"PIPA UNDERGROUND 2 m, 200 M LENGTH" SUMMARY OF CALCULATION 1 Diameter Length Surface Area Factor Breakdown Current Density Current Demand Pipeline Name 2 (m) (m) (m²) (%) (mA/m²) (A) 3 2 m Pipe Dia, underground, 200 m length 2 200 1256,64 10 25 3,14 4 w/o Safety Factor 3,14 CATHODIC PROTECTION FOR EXTERNAL PIPELINE 5 + Safety Factor 25% 6 TOTAL SURFACE AREA (M²) 1.256,64 TOTAL 4 7 THIS DESIGN COVERS CALCULATION & GROUNDBED DESIGN WITH PREPACKED MAGNESIUM ANODE 8 CATHODIC PROTECTION 9 DESCRIPTION DESIGN FOR VERTICAL 10 SHALLOW GROUNDBED 11 Basic Design Data 12 Backfill Resistivity Ohm-m 0,5 13 Design Life Time Years 20 14 Soil Resistivity Ohm-m 6,28 15 Minimum Protective Potential VS Cu/CuSO4 Volt -0,85 16 Closed Pottential VS Cu/CuSO4 Volt -1,58 17 Magnesium Anode Requirement Based on Current Output 18 Type High Potential Pre-packed 19 Bare Mg Diameter meter 0,127 20 Bare Mg Length meter 0,512 21 Anode to backfill resistance Ohm 0,277 22 Spacing between anode in ground bed meter 1,00 23 Number of prepacked anode each groundbed pcs 10 24 Diameter of prepacked anode meter 0,152 25 Length of prepacked anode meter 0,762 26 Resistance of prepacked anode to soil Ohm 2,621 27 Interference factor 2,065 28 Total resistance of groundbed Ohm 0,598 29 Single groundbed current output Amp 1,220 30 Number of groundbed ea 4 31 Number of prepacked anode required pcs 40 32 Magnesium Anode Requirement Based on Weight 33 Anode Capacity Amp.Hr/kg 1230 34 Utilization factor 0,8 35 Bare Anode weight (each) kg 14,5 36 Minimum anode weight requirement kg 712,20 37 Number of prepacked anode required pcs 50 38 Summary 39 Number of prepacked anode required to be selected pcs 50 40 Number of groundbed to be selected ea 5 41 Distance of Each Ground Bed meter 40