Professional Documents
Culture Documents
TK4N(W48×H24mm)
High function/High performance PID control
Features
● Upgrade functions( ) Be sure that ( ) marks are for upgraded functions.
Convenient parameter setting (by DAQMaster)
- Parameter mask
Hides unnecessary and seldom used parameters
- User parameter group
Groups usually used parameters to set parameters
fast and conveniently
Line-up Alarm output3(heating&cooling OUT2
Relay output model), transmission output 2
(transmission output model)
● Super high-speed sampling cycle (10 times faster compared to previous models)
: 50ms sampling cycle and ±0.3% display-accuracy.
● Improved visibility with wide display part and high luminance LED
● High performance controlling with heating/cooling control and automatic/manual control modes.
● Communication function supported: RS485 (Modbus RTU)
● Allows parameter setting by USB port of PC.
: Free download the integrated device management program(DAQMaster)
※Communication converter, sold separately.
: SCM-US(USB to Serial converter), SCM-38I(RS-232C to RS485 converter), SCM-US48I(USB to RS485
converter)
● SSR drive output / Current output selectable.
● SSRP output (standard/phase/cycle control selectable)
● Heater burn-out alarm (CT input) (except TK4SP) (※CT, sold separately: CSTC-E80LN, CSTC-E200LN)
● Multi SV setting fuction (Max. 4) - selectable via digital input terminals.
● Mounting space saving with compact design.
: downsized by approx. 38%(60mm) in depth compared to previous models.
※Terminal cover, sold separately: R A -COVER(except TK4N, TK4SP)
● Multi input / Multi range
Manual
●●Visit our website (www.autonics.com) to download user manual and communication manual.
●●User manual describes for specifications and function, and communication manual describes for RS485 communication
(Modbus RTU protocol) and parameter address map data.
H-18
High Accuracy Standard PID Control
TK 4 S 1 4 R R (B)
Fiber
optic
OUT2 None sensor
control output
※3 Standard N ※Select in case of standard control(Heating or Cooling)
(C)
Heating & R Relay output Door/Area
sensor
Cooling C Current output+SSR drive output
(D)
※2 R Relay output Proximity
OUT1 control output sensor
S SSR drive output(standard ON/OFF control, phase control, cycle control)
C Current output+SSR drive output (E)
Power supply Pressure
sensor
4 100-240VAC 50/60Hz
※4
Standard Alarm output1+CT input (F)
1 ※5
Rotary
encoder
Heating&Cooling Alarm output2
2 Standard Alarm output1+Alarm output2 (G)
Connector/
( ) Standard Alarm output 1+Digital input(DI-1, DI-2) Socket
D
N Heating&Cooling Digital input(DI-1, DI-2)
(H)
Standard Alarm output1+Transmission output Temp.
R controller
※1 Heating&Cooling Transmission output
Option input/output
Standard Alarm output1+RS485 communication output (I)
SSR/
T Power
Heating&Cooling RS485 communication output controller
SP 1 Alarm output1
(J)
1 Alarm output1 Counter
※2: “S” represents SSR drive output support models which SSRP function (standard ON/OFF control, cycle control, phase control) are (R)
Graphic/
available. “C” represents selectable current and SSR drive output support models. Logic
panel
※3: Select "R" or "C" type in case of using heating&cooling control and "N" type in case of using standard control.
※4: ( ) CT input of TK4N is available only for the standard model which has alarm output1. (S)
Field
network
※5: ( ) The heating&cooling model of TK4N-1 has only alarm output 2. device
※6: Only for TK4S-D , OUT2 output terminal is used as DI-2 input terminal.
