CALCULATION
CRUDE OIL STORAGE TANK SIZING
9-Nov-21 DC
TOTAL OR PARTIAL REPRODUCTION AND/OR UTILISATION OF THIS DOCUMENT ARE FORBIDDEN WITHOUT PRIOR WRITTEN
AUTHORIZATION OF THE OWNER
DOCUMENT NO
EMP MALACCA STRAIT S.A
SEL-TBD-O-CA-003
REVISION STATUS
PT LOKA WAHANA USAHA
0 IFD
CRUDE OIL STORAGE TANK
CALCULATION
TABLE OF CONTENT
1. INTRODUCTION ................................................................................................................ 3
2. OBJECTIVE ....................................................................................................................... 3
3. TERMINOLOGY AND ABBREVIATIONS.......................................................................... 3
3.1 Terminology........................................................................................................................ 3
3.2 Abbreviations ..................................................................................................................... 4
4. REFERENCE ..................................................................................................................... 5
5. FACILITY DESCRIPTION .................................................................................................. 5
6. BASIS AND ASSUMPTION ............................................................................................... 5
6.1 Design Capacity ................................................................................................................. 5
6.2 Operating Condition........................................................................................................... 5
7. METHODOLOGY AND CRITERIA .................................................................................... 6
7.1 Tank Dimension ................................................................................................................. 6
7.2 Inbreathing and Outbreathing Capacity ........................................................................... 6
8. RESULT ............................................................................................................................. 8
1. INTRODUCTION
MSTB production field is located in Desa Tanjung, Kecamatan Tebing Tinggi Barat, Kabupaten
Kepulauan Meranti. Currently fluid transfer is carried out via barging from MSTB to FSO Gandini/Kurau
Plant. Wells currently operating are MSTB-01, MSTB-02, MSTB-03, MSTB-05, MSTB-06, MSTB-08,
MSTB-09 with production rate of around 1,900 BFPD and BSW ranges between 1.00-56.00% (based
on Production Daily Report 18 November 2019).
MSTB-01 is part of a scattered discovery in the eastern region of the Malacca Strait, which is located
in the inland area onshore in the Ringgit area and the surface conditions are swampy. The eastern
region of Malacca Strait is quite far from existing production facilities.
Along with the MSTB field development program, efforts will be made to increase production capacity
by carrying out a series of drilling programs with the target of increasing production to 4,500 BFPD
from MSTB Field, and 4,000 BFPD from Ringgit Field.
2. OBJECTIVE
The objective of this document is to presents optimum crude oil storage tank dimension including
venting device dimension on the crude oil tank for the MSTB and MSAI Facility. The physical properties
of the fluid is taken from the process simulation results document.
3.1 Terminology
SUBCONTRACTOR Party who provides services to perform part of the contractual scope
of work on behalf of CONTRACTOR
VENDOR Party who supplies and manufactures equipment / materials or
services part of the contractual scope of work
Shall Means absolute requirement to be followed strictly in order to
conform the strategy
Should Means recommendation, that alternative solutions having the same
functionality and quality are acceptable
May Means course of action that is permissible within the limits of the
philosophy (permission)
3.2 Abbreviations
API American Petroelum Institute
BFPD Barrel Fluid per Day
BoD Basis of Design
BOV Botton of Vessel
LIAHH High High Interface Level
LAHH High High Liquid Level
LIAH High Interface Level
LAH High Liquid Level
NIL Normal Interface Level
NLL Normal Liquid Level
LIAL Low Interface Level
LIALL Low Low Interface Level
LAL Low Liquid Level
LALL Low Low Liquid Level
MMscfd Million standard cubic feet per day
MW Molecular Weight
P&ID Piping and Instrumentation Diagram
PFD Process Flow Diagram
POD Plan of Development
TBA To be announced
CRUDE OIL STORAGE TANK
CALCULATION
4. REFERENCE
5. FACILITY DESCRIPTION
Fluid from MSTB wells is transferred through flowlines with a size of 4” with varying lengths to MSTB
Production Facility. Fluid from the Production Manifold flows to the Crude Oil Storage Tank (T-701D/E),
while the fluid from the Test Manifold is routed to the Test Separator to separate Gas, Oil and Water.
The Test Separator outlet gas flows to the KO Drum and Venting System. Oil and Water from the Test
Separator are routed to the Storage Tank.
From Crude Oil Storage Tank (T-701D/E), the fluid is pumped to MSAI facility via 32 km long 4” & 6”
pipeline. In addition to the pumping process, the fluid is also heated by Crude Oil Heater so that the
fluid temperature remains above the pour point when it arrives at MSAI.
At MSAI Facility (Selatan Field), the fluid is stored in a Storage Tank (T-801) before transferred to
Kurau Plant. From Crude Oil Storage Tank, the fluid is heated in order to keep the fluid temperature
remains above the pour point when it arrives at Kurau Facility. Fluid is then pumped from MSAI Facility
to Kurau Facility through the existing 12” pipeline along 27 km.
