SCHEDULE-B : Insulating Sheet

ITEM: Supply and installation of RRRB Insulating sheet with all arrangements of
fabrication (Steel, bolts, fasteners etc.,) for fixing the sheet under ROB

Supply, Installation, Testing and Commissioning of min 10 mm thick (or 2 sheets of min 5 mm
each) Below the bottom surface of Road Over Bridges and above the Railway OHE as per the
directions of the Railway representative.

The Detailed Specifications of the Insulating sheet is as given below:

1. The Insulating sheet should have excellent tracking resistant properties which provides
longevity.

2. The Insulating sheet should have the Ultra violate with standing properties which makes it
suitable for outdoor applications.

3. The insulation sheet should be durable and should have damage resistant properties from
solvents, mechanical impact and general wear and tear.

4. The Insulating sheet should have machining properties which may allow it to be cut and
drilled for mounting without the need of special safety equipment.

5. General Technical Requirements:

Property Requirement
Tensile Strength 17 MPs Min., 2450 PSI min
Ultimate Strength 25% min
Secant Modulus (23±2) 200 MPa Min., 29000 PSI min
Density 1.1-1.3 g/cm3
Accelerated aging 168 hrs. at (120±)℃ 17 MPa Min., 2450 PSI min.
Tensile strength Ultimate Elongation 25% Min
Low Temperature Flexibility –(40±3)℃ No Cracking
Dielectric Constant 150kV/cm min., 380 V/mil min
Tracking and Erosion Resistance No Tracking, Erosion to top surface or flame
failure after
1 hr. at 2.5 kV
1 hr. at 2.75 kV
1 hr. at 3.0 kV
20 minutes at 3.25 kV
Water Absorption 336 hrs. at (23±2) ℃ 0.5% max
Temperature Cycling -40+60) ℃, 3 No Stress Cracking
Cycles/day, 30 days
Tracking & Erosion Resistance, Post No Tracking, Erosion to top surface or flame
Power-Arc failure after
1 hr. at 2.5 kV
1 hr. at 2.75 kV
1 hr. at 3.0 kV
20 minutes at 3.25 kV
6. Mounting Arrangement of Insulating Sheet:

The Tentative mounting arrangement of the Insulating sheet below the Road Over Bridge’s bottom
structure is shown in following image, The Tenderer shall inspect and measure the actual site
and put up the mounting arrangement of Insulating sheet to the Sr.DEE/Tr/GTL for the approval.