(T)
※7: Sockets for TK4SP (PG-11, PS-11) are sold separately. Software
(U)
Other
H-19
TK Series
Specifications
Series TK4N( ) TK4SP TK4S TK4M TK4W TK4H TK4L
Power supply 100-240VAC 50/60Hz
Allowable voltage range 90 to 110% of rated voltage
Power consumption Max. 6VA Max. 8VA
Display method 7 Segment (PV: red, SV: green), Other display part (green, yellow, red) LED method
Character PV(W×H) 4.5×7.2mm 7.0×14.0mm 9.5×20.0mm 8.5×17.0mm 7.0×14.6mm 11.0×22.0mm
size SV(W×H) 3.5×5.8mm 5.0×10.0mm 7.5×15.0mm 6.0×12.0mm 6.0×12.0mm 7.0×14.0mm
RTD JPt100Ω, DPt100Ω, DPt50Ω, Cu100Ω, Cu50Ω, Nikel 120Ω (6 types)
Input
Thermocouple K, J, E, T, L, N, U, R, S, B, C, G, PLII (13 types)
type
Analog Voltage: 0-100mV, 0-5V, 1-5V, 0-10V (4 types) / Current: 0-20mA, 4-20mA (2 types)
※1
RTD At room temperature(23℃±5℃): (PV ±0.3% or ±1℃, select the higher one) ±1digit
Out of room temperature range: (PV ±0.5% or ±2℃, select the higher one) ±1digit
Display Thermocouple ※In case of TK4SP Series, ±1℃ will be added.
accuracy
Analog At room temperature(23℃±5℃): ±0.3% F.S. ±1digit, Out of range of room temperature: ±0.5℃% F.S. ±1digit
CT input ±5% F.S. ±1digit
Relay OUT1, OUT2: 250VAC 3A 1a
Control
SSR 11VDC±2V 20mA Max.
output
Current DC4-20mA or DC0-20mA selectable (load 500Ω Max.)
Alarm AL1, AL2 Relay: 250VAC 3A 1a
Relay ※TK4N AL2: 250VAC 0.5A 1a(Max.125VA), TK4SP has only AL1.
output
Option Transmission DC4-20mA (load 500Ω Max., Accuracy: ±0.3% F.S.)
output Communication RS485 communication output (Modbus RTU)
CT input 0.0-50.0A(primary heater current value measuring range) ※CT ratio = 1/1000 (except TK4SP)
Option Contact Input: ON - Max. 2kΩ, OFF - Min. 90kΩ
input Non-contact Input: ON - Residual votage max. 1.0V, OFF - Leakage current max. 0.1mA
Digital input
Outflow current: Approx. 0.5mA
※TK4S/M-1EA(TK4S-D -2EA, TK4SP-None), TK4N/H/W/L-2EA
Control Heating,cooling
ON/OFF, P, PI, PD, PID control
type Heating&cooling
Hysteresis Thermcouples / RTD: 1 to 100℃/℉ (0.1 to 100.0℃/℉) variable Analog: 1 to 100digit
Proportional band (P) 0.1 to 999.9℃/℉ (0.1 to 999.9%)
Integral time (I) 0 to 9999 sec.
Derivative time (D) 0 to 9999 sec.
Relay output, SSR drive output: 0.1 to 120.0 sec.
Control period (T)
Current output+SSR drive output: 1.0 to 120.0 sec.
Manual reset value 0.0 to 100.0%
Sampling period 50ms
Dielectric strength 2,000VAC 50/60Hz for 1min. (between power source terminal and input terminal)
Vibration 0.75mm amplitude at frequency of 5 to 55Hz(for 1min.) in each of X, Y, Z direction for 2 hours
Relay Mechanical OUT1/2: Over 5,000,000 times, AL1/2: Over 20,000,000 times (TK4H/W/L: Over 5,000,000 times)
life cycle Electrical OUT1/2: Over 200,000 times, AL1/2: Over 100,000 times (TK4H/W/L: Over 200,000 times)
Insulation resistance Min. 100MΩ (at 500VDC megger)
Noise resistance ±2kV R-phase, S-phase the square wave noise (pulse width: 1us) by the noise simulator
Memory retention Approx. 10 years (when using non-volatile semiconductor memory type)
Ambient -10 to 50℃, storage: -20 to 60℃
Environ- temperature
ment Ambient 35 to 85%RH, storage: 35 to 85%RH
humidity
Protection IP65 (Front panel) ※TK4SP: IP50 (Front panel)
Double insulation or reinforced insulation
Insulation type
(Mark: , Dielectric strength between the measuring input part and the power part: 2kV)
Approval
※2 Approx. 140g Approx. 130g Approx. 150g Approx. 210g Approx. 294g
Weight Approx. 211g(Approx. 141g)
(Approx. 70g) (Approx. 85g) (Approx. 105g) (Approx. 140g) (Approx. 198g)
※1: At room temperature(23℃±5℃)
Thermocouple K, J, T, N, E type, below -100℃ / Thermocouple L, U, PLⅡ type, RTD( ) Cu50Ω, DPt50Ω
: (PV ±0.3% or ±2℃, select the higher one) ±1digit
Thermocouple C, G, R, S type, below 200℃: (PV ±0.3% or ±3℃, select the higher one) ±1digit
Thermocouple B type, below 400℃: There is no accuracy standards.
