You are on page 1of 6

TECHNICAL SUBMITTAL

Submittal Reference #: SAC-0862-T-MAR-ME-0012-01 Date:29-06-2021

Project Name: 21MW Standby Diesel Power plant Contractor: Sim Arabia Company Ltd

RAC Project Manager: Mr. Misbah Khan Consultant: WSP

Submittal Details (by the Contractor)


Type of Submittal:
☒ Material ☐ Shop Drawings ☐ Design Drawings ☐ Test Report ☐ Manufacturer’s Data
☐ Method Statement ☐ Prequalification ☐ As- Built Drawings ☐ Sample ☐ Catalogues
☐ Others:
Discipline:
☐ Architectural ☐ Civil/ Structure ☒ Mechanical ☐ Electrical ☐ Project Controls ☐ General

Submittal Description:

# Description Revision # Date Copies

1 Material Submittal for “ Sprinklers, as per mentioned Model” 00 29-06-2021

Model B-1 — 3.0 K-factor Upright and Pendent Foam-Water Sprinklers

For the Contractor: THAMARAI KANNAN Designation: PM Sign & Stamp:

Documents Review (by RAC’s Execution Team)


☐ Accepted ☐ Rejected

Reviewed by: Date: Signature:

Technical Review (by RAC’s Engineering Team)


☐ A: Approved ☐ B: Approved as Noted ☐ C: Revise & Resubmit ☐ D: Rejected

Consultant: Date: Signature:

Discipline Engineer: Date: Signature:

Approval shall not relieve Contractor of his liabilities under the Contract or constitute authorization of any change to Contract Documents.

TECHNICAL SUBMITTAL FORM Page 1 of 1


TECHNICAL SUBMITTAL

Date:05-12-2020

Project Name: 21MW Standby Diesel Power plant Contractor: Sim Arabia Company Ltd

RAC Project Manager: Mr. Misbah Khan Consultant: WSP

Material Shop Drawings Design Drawings Test Report


Method Statement Prequalification As- Built Drawings Sample Catalogues
Others:

Architectural Civil/ Structure Mechanical Electrical Project Controls General

# Description Revision # Date Copies

1 Material Subm Fittings, Valves, Sprinklers, FHC, 00 05-12-2020


FDC, Extinguishers

For the Contractor: THAMARAI KANNAN Designation: PM Sign & Stamp:

