You are on page 1of 4

DOCUMENT No.

HAND CONTROL VALVES 6347-40-16-43-SP-41 Rev. 0


Page 1 of 4

SPECIFICATION FOR HAND CONTROL


VALVES

0 31.01.05 ISSUED FOR BIDS SANJEEV KKM LBJ


Rev. Prepared Checked Approved
Date Purpose
No by by by

Format No. EIL 1641-1924 Rev. 1 Copyright EIL – All rights reserved
DOCUMENT No.
HAND CONTROL VALVES 6347-40-16-43-SP-41 Rev. 0
Page 2 of 4

CONTENTS

SECTION DESCRIPTION

1.0 SCOPE

2.0 TECHNICAL REQUIREMENTS

3.0 TAGS

4.0 SITE CONDITIONS

5.0 VENDOR DATA

6.0 INSPECTION AND TESTING

7.0 SPARES

8.0 WARRANTY

9.0 ATTACHMENTS

Format No. EIL 1641-1924 Rev. 1 Copyright EIL – All rights reserved
DOCUMENT No.
HAND CONTROL VALVES 6347-40-16-43-SP-41 Rev. 0
Page 3 of 4

1.0 SCOPE

This specification describes the requirements for the supply of Hand Control Valves
(Pressure Reducing Valves) to be installed on the offshore platform.

2.0 TECHNICAL REQUIREMENTS

1. The supply of Hand Control Valves shall be made in accordance with the
data sheets, which form a part of this specification.

2. The valve shall be Multi-stage pressure reducing type, designed for the
pressure drop as indicated in the Datasheet.

3. The valve trims shall be anti-cavitation, anti-corrosion, anti-erosion &


anti-noise type.

4. The noise level at 3M distance from the valve shall not be more than
85 dBA. For other details, refer Specification for Equipment Noise limits,
spec. no. 6347-40-25-54-SP-01.

5. The actuator of the valve shall be pneumatic actuator with manual


over-ride.

6. Valve shall be 100% radiographically examined as per procedures &


acceptance criteria shall be as per ANSI B 16.34.

3.0 TAGS

Tags shall be marked on SS-316 material and permanently attached.

4.0 SITE CONDITIONS

For site conditions and climate refer Specification No. 6347-40-16-56-SP-03.

5.0 VENDOR DATA

Vendor data shall be furnished in accordance with Specification for Vendor Data
Requirement, Spec. No. 6347-40-16-44-SP-04.

6.0 INSPECTION & TESTING

All valves shall be tested as mentioned in the data sheets. Company or its
representative(s) reserve(s) the right to witness the tests.

7.0 SPARES

Vendor shall recommend and provide spare parts needed for start-up &
commissioning.

Format No. EIL 1641-1924 Rev. 1 Copyright EIL – All rights reserved
DOCUMENT No.
HAND CONTROL VALVES 6347-40-16-43-SP-41 Rev. 0
Page 4 of 4

Vendor shall also recommend & supply spare parts (with prices) needed for one (1)
year operation and maintenance.

8.0 WARRANTY

Vendor shall have final and total responsibility for the design, fabrication and
performance of all valves supplied under this specification.

Vendor shall warrant the equipment furnished by him in accordance with this
specification and Specification for General Technical Requirements, “6347-40-
16-44-SP-01”

9.0 ATTACHMENTS

1. 6347-40-16-44-SP-01 Specification for General Technical


Requirements
2. 6347-40-06-42-SP-01 Specification for Protective Coating
3. 6347-40-16-56-SP-03 Specification for Site Conditions & Climate
4. 6347-40-16-44-SP-04 Specification for Vendor Data
Requirements.
5. 6347-40-16-43-SP-04 Piping Material Specifications (Only
General Notes and relevant piping classes
as per Data Sheet).
6. 6347-40-16-54-SP-01 Specification for Equipment Noise limits
7. 6347-40-16-43-DS-41 Data Sheet for Hand Control Valves

Format No. EIL 1641-1924 Rev. 1 Copyright EIL – All rights reserved