Out of room temperature range
RTD Cu50Ω, DPt50Ω: (PV ±0.5% or ±3℃, select the higher one) ±1digit
Thermocouple R, S, B, C, G type: (PV ±0.5% or ±5℃, select the higher one) ±1digit
Others, Below -100℃: Within ±5℃
In case of TK4SP Series, ±1℃ will be added to the degree standard.
※2: The weight is with packaging and the weight in parentheses is only unit weight.
※Environment resistance is rated at no freezing or condensation.
H-20
High Accuracy Standard PID Control
Connections (A)
Photo
※Please check the polarity when connecting temperature sensor or analog input. electric
sensor
※Standard model has shaded terminals only.
(B)
( )Operation mode of heating&cooling OUT2 relay output model is heating or cooling, OUT2 is available as alarm output 3. Fiber
(except TK4N Series). optic
sensor
( )Operation mode of heating&cooling OUT2 current output model is heating or cooling, OUT2 is available as transmission
output 2. (C)
Door/Area
sensor
TK4N Transfer Output
DC4-20mA
(D)
Line-up
RS485(B-)
RS485(A+)
Proximity
Communication sensor
Output
V
DI-2
3 3 (F)
OUT1
TC DI-1 Digital Input Rotary
V mA encoder
SENSOR Non-contact, contact input
RTD DI-2 4 4
DI-1
11VDC±2V DC0-20mA (G)
Connector/
20mA Max. Load 500Ω Max. Socket
AL2 OUT:
OUT2/AL1 OUT:
250VAC 3A 1a
OUT1:
250VAC 3A 1a 250VAC 0.5A 1a 1 1
RESISTIVE LOAD V mA (H)
RESISTIVE LOAD RESISTIVE LOAD
OUT2
Temp.
2 2 controller
OUT1
Non-contact, DI-1 DI-1 Non-contact, DI-2 DI-2 250VAC 3A 1a
contact input contact input RESISTIVE LOAD V mA
2 14 8 AL2 OUT: 4 4 (K)
250VAC 3A 1a Timer
OUT1: 3 Transfer RS485(A+) 15 Communi- 9 RESISTIVE LOAD 11VDC±2V DC0/4-20mA
Relay mA 20mA Max. Load 500Ω Max.
250VAC 3A 1a Output cation
DC4-20mA Output A
RESISTIVE LOAD 4 RS485(B-) 16 10 (L)
13 13 Panel
B meter
5 17 11 V mA
OUT2
mA
Current
Transformer CT V 14 14 (M)
0.0-50.0A B'
SOURCE 6 18 12 Tacho/
100-240VAC RTD TC 11VDC±2V DC0/4-20mA Speed/ Pulse
50/60Hz 8VA SENSOR 20mA Max. Load 500Ω Max. meter
(N)
TK4SP OUT2:
SSR Current Display
unit
Relay
250VAC 3A 1a 5 5
OUT1
RESISTIVE LOAD
6 V mA (O)
OUT1:
Relay
5 7 4 4 Sensor
controller
250VAC 3A 1a AL1:
RESISTIVE LOAD 4 8 Relay
11VDC±2V DC0/4-20mA
250VAC 3A1a (P)
RESISTIVE LOAD 20mA Max. Load 500ΩMax. Switching
B'
3 9 mode power
V 9 9 supply
B
10 V mA
OUT2
mA
TC
2 (Q)
1 11 6 6 Stepper
A motor&
SOURCE Driver&Controller
RTD 100-240VAC 11VDC±2V DC0/4-20mA
SENSOR 50/60Hz 8VA 20mA Max. Load 500ΩMax. (R)
Graphic/
Logic
panel
TK4M
1 AL1 OUT: 19 10 Digital Input
(S)