Accepted Rejected

Abdelghany Abdelaal 6-12-2020 Abdelghany

A: Approved B: Approved as Noted C: Revise & Resubmit D: Rejected

Abdulaziz 10.12.2020
Worldwide
www.tyco-fire.com
Contacts

Model B-1 — 3.0 K-factor


Upright and Pendent
Foam-Water Sprinklers
General in addition to the standards of any other
authorities having jurisdiction. Failure
Description to do so may impair the performance
of these devices.
TYCO Model B-1 Upright and Pendent The owner is responsible for main-
Foam-Water Sprinklers are air-aspirat- taining their fire protection system
ing foam discharge outlets designed and devices in proper operating con-
for use in foam-water deluge systems. dition. Contact the installing contrac-
They are designed for flammable liquid tor or product manufacturer with any
risks where it is desired to apply foam questions.
from overhead sprinklers (either upright
or pendent) and where follow-up with
plain water in a standard spray sprin-
Technical
kler pattern is necessary as in the case
of NFPA 16, “Standard for the Instal- Data
lation of Foam-Water Sprinkler and Approvals
Foam-Water Spray Systems.” UL and ULC Listed
It is recommended that the end user
be consulted with respect to the suit-
Discharge outlets and foam concentrates
are Listed for use together. Refer to the
Operation
ability of the materials of construction individual foam concentrate Listing for TYCO Model B-1 Foam-Water Sprin-
for any given corrosive environment. operating limitations and compatibility klers are designed with a unique ven-
The effects of ambient temperature, with the B-1 Foam-Water Sprinklers turi-style body. As foam solution (water
concentration of chemicals, and gas/ as provided in the UL Fire Protection and foam concentrate mixture) flows
chemical velocity, should be consid- Equipment Directory. through the inlet of the body, air is
ered, at a minimum, along with the cor- The Model B-1 Upright and Pendent drawn into the body through the open-
rosive nature to which the sprinklers Foam-Water Sprinklers meet the ings adjacent to the wrenching area.
may be exposed. requirements of: The foam solution and air mix is then
agitated to create an air-aspirated
The Model B-1 Foam-Water Sprinkler is MIL-S-901C foam.
a redesignation for the Gem Issue B-1 (for light-weight Grade A shock-proof
and Star Model B-1 Sprinklers. equipment) The B-1 Foam-Water Sprinklers are
designed to discharge foam in a pre-
MIL-H-24146
NOTICE determined discharge pattern, as well
Maximum Working Pressure as to discharge water similar to stan-
The Model B-1 Foam-Water Sprinklers 175 psi (12,1 bar) dard spray sprinklers. To meet the
described herein must be installed and intent of NFPA 16, foam-water sprin-
maintained in compliance with this Discharge Coefficients
K=3.0 GPM/psi½ (43,2 LPM/bar½)
klers must be able to sufficiently dis-
document, as well as with the applica- tribute water after depletion of the foam
ble standards of the NATIONAL FIRE Thread Connection concentrate.
PROTECTION ASSOCIATION (NFPA), 1/2 in. NPT
Finish
Natural Bronze
IMPORTANT
Refer to Technical Data Sheet Physical Characteristics
TFP2300 for warnings pertaining to Body ���������������������������������������������������������Bronze
Deflector �����������������������������������������������������Brass
regulatory and health information. Agitator �������������������������������������������������������Brass
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Page 1 of 4 AUGUST 2018 TFP840


TFP840
Page 2 of 4

2-1/8" DIA. WRENCHING


(54,0 mm) AREA 1"
DEFLECTOR 1/2" (25,4 mm)
NPT ACROSS
WRENCH
FLATS
BODY
7/16"
(11,1 mm) 3/8" DIA.
5-13/16" NOMINAL (9,5 mm)
(147,6 mm) MAKE-IN

AGITATOR
AGITATOR

7/16" 5-15/16"
(11,1 mm) 3/8" DIA. (150,8 mm)
NOMINAL (9,5 mm)
MAKE-IN
BODY
1"
(25,4 mm)
1/2" ACROSS
NPT WRENCH DEFLECTOR
WRENCHING FLATS 2-1/8" DIA.
AREA (54,0 mm)

UPRIGHT PENDENT
FIGURE 1
MODEL B-1 FOAM-WATER UPRIGHT AND PENDENT SPRINKLERS
NOMINAL DIMENSIONS

Design The applied density (flow per unit of


area) of foam solution must meet the Installation
Criteria requirements of the authority having
jurisdiction for the type flammable
TYCO Model B-1 Foam-Water Sprin-
klers must be installed in accordance
TYCO Model B-1 Upright and Pendent liquid and occupancy. Per NFPA 16, with this section.
Foam-Water Sprinklers are intended coverage density must not be less
than 0.16 gpm/ft² (6,52 mm/min) of General Instructions
for fire protection systems designed in
floor area with a resulting minimum Obtain a leak-tight 1/2 in. NPT sprin-
accordance with the standard instal-
discharge pressure of not less than kler joint by applying a minimum-to-
lation rules for foam-water sprinklers
30 psi (2,1 bar). maximum torque of 7 to 14 ft-lb (9,5 to
systems recognized by the applicable
19,0 N∙m). Higher levels of torque may
Listing agency (e.g., UL Listing is based Foam-water sprinkler spacing must
distort the sprinkler inlet and cause
on the requirements of NFPA 13 and not exceed the requirements of NFPA
impairment of the sprinkler.
16). 13 for extra hazard occupancies and
Graph A provides the nominal dis- the system must be hydraulically cal- Upright and Pendent Sprinklers
charge patterns for reference use. culated to obtain the required density Note: Pendent sprinklers are to be
and discharge pressure. installed in the pendent position;
Note: The discharge patterns shown in upright sprinklers are to be installed in
Graph A are not to be used for design Note: Discharge outlets and foam con-
centrates are listed for use together. the upright position.
purposes or to disregard standard
installation rules. Refer to the individual foam concen- Step 1. With pipe thread sealant
trate listing for operating limitations and applied to the pipe threads, hand
Not less than two (2) foam-water sprin- compatibility with the B-1 Foam-Water tighten the sprinkler into the sprinkler
klers are to be installed in any area, Sprinklers as provided in the UL Fire fitting.
regardless of size, in order to obtain Protection Equipment Directory.
pattern overlap. Step 2. Tighten the sprinkler into the
sprinkler fitting using an 8 in. or 10 in.
adjustable wrench. With reference to
Figures 1 and 2, the adjustable wrench
is only to be applied to the wrench flats
of the wrenching area.
TFP840
Page 3 of 4

