3.3.5.8 Surface Cables

Cable shall be heat and oil resistant, flame retardant (HOFR) type suitable for
service in environmental conditions described for the platform. All (normal and
emergency) cables have flame retardant characteristics to IEC 60332-3
category A.
Cables for safety systems like critical lighting system, navigational aids, F&G
system and Communication system etc., shall be fire resistant type to the
requirement of IEC 60331.

Cable joints via cast resin kit or other type are not permitted on the offshore
installations.

Special care shall be taken to the routing and separation of cables to minimize
the effect of fire on emergency and essential supplies and production
operations.

Emergency and instrumentation systems shall be routed away from normal


services/systems as far as possible.

All cables are identified with SS - 316 Tags.

In addition, the minimum distance between power/control wiring and electronic


signal wiring on prolonged cable route will be as follows –

Power / Control Minimum distance


cable from electronic/
signal cable
Up to 125 V 150mm
Up to 300 V 150mm
Up to 1000 V 300mm
Above 1000V 450mm

3.3.5.9 Earth Conductor

Earth cable shall be 6 mm2, 16 mm2 , 70 mm2 or 240 mm2 , stranded copper
conductor with CSP or EVA insulated with green / yellow insulation sheath.

3.3.5.10 Cable support System

Format No Ref. Proc. No Issue No Rev No Rev. Date 16


DD/SOF/046B DD/SOP/008 to 015 01 01 15/10/2003

Please refer ONGC Design Criteria, Earth conductor shall have CSP or EVA insulation. SE shall
provide as per ONGC requirement.