250VAC 3A 1a DI-1 DI-1 Field
RESISTIVE LOAD Non-contact, contact input network
2 AL2 OUT:
20 11 device
250VAC 3A 1a RS485(A+) SSR Current
3 RESISTIVE LOAD 21 12 (T)
mA Transfer Output Software
RS485(B-) DC4-20mA 6 6
OUT1
4 OUT2: 22 13
Relay Communication Output V mA
250VAC 3A 1a 7 7
5 RESISTIVE LOAD 23 14 Current (U)
Transformer Other
CT 11VDC±2V DC0/4-20mA
0.0-50.0A
6 OUT1: 24 15 20mA Max. Load 500Ω Max.
Relay
250VAC 3A 1a A
7 RESISTIVE LOAD 25 16 4 4
V mA
OUT2
B
8 26 17 mA
5 5
SOURCE V
100-240VAC B'
50/60Hz 8VA 9 27 18 RTD TC
11VDC±2V DC0/4-20mA
20mA Max. Load 500Ω Max.
SENSOR
H-21
TK Series
Connections
※Please check the polarity when connecting temperature sensor or analog input.
※Standard model has shaded terminals only.
( )Operation mode of heating&cooling OUT2 relay output model is heating or cooling, OUT2 is available as alarm output 3.
(except TK4N Series).
( )Operation mode of heating&cooling OUT2 current output model is heating or cooling, OUT2 is available as transmission
output 2.
2 14 Digital Input
Non-contact, contact input
3 AL1 OUT: 15 ※Digital input is not electrically insulated from internal
250VAC 3A 1a DI-1 DI-1
RESISTIVE LOAD circuits, so it should be insulated when connecting other
4 16 DI-2 DI-2
circuits. (Photocoupler, Relay, Independent switch)
5 AL2 OUT: 17
250VAC 3A 1a
RESISTIVE LOAD RS485(A ) SSR Current
6 18 Transfer Out
mA DC4-20mA
RS485(B ) 9 9
OUT1
7 OUT2: 19
Relay V mA
250VAC 3A 1a Communication Output
RESISTIVE LOAD 10 10
8 20 Current
CT Transformer 11VDC±2V DC0/4-20mA
0.0-50.0A 20mA Max. Load 500Ω Max.
9 OUT1: 21
Relay
250VAC 3A 1a A
10 RESISTIVE LOAD 22 7 7
V mA
OUT2
B
11 23 mA 8 8
V
B'
SOURCE 12 24 11VDC±2V DC0/4-20mA
100-240VAC RTD TC 20mA Max. Load 500Ω Max.
50/60Hz 8VA SENSOR
Dimensions
(unit: mm)
TK4N Line-up TK4S 6 64.5
48 1.7
94.8
48 3
21.8
45
24
91.5
96
H-22
High Accuracy Standard PID Control
Dimensions (A)
Photo
electric
TK4L ●Panel cut-out sensor
6 64.5 A (B)
96 Fiber
1.5 optic
D sensor
B (C)
C Door/Area
sensor
(unit: mm)
Size A (D)
Model B C D Proximity
sensor
TK4N Min. 55 Min. 37 45 +0.6
22.2 +0.3
91.5
0 0
3.3
(I)
45 5 SSR/
Power
controller
36.3
28.8
22
4
46
44.9
36
(J)
16
Counter
45.2
37.5
40.5
48.6
32.4 15
(K)
3.5
Timer
26.4 55
21 12
11.6
(L)
23.9 Panel
meter
10 56
7.9
(M)
Tacho/
Speed/ Pulse
meter
41.5
68.5
(P)
64
Switching
mode power
supply
18
(Q)
22
Stepper
※TK4N COVER is accessory. motor&
13
9.8 Driver&Controller
22.5 (R)
Graphic/
Logic
panel
●RHA Cover(48×96mm, 96×48mm) ●RLA Cover(96×96mm)
(S)
Field
47.2 4 94 3 network
device
(T)
Software
91.5
91.5
86
86
(U)
Other
13
13
H-23
TK Series
Product mounting
TK4N(48×24mm) Series TK4S/SP(48×48mm) Series Other Series
(-)driver
(+)driver
※Insert the unit into a panel, fasten
※Insert the unit into a panel, fasten the bracket by pushing with tools (-)driver
the bolt with a (+) driver. with a (-) driver.