Crude Oil Storage Tank will be equipped with venting system. The venting requirement should be sized
to anticipate required venting condition. The venting scenario which considered to be calculate are normal
venting, liquid movement, and thermal effect.
Crude Oil Storage Tank will also be equipped with immersed heater to maintain the fluid temperature at
100 oF
The tank sizing calculation is performed with In-house vessel calculation spreadsheet. The methodology
based on API STD 2000 is applied to select the proper pressure and vacuum relief size based on the tank
service condition and flow requirement.
In-house venting requirement spreadsheet for atmospheric tank based on API 2000 is also used to
performed tank venting calculation.
Tank working capacity is liquid volume between minimum operating liquid level (LLL) and maximum
operating liquid level (HLL). The required working capacity for new Crude Oil Storage Tank at MSTB and
MSAI has been determined as 5,000 BBL refer to the latest production profile flowrate with some margin.
As limiting criteria, the height – diameter ratio of the Tank should be equal to or less than 1 (H/D < 1).
Tank dimension is determined based on Table A.1b of Annex A in API STD 650, 12th edition.
Minimum height between center line of outlet nozzle and bottom of tank is determined based on Table
5-6, API STD 650, 12th edition. Outlet nozzle type is assumed as regular type.
Crude Oil Storage Tank is assumed to be designed to use 72-inch height courses.
Basis for calculating outbreathing and inbreathing capacity:
- Crude Oil Storage Tank is not insulated
- MSTB Facility is located in Indonesia. Hence, belongs to latitude below 42°.
- Operating temperature of Crude Oil Storage Tank is refer to Process Simulation Report
- Vapor pressure of crude oil is 0.2 psi (at 100 °F) based on laboratory analysis.
7.1 Tank Dimension
Crude Oil Storage Tank and Diesel Oil Storage Tank are cylindrical tanks where the volume is
calculated based on this equation:
Where:
V : Tank volume
D : Tank diameter
H : Tank height
7.2 Inbreathing and Outbreathing Capacity
Inbreathing and outbreathing calculation refers to API STD 2000, 7th edition.
Where:
Vip : Inbreathing venting Requirement (SCFH)
Vpe : maximum rate of liquid discharging (GPM)
Vop : outbreathing volumetric flowrate (ACFH)
Vpf : maximum volumetric filling rate (GPM)
Inbreahting capacity calculation due to thermal effect is calculated using these equations:
Outbreahting capacity calculation due to thermal effect is calculated using these equations:
Where
VOT : Thermal outbreathing apacity (SCFH)
VIT : Thermal inbreathing capacity (SCFH)
C : Factor that depends on vapor pressure, average storage temperature and latitude (see
Table 6.2)
Y : Factor for latitude
Vtk : Tank volume (ft3)
Ri : Reduction factor for insulation (Ri = 1 if no insulation)
Table 7.2 – Y-Factor for Various Latitudes
Latitude Y-Factor
8. RESULT
The working capacity for the Crude Oil Storage Tank of MSTB and MSAI is 5000 BBL based on production
profile with safety margin. Working capacity is liquid volume between Low Liquid Level (LLL) and High
Liquid Level (HLL).
The tank dimension is determined based on Table A.1b of Annex A in API STD 650, 12th edition. Crude
Oil Storage Tank is assumed to be designed to use 72-inch height courses.
Table 8.1 – Nominal Capacities (barrels) for Tanks API STD 650
Refer to Table A.1b API STD 650, by considered dead volume and vapor space area, the selected
nominal volume for the MSTB and MSAI Crude oil tank is 6300 BBL with 50 ft (ID) x 18 ft (Height).
The Crude Oil Storage Tank sizing result is summarized on the following table. Detailed calculation can
be found on Attachment-A.
CRUDE OIL STORAGE TANK
CALCULATION
MSTB Crude Oil Storage Tank MSAI Crude Oil Storage Tank
Description
(T-701D/E) (T-801)
Dimension 50 ft (ID) x 18 ft (Height) 50 ft (ID) x 18 ft (Height)
Low-Low Liquid Level (LLLL) 306 mm 406 mm
Low Liquid Level (LLL) 606 mm 606 mm
High Liquid Level (HLL) 4958 mm 4958 mm
High-High Liquid Level (HHLL) 5079 mm 5086 mm
Working Volume 5000 bbl 5000 bbl
0
Total Volume 6300 bbl 6300 bbl
Holding Time 1.2 day 0.6 day
Inlet Flow 4175 BPD 8000 BPD
Outlet Flow 4175 BPD (122 USGPM) 8000 BPD (234 USGPM)
Inlet Nozzle 4” 6”
Outlet Nozzle 4” 6”
Pump Circulation Nozzle 4” 6”
Design Pressure Full of Water Full of Water
Design Temperature 200 oF 200 oF
The venting requirement during normal is summarized in the following table. Detail calculation can be
found on Attachment A.
Table 8.3 – Venting of Crude Oil Storage Tank Summary Result
The bund wall dimension for each crude oil storage tank is summarized in the following table. Detail
calculation can be found on Attachment A.
