BUREAU OF INDIAN STANDARDS

BIS, Central Laboratory (CL) ULR No. :

DOC No. : CLQF0716 20/9, Site 4, Sahibabad Industrial Area, Sahibabad,


Telephone : Ghaziabad, Ghaziabad, Uttar Pradesh, India - 201010
FAX : -
E-Mail : cl@bis.gov.in
BO Code : CHBO

Test REPORT AS PER : IS 9537 : Part 3 (1983)

QR Code/Barcode : 100000442651

REPORT NO : CHBO/70378/20231120/MS/4_1 DATE : 12 Jan, 2024

PART A. PARTICULARS OF SAMPLE SUBMITTED

a) Customer Name & Address : -


b) Nature of sample : MS
c) Grade/Variety/Type/Class Size etc : Size : 25mm, Socket ended, Type : Heavy (HMS)
d) Declare values, if any : --
e) Batch No. & Date of Manufacture : /
f) Quantity : 4 pieces of 1.5 mtr
g) Date of Receipt : 20 Dec, 2023
h) BIS Seal : Verified by Sample Cell
i) IO's Signature : Verified by Sample Cell
j) Any other Information / Expiry Date, If any : /
k) Date of Commencement of Testing : 01 Jan, 2024
l) Date of Completion of Testing : 12 Jan, 2024
m) Section Code : 23E362EN
n) Section Report No. : 23E362EN_1
o) Report Type : New
p) Reference Report No. :
q) Remarks :

A K MOHINDROO
OIC SAMPLE CELL
(Authorized Signatory)
Authorized on: 12 Jan, 2024 10:25 AM

1. This report, in full or in part, shall not be published, advertised, used for commercial purpose or any legal action,
unless prior permission has been ecured from the Director General, Bureau of Indian Standards . This report Is
intended for "BIS CERTIFICATION MARKS PURPOSE ONLY"

2. This test report is ONLY FOR THE SAMPLE TESTED.

This is a Computer Generated Report.

Page 1 of 6
Section Report No. : 23E362EN_1 IS 9537 : Part 3 (1983)

PART B. SUPPLEMENTARY INFORMATION

1. Reference to sampling procedure, wherever applicable. Not Applicable


2. Supporting documents for the measurements taken and results derived like graphs, Not Applicable
table sketches and or photographs as appropriate to test report, if any.
3. Deviation from the test methods as prescribed in relevant ISS/Work instruction, if any. Not Applicable
3. NABL Report required ? -

Raju Sharma
OIC Electrical
(Authorized Signatory)
Authorized on: 12 Jan, 2024 10:20 AM

This is a Computer Generated Report.

Page 2 of 6
Section Report No. : 23E362EN_1 IS 9537 : Part 3 (1983)

PART C. TEST RESULT

S.No. Clause No Parameter - Test Min Max Unit Conformity Result/


Table No. Method of Description Limit Limit Observation
Sl. No test

1 12 Electrical Mega Ohm - - - Not Applicable Test could not


Characteristics- be carried out
Insulation due to
resistance test insufficient
as per clause quantity
12.1.2 of IS: (length) of
9537 (Part sample
1)-1980 provided.

2 12 Electrical Voltage of - - - Not Applicable Test could not


Characteristics- 2000V, 50 Hz be carried out
Test for electric sine wave form due to
strength as per applied for 15 insufficient
clause 12.1.1 of minutesNo quantity
IS: 9537 (Part breakdown shall (length) of
1)-1980 occur during the sample
test. provided.

3 11 Resistance to Seconds - - - Not Applicable Test could not


burning as per be carried out
clause 11 of IS: due to
9537 (Part insufficient
1)-1980 quantity
(length) of
sample
provided.

4 10 Resistance to mm - - - Conforms Requirement


Heat -Ball (mm) : 2; Max.,
presure test Result: Less
than 2 mm.

5 9.5 Collapse Test as Checked by - - - Conforms Passed in the


per clause 9.5 inspection.The test
of IS: 9537 (Part gauge shall
1)-1980 pass through
the conduit,
fixed to support
under its own
weight.

6 9.4 Impact Test as Nos. - - - Not Applicable Test could not


per clause 9.4 be carried out
of IS: 9537 (Part due to
1)-1980 insufficient
quantity
(length) of
sample
provided.

7 9.3 Compression Percentage - - - Conforms Requirement


Test as per (%) : (i)
caluse 9.3 of IS: Compression on
9537 (Part load, 25; Max.,
1)-1980 (ii) Compression
after removing
the load: 10;
Max., Result : (i)
Specimen I:
19.06,
Specimen II:
18.28,
Specimen III:
16.51, (ii)
Specimen I:
3.57, Specimen
II: 1.46,
Specimen III:
2.45

Page 3 of 6
8 9.2 Bending Test i) The sample - - - Conforms i) Passed in the
At Room Temp shall show no test, ii) Passed
ii) At Low Temp cracks visible to in the test
(-5 ±2°C) normal or
corrected vision
without
magnification.

9 8.1 Construction as a) The inside - - - Conforms a) Satisfactory,


per clause 8 of and outside b) Satisfactory
IS: 9537 (Part surface of
1)-1980 conduit shall be
reasonably
smooth and free
from burrs, flash
and similar
defects. b) The
edges over
which the
conductors or
cables are likely
to drawn shall
not damage the
cable or
conductor.

10 7.4 Unifomity of The In no case shall - 0.272 mm Conforms 0.2


wall Thickness the difference
between the
value measured
and the average
of the twelve
values obtained
from the three
samples exceed
0.1 mm + 10 %
of the average
value.

11 7.3 Length of - - - - Conforms 1.5 m x 4 pcs.


conduit

12 7.2 Minimum inside The minimum - - - Conforms Passed in the


diameter of inside diameter test.
conduit of the conduit
shall be
checked by
means of the
gauge as given
in Fig.3 of IS:
9537(Part3)-198
3

13 7.1.2 Maximum and The maximum - - - Conforms Passed in the


minimum and minimum test.
outside outside
diameter of diameter of the
conduit conduit shall be
checked by
means of gauge
as given in Fig.1
& 2 of IS:
9537(Part
3)-1983.

14 7.1.1 Maximum and Checked by - - - Conforms Passed in the


minimum manual test by test.
outside means of
diameter of gauges given in
socket Fig.7 and Fig.8

15 6.3 Standard Mark Standard Mark - - - Conforms Marked


on Conduit on Conduit

16 6.2 Durability of Durability of - - - Conforms Satisfactory


Marking as per Marking as per
6.4 of IS: 9537 6.4 of IS: 9537
(Part 1)-1980 (Part 1)-1980

Page 4 of 6
17 6.1 Marking Each length of - - - Conforms a) Masked, b)
the conduits 25mm, c) INDIA,
shall be marked d) HEAVY (HMS)
preferably at 50
mm, from one
end, with the
following
information: a)
Manufacturer's
name or trade
mark, if any b)
Nominal size of
the conduits c)
Country of
Manufacture d)
Informational
relating to
classification as
given in
5.1(Conduits for
light/medium/
heavy
mechanical
stresses).

Raju Sharma
OIC Electrical
(Authorized Signatory)
Authorized on: 12 Jan, 2024 10:20 AM

This is a Computer Generated Report.

Page 5 of 6
Section Report No. : 23E362EN_1 IS 9537 : Part 3 (1983)

PART D. REMARKS

nil

Raju Sharma
OIC Electrical
(Authorized Signatory)
Authorized on: 12 Jan, 2024 10:20 AM