Sold separately
Communication converter
SCM-38 SCM-US48 SCM-US
(RS232C to RS485 (USB to RS485 (USB to Serial
converter) converter) converter)
Current transformer(CT)
CSTC-E80LN
F=50Hz
Ø23.3 10
Ta=25℃
Ø7 100Ω
OUTPUT IN VOLTS RMS(V)
3
K(Black) 1 10Ω Max. load current: 80A(50/60Hz)
※Max. load current for TK4 Series
3.8
7
is 50A.
L(White)
0.1 Current ratio: 1/1000
Wire wounded resistance: 31Ω±10%
26.5 150
0.01
10.5
(unit: mm)
0.001
0.1 1 10 100 1000
SENSED CURRENT IN AMPS RMS(Io)
CSTC-E200LN
Ø37.1 10 100Ω
Ta=25℃
Ø13
OUTPUT IN VOLTS RMS(V)
3 10Ω
is 50A.
L(White) 0.1 Current ratio: 1/1000
Wire wounded resistance: 20Ω±10%
40.8 150
0.01
13.5
H-24
High Accuracy Standard PID Control
SV setting (P)
Switching
mode power
You can set the temperature to control with keys. supply
Set range is within SV low-limit value [ L-SV] to SV high-limit value [ H-SV]. (Q)
Stepper
Ex) In case of changing set temperature from 210ºC to 250ºC motor&
Driver&Controller
(T)
Software
H-25
TK Series
Parameter group
Run mode
When PW is
valid
When PW is
valid
PARU※3 PAR1 PAR2
※Press key over 2 sec in RUN mode to enter into setting mode.
※Press key for 1.5 sec while in setting mode to move to other
parameter group.
※Press key over 3 sec while in setting mode to return to RUN mode.
※Press key at the last parameter of each parameter, it moves to that
parameter name. You can move to other groups.
※If there is no additional key operation within 30 sec after entering into
setting mode, it will be automatically returned to RUN mode and previous
setting value will be remained.
H-26
High Accuracy Standard PID Control
(A)
Photo
electric
sensor
3 sec.
(B)
Fiber
optic
sensor
(C)
※2 ※2 Door/Area
sensor
H-MV C-MV
Heating MV Cooliing MV (D)
Proximity
Monitoring Monitoring sensor
(E)
Pressure
(F)
Rotary
encoder
Input type[ IN-T] Alarm output1operation mode[ AL-1] Multi SV[ MtSV]
(G)
Connector/
1.5 sec. 1.5 sec. 1.5 sec. Socket
Sensor temperature unit[ UNIT] Alarm output1 option[ AL!T] Digital input key[ DI-K] (H)
Temp.
Analog low-limit input value[ L-RG] Alarm output1 hysteresis[ A!HY] DI-1 input terminal function[ DI-1] controller
Analog high-limit input value[ H-RG] Alarm1 N.O./N.C.[ A!N] DI-2 input terminal function[ DI-2] (I)
SSR/
Scaling decimal point[ DOT] Alarm1 ON delay time[ A!ON] Manual control, initial MV[ ItMV] Power
controller
Low-limit scale value[ L-SV] Alarm1 OFF delay time[ A!OF] Manual control, preset MV[ PrMV]
(J)
High-limit scale value[ H-SV] Alarm output2 operation mode[ AL-2] Sensor error, MV[ ErMV] Counter
Display unit[ dUNT] Alarm output2 option[ AL@T] Control stop, MV[ StMV]
(K)
Input correction[ IN-B] Alarm output2 hysteresis[ A@HY] Control stop, alarm output[ StAL] Timer
Input digital filter[ MAvF] Alarm 2 N.O./N.C.[ A@N] User level[ USER]
(L)
SV low-limit[ L-SV] Alarm 2 ON delay time[ A@ON] SV setting lock[ LcSV] Panel
meter
SV high-limit[ H-SV] Alarm 2 OFF delay time[ A@OF] Parameter 1group lock[ LcP1]
(M)
Tacho/
Control output operation mode[ O-FT] Alarm output3 operation mode[ AL-3] Parameter 2group lock[ LcP2] Speed/ Pulse
meter
Control type[ C-MD] Alarm output3 option[ AL#T] Parameter 3group lock[ LcP3]
(N)
Auto-tuning mode[ AtT] Alarm output3 hysteresis[ A#HY] ( ) Parameter 4group lock[ LcP4] Display
unit
OUT1 control output selection[ OUT1] Alarm 3 N.O./N.C.[ A#N] Parameter 5group lock[ LcP5]
(O)
OUT1 SSR drive output type[ O!SR] Alarm 3 ON delay time[ A#ON] Password setting[ PWD] Sensor
controller
OUT1 current output range[ O!MA] Alarm 3 OFF delay time[ A#OF]
(P)
OUT2 control output selection[ OUT2] LBA time[ LBaT] Switching
mode power
supply
OUT2 current output range[ O@MA] LBA band[ LBaB]
(Q)
Heating control time[ H-T] Analog trans. output 1 mode[ AoM1] Stepper
motor&
Driver&Controller
Cooling control time[ C-T] Trans. output 1 low-limit value[ FsL1]
(R)
Trans. output 1 high-limit value[ FsH1] Graphic/
Logic
Analog trans. output 2 mode[ AoM2] panel
H-27
TK Series
Parameter 1 group
3 sec. ※1: S : Press any key among , ,
Run mode ※After entering setting mode, press key anytime for 3 sec. to return to Run mode.
