of fuse shown. Noted.
legend kindly refer to the revised drawing

Indicate OLP panel designation as shown in Control Room


1.3 Kindly Note That Panel designation in Control Room as mentioned here. Noted.
panels layout drawing.

1.4 Write Sh. Ckt Current rating unit as 'kA' instead of 'KA'. Complied & Updated, Kindly Refer to the revised Drawing. Noted.

OUTDOOR LIGHTING & SMALL POWER SINGLE LINE DIAGRAM.


DRAWING NO.SA-218547 REV-01 SHTS-01 :
1.5 Complied & Updated Kindly refer to the revised drawings Noted
As per TES-P-119.30 REV 02, Figure 30-2, Lighting & Receptacle Panels shall have
two incommers with ATSS. Please Comply.

2
INDOOR LIGHTING & SMALL POWER SINGLE LINE DIAGRAM.
DRAWING NO.SA-218542 REV-00 SHTS-01.

Kindly Be informed that it will be as the manufacture recommendation & added to


2.1 Write rating of fuse shown in SLD of ILP-01 & ELP. Noted.
legend kindly refer to the revised drawing

Indicate ILP-01 & ELP panel designations as shown in Control


2.2 Kindly Note That Panel designation in Control Room as mentioned here. Noted.
Room panels layout drawing.

2.3 Show Contol Circuit of Contactor K. Complied & Added, Kindly Refer to the revised Drawing. Noted.

2.4 Write Sh. Ckt Current rating unit as 'kA' instead of 'KA'. Complied & Updated, Kindly Refer to the revised Drawing. Noted.

INDOOR LIGHTING & SMALL POWER SINGLE LINE DIAGRAM.


DRAWING NO.SA-218542 REV-01 SHTS-01 : As per TES-P-119.30 REV 02, Figure 30-
2.5 Complied & Updated Kindly refer to the revised drawings Noted
2, Lighting & Receptacle Panels shall have two incommers with ATSS. Please
Comply.

NORMAL & EMERGENCY LIGHTING LAYOUT & DETAILS.


3
DRAWING NO. SA-218538 REV-01A SHTS-03.

Complied & Added Kindly refer to detail-12 in the revised drawing of the
mentioned submittal (every lighting fixture has RGS CONDUIT CONTAINS (3 WIRES)
3.1 Noted.
PHASE, NEUTRAL & EARTHING CONDUCTORS AT WHICH EARTHING WIRE WILL BE
CONNECTED TO THE BODY OF THE LIGHTING FIXTURES INTERNALY)
In sheet 03, show grounding detail of a typical light fixture.
BRANCH CABLE SIZING FOR INDOOR LIGHTING. DRAWING
4 To be revised as per 2.5 above. Complied & Updated Kindly refer to the revised Calculations Noted
NO.SE-218551 REV-00 SHTS-14.

4.1 Noted. -
BRANCH CABLE SIZING FOR OUTDOOR LIGHTING. DRAWING
5 To be revised as per 1.5 above. Complied & Updated Kindly refer to the revised Calculations Noted
NO.SE-218552 REV-00 SHTS-06.

5.1 Noted. -