DATA KEY
WATER DISCHARGE FOAM DISCHARGE
8 or 10 INCH
RADIUS, METERS RADIUS, FEET ADJUSTABLE
3,0 2,0 1,0 0 2 4 6 8 10 WRENCH
0 0

DISTANCE BELOW
DISTANCE BELOW
CEILING, METERS

0,5
2

CEILING, FEET
APPLY TO
1,0 WRENCH
4 FLATS
1,5 ONLY
6
2,0

8 FIGURE 2
2,5
UPRIGHT WRENCH FLATS
RADIUS, METERS RADIUS, FEET

0
3,0 2,0 1,0 0 2 4 6 8 10
0
Limited
Warranty

DISTANCE BELOW
DISTANCE BELOW
CEILING, METERS

0,5
2

CEILING, FEET
For warranty terms and conditions, visit
1,0 www.tyco-fire.com.
4
1,5
6
Ordering
2,0
Procedure
2,5 8 Contact your local distributor for avail-
PENDENT
ability. When placing an order, indi-
GRAPH A cate the full product name, including
NOMINAL DISCHARGE PATTERNS description and part number (P/N).
(SHOWN FOR REFERENCE ONLY — NOT SUITABLE FOR DESIGN PURPOSES)
Upright Foam-Water Sprinklers
Specify: Model B-1 Upright Foam-
Care and Frequent visual inspections are recom-
mended to be initially performed for
Water Sprinkler, P/N 49-210-1-001

Maintenance sprinklers installed in potentially cor-


rosive atmospheres to verify the integ-
Pendent Foam-Water Sprinklers
Specify: Model B-1 Pendent Foam-
rity of the materials of construction as Water Sprinkler, P/N 49-211-1-001
TYCO Model B-1 Foam-Water Sprin-
klers must be maintained and serviced they may be affected by the corrosive
in accordance with this section. conditions present for a given installa-
tion. Thereafter, annual inspections per
Before closing a fire protection system NFPA 25 are required.
control valve for maintenance work on
the fire protection system that it con- The owner is responsible for the inspec-
trols, permission to shut down the tion, testing, and maintenance of their
affected fire protection system must fire protection system and devices in
be obtained from the proper authorities compliance with this document, as well
and all personnel who may be affected as with the applicable standards of the
by this action must be notified. NATIONAL FIRE PROTECTION ASSO-
CIATION (e.g., NFPA 25), in addition to
Model B-1 Foam-Water Sprinklers the standards of any other authorities
must never be painted, plated, coated having jurisdiction. Contact the install-
or altered in any way after leaving the ing contractor or product manufacturer
factory; otherwise, the spray perfor- with any questions.
mance may be impaired.
It is recommended that foam-water
Care must be exercised to avoid sprinkler systems be inspected, tested,
damage to the sprinklers before, and maintained by a qualified Inspec-
during, and after installation. Sprin- tion Service in accordance with local
klers damaged by dropping, striking, requirements and/or national codes.
wrench twist/slippage, or the like, must
be replaced.
TFP840
Page 4 of 4

1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association