※After entering setting mode, press key anytime for 1.5 sec. to go to the concerned group name.
2 sec.
S ※1
※If you press the key after changing the setting value of the parameter the setting value will be stored.
PASS ※ Shaded parameters are for standard-level users, the others are for high-level users.
Output code when (You can set the user level in parameter 5 group)
PW value is unequal ※ This parameter might not be displayed depending on other parameter settings.
in SV display
Password entry
S
PASS 0001
When PW
is unequal When PW is valid.
Multi SV number
S
SV-N SV-0 SV-1 SV-2 SV-3
※Display SV0 through SV3, depending on the preset number of multi SVs[ MtSV]
Heater current monitoring
S Set range: 00.0 to 50.0A
CT-A )0 ※Displayed only with current transformer(CT) input models(Expect for TK4SP)
Set range: Deviation alarm (-F.S. to F.S.),
Alarm output1 low-limit set value Absolute alarm (within display range), Unit (℃/℉)
S ※Displayed only when alarm output 1's operation mode[ AL-1] is set to low-limit
AL!L 1550 alarm for offset/absolute value or high/low-limit alarm/reverse alarm for offset
value.
※Sets the heater burnout SV for a current transformer(with option inputs) when
Alarm output 1 operation mode[ AL-1] is in heater burnout alarm[ HBA].
Alarm output1 high-limit set value ※It does not display if alarm output 1's operation mode[ AL-1] is set to OFF, SBA or LBA.
S ※Displayed only when alarm output 1's operation mode[ AL-1] is set to high-limit
AL!H 1550
alarm for offset/absolute value or high-limit alarm/reserve alarm for offset value.
※It does not display if alarm output 1's operation mode[ AL-1] is set to OFF, SBA,
Alarm output2 low-limit set value LBA or HBA.
S
AL@L 1550 Set range: Deviation alarm (-F.S. to F.S.),
Absolute alarm (within display range), Unit (℃/℉)
Alarm output2 high-limit set value ※Displayed only with option output models that support alarm output 2.
S (Active/inactive conditions ard the same as alarm output 1 with the exception for
AL@H 1550 HBA)
Setting value(SV)-0
S
SV-0 0000
Setting value(SV)-1
S
SV-1 0000
Set range: L-SV to H-SV, unit(℃/℉)
Setting value(SV)-2
※The number of multi SVs [ SV0 to SV3] set at Multi SV [ MtSV] are displayed.
S
SV-2 0000
Setting value(SV)-3
S
SV-3 0000
H-28
High Accuracy Standard PID Control
※After entering setting mode, press key anytime for 3 sec. to return to Run mode. (B)
Fiber
※After entering setting mode, press key anytime for 1.5 sec. to go to the concerned group name. optic
sensor
※If you press the key after changing the setting value of the parameter the setting value will be stored.
※ Shaded parameters are for standard-level users, the others are for high-level users. (C)
(You can set the user level in parameter 5 group) Door/Area
sensor
※ This parameter might not be displayed depending on other parameter settings.
Parameter 2 group Parameter 3 group Parameter 4 group (D)
Proximity
PAR2 PAR3 PAR4 sensor
(E)
Pressure
Auto-tuning RUN/STOP sensor
S
AT OFF ON
(F)
Rotary
encoder
Heating proportional band
S Set range: 000.1 to 999.9℃ / ℉, %
H-P 01)0 ※Displayed only when control output operation mode[ O-FT] is
(G)
Connector/
Socket
set to heating[ HEAT] or heating and cooling[ H-C].