Table 8.4 – Bund Wall Dimensions
Equipment Dimension
MSTB Crude Oil Storage Tank (T-701 D) 30 m (L) x 30 m (W) x 1.4 m (H)
MSTB Crude Oil Storage Tank (T-701 E) 30 m (L) x 30 m (W) x 1.4 m (H)
MSAI Crude Oil Storage Tank (T-801) 30 m (L) x 30 m (W) x 1.4 m (H)
CRUDE OIL STORAGE TANK
CALCULATION
1. Refer to API standard 650: 50 ft(ID ) and 18 ft(H) is 6300 bbl tank volume
Properties Liquid
Temperature C 37.78 100.00 F
Pressure kg/cm2 1.03 0.00 psig ```````
Mass Density kg/m3 864.10 53.94 lb/ft3
Viscosity cP 24.79
Specific Gravity 0.86
Molecular Weight 155.90
Note:
H1 is based on common practice of ideal distance from top tangent to centre of circulate nozzle which is 4 x nozzle diameter
H2 is estimated by considering working capacity required and also considering required time for liquid to reach High High Level for Operator response time
H3 is based on common practice with minimum distance 150 mm and also considering required time for liquid to reach Low Low Level (Operator response time)
H4 is based on Table 5-6a in API 650
3
Working Capacity is from NLL to HLL = 795 m
= 5,000 barrel
(Non-Volatile Liquid Vap. Press ≤ 0.73 psi, Liquid Vap Pressure is 0.2 psi)
Inflow of liquid into the Tank (liquid movement in) = 4175.0 BPD from Production Profile
= 121.8 USGPM
Outbreathing Flowrate = 976.7 ACFH
= 906.96 SCFH
Outflow of liquid from the Tank (liquid movement out) = 4175.0 BPD ---> 1 x 100% Crude Oil Transfer Pump Running
= 121.8 USGPM
Inbreathing Flowrate = 976.7 SCFH
2. Thermal Inbreathing/Outbreathing
Tank Volume (Critical height/Overflow to bottom), Vtk = 35372.0 ft3
Thermal Outbreathing
Equation (8) from API STD 2000 7th edition, March 2014
Y Factor for the latitude = 0.3 Table 1 API STD 2000 7th edition, March 2014 (Plant is located in Indonesia)
Ri The reduction factor for insulation = 1.0 (no insulation)
Thermal Outbreathing Flowrate = 5996.8 SCFH
Thermal Inbreathing
Equation (10) from API STD 2000 7th edition, March 2014
C Factor = 6.5 Table 2 API STD 2000 7th edition, March 2014 Thermal Inbreathing Flowrate
= 30586.2 SCFH
RESULT Selected Bund Wall Size : 30.0 m (L) x 30.0 m (W) x 1.4 m (H)
CALCULATION NOTE
1. Refer to API standard 650: 50 ft(ID ) and 18 ft(H) is 6300 bbl tank volume
Properties Liquid
Temperature C 37.78 100.00 F
Pressure kg/cm2 1.03 0.00 psig ```````
Mass Density kg/m3 874.60 54.60 lb/ft3
Viscosity cP 32.48
Specific Gravity 0.87
Molecular Weight 92.32
Note:
H1 is assumed 400 mm height due to limited height, since the residence time is still adequate for operator response
H2 is estimated by considering working capacity required and also considering required time for liquid to reach High High Level for Operator response time
H3 is based on common practice with minimum distance 150 mm and also considering required time for liquid to reach Low Low Level (Operator response time)
H4 is based on Table 5-6a in API 650
3
Working Capacity is from NLL to HLL = 795 m
= 5,000 barrel
8000 BPD
8000 BPD
(Non-Volatile Liquid Vap. Press ≤ 0.73 psi, Liquid Vap Pressure is 0.2 psi)
Inflow of liquid into the Tank (liquid movement in) = 8000.0 BPD from Production Profile
= 233.4 USGPM
Outbreathing Flowrate = 1871.5 ACFH
= 1737.89 SCFH
Outflow of liquid from the Tank (liquid movement out) = 8000.0 BPD ---> 1 x 100% Crude Oil Transfer Pump Running
= 233.4 USGPM
Inbreathing Flowrate = 1871.5 SCFH
2. Thermal Inbreathing/Outbreathing
Tank Volume (Critical height/Overflow to bottom), Vtk = 35372.0 ft3
Thermal Outbreathing
Equation (8) from API STD 2000 7th edition, March 2014
Y Factor for the latitude = 0.3 Table 1 API STD 2000 7th edition, March 2014 (Plant is located in Indonesia)
Ri The reduction factor for insulation = 1.0 (no insulation)
Thermal Outbreathing Flowrate = 5996.8 SCFH
Thermal Inbreathing
Equation (10) from API STD 2000 7th edition, March 2014
C Factor = 6.5 Table 2 API STD 2000 7th edition, March 2014 Thermal Inbreathing Flowrate
= 30586.2 SCFH
RESULT Selected Bund Wall Size : 30.0 m (L) x 30.0 m (W) x 1.4 m (H)