SAGARDIGHI THERMAL POWER PROJECT


WEST BENGAL POWER DEVELOPMENT CORPORATION LIMITED

Test Record of Circuit Breaker


Date: 01/09/2021
Location: 400 KV Switchyard
Equipment: 4011 C.B (GT # 1 Bay)

1. Contact Resistance Measurement (at circuit breaker closed condition) (Instrument Used: Digital
Low Resistance Ohm Meter, Model: DLRO-600, Make-Megger)
Phase Contact Resistance
R-Φ 76.00 μΩ (100A)
Y- Φ 79.90 μΩ (100A)
B- Φ 78.80 μΩ (100A)

2. Timing Test: (Instrument Used: Hisac-Ultima, Model: PW636i, Make: SCOPE)


Phase → R-Φ Y- Φ B- Φ
Closing time (ms) 106.0 104.8 104.4
Close Pole Mismatch (ms) 1.6

R-Φ Y- Φ B- Φ
Phase →
TC1 TC2 TC1 TC2 TC1 TC2
Opening time (ms) 23.7 23.1 24.4 23.0 22.3 22.7
Open Pole Mismatch TC1(ms) 2.1
Open Pole Mismatch TC2(ms) 0.4
Close-Open Time (ms) 66.7 66.8 69.0 67.1 67.2 67.5