Cooling proportional band (H)
Temp.
S Set range: 000.1 to 999.9℃ / ℉, % controller
C-P 01)0 ※Displayed only when control output operation mode[ O-FT] is
(I)
set to cooling[ COOL] or heating and cooling[ H-C]. SSR/
Power
Heating integral time controller
S Set range: 0001 to 9999 sec. ※Displayed only when
H-I 0000 ※Displayed only when control output operation mode[ O-FT] is temperature control (J)
Counter
set to heating[ HEAT] or heating and cooling[ H-C]. type[ C-MD] is set to
Cooling integral time PID control.
S
S
Set range: 0001 to 9999 sec. (K)
C-1 0000 ※Displayed only when control output operation mode[ O-FT]is
Timer
ONOFF/ONOFF control: -999 to 999 digit(Temp. H), -199.9 to 999.9 digit(Temp. L), (P)
Switching
-99.9 to 99.9% F.S.(Analog) mode power
Manual reset ※Displayed only when control output operation mode[ O-FT] is set to heating and cooling[ H-C]. supply
S
S
REST 05)0 Set range: 000.0 to 100.0% (Q)
Stepper
※Displayed only under proportional control. motor&
※Does not display if control output operation mode[ O-FT] is set to heating and cooling[ H-C]). Driver&Controller
(S)
※Displayed only when control output operation Field
Heating OFF offset network
mode[ O-FT] is set to heating[ HEAT] or heating device
S Set range: 000 to 100digit
hOST 000 and cooling[ H-C].
(000.0 to 100.0) (T)
Software
※Displayed only when temperature control type[ C-MD] is
Cooling hysteresis set to ONOF or OnON control.
S
cHYS 002 Set range: 001 to 100digit (U)
Other
(000.1 to 100.0)
※Displayed only when control output operation
Cooling OFF offset mode [ O-FT] is set to cooling[ COOL] or heating
S
cOST 000 Set range: 000 to 100digit and cooling[ H-C].
(000.0 to 100.0)
H-29
TK Series
MV low limit
S
Set range: 000.0 to ( H-MV-0.1%) (Standard control),
L-MV 00)0 -100.0 to 000.0% (Heating & cooling control) ※Displayed only when control
type[ C-MD] is PID control, or
MV high limit
control output operation[ O-FT]
S is heating&cooling[ H-C].
Set range: ( L-MV+0.1) to 100.0% (Standard control),
H-MV 10)0 000.0 to 100.0% (Heating & cooling control)
RAMP unit
S
rUNT MIN HOUR SEC Set range: SEC / MIN /HOUR
Parameter 3 group
※1: S : Press any key among , ,
※After entering setting mode, press key anytime for 3 sec. to return to Run mode.
※After entering setting mode, press key anytime for 1.5 sec. to go to the concerned group name.
※If you press the key after changing the setting value of the parameter the setting value will be stored.
※ Shaded parameters are for standard-level users, the others are for high-level users.
(You can set the user level in parameter 5 group)
※ This parameter might not be displayed depending on other parameter settings.
Parameter 3 group Parameter 4 group Parameter 5 group
Input type
S
IN-T KCaH KCaL AMA2
Decimal point
S
DOT )0 Set range: 0 / 0.0 / 0.00 / 0.000
Display unit
S
dUNT ?/? OFF ?C ?F
H-30
High Accuracy Standard PID Control
(A)
Photo
Input correction electric
sensor
S
IN-B 000 Set range: -999 to 0999digit (-199.9 to 999.9)
(B)
Fiber
optic
sensor
Input digital filter
S (C)
MAvF 00)1 Set range: 000.1 to 120.0 sec. Door/Area
sensor
SV low-limit (D)
Proximity
S sensor
L-SV -200 Set range: Low limit input[ L-SC] to H-SV-1digit ℃ / ℉ / %
(E)
Pressure
SV high-limit sensor
S
H-SV 1350 Set range: L-SV+1digit to High limit input[ H-SC] ℃ / ℉ / %
(F)
Rotary
encoder
(J)
Auto-tuning mode Counter
S
AtT TUN1 TUN2 ※Displayed only when