Analysis of Roof Truss for Stage IV: Sone Pump House

DESIGN DATA

Covered Plan Area


Roof Truss Span
Height of Column
Spacing of Truss
Rise
no. of Purlins
No. of Panels
Roof Slope, θ
Design Wind Pressure
Weight of Roofing Material ( incl overlaps and fasteners )
Intensity of Miscellaneous Load
Intensity of Live Load (=75-2*(26.1804-10))
weight /m of ISMC

LOAD CALCULATION

Length of Principal Rafter


Plan Area for a Truss
Roof Area for a Truss
Intensity for Self Weight of Truss
((Span/3)+5) kg/m2 (P 854, Limit state Design of Steel Structure-third edition by S K Duggal)

1 DEAD LOAD

Weight of Roofing material ( On Roof Area of Truss)


Weight of Purlin
Self Weight of Truss ( On Plan Area of Truss )
Miscellaneous Load ( On Plan Area of Truss )
Total Weight
D.L. on one intermediate panel
D.L. on shoe

2 LIVE LOAD

Live Load ( on Plan Area )


L.L. on one intermediate panel
L.L. on Shoe
3 WIND LOAD

Wind Load ( On Roof Area )


W.L. on one intermediate panel
W.L. on Shoe

LOAD COMBINATIONS

A) D.L.

B) D.L. + W.L.
cos θ

REACTION
A) Maximum vertical load
So, Reaction generated at ends
Vertical
Horizontal

B) Reaction generated at ends


Horizontal
House

= 11 * 81 m2
= 11 m
= 9.3 m
= 6.75 m
= 2.704 m (from old drawing)
= 10 no. (from old drawing)
= 8 no. (from old drawing)
= 26.1804 degrees
= 128.5165 kg/m2 (see Annexure 1 sheet)
= 13.3 kg/m 2
( AC sheet, IS 875 Part1)
= 3.5 kg/m2
= 42.63918 kg/m2 (Table 2, IS:875 (Part2) 1987, Reaffirmed 2008)
125 = 12.7 kg/m (IS 800:2007 Annex H)

= 6.1288 m
= 74.25 m2
= 82.7382 m2
= 9 kg/m
2

= 1100.418 kg
= 857.25 kg
= 668.25 kg
= 259.875 kg
= 2885.793 kg
= 370 kg
= 185 kg

= 3165.959 kg
= 396 kg
= 198 kg
= 10633.22 kg
= 1330 kg
= 665 kg

W = 766 kg
H = 0 kg

cos θ = 0.897409
sin θ = 0.441199
W = 620 kg ( acting on member )
H = 450 kg ( acting away from member )

= 766 kg
= 4W kg ( From Fig 1 of memb forces sheet )
= 3064 kg
= 0 kg

= 2480 kg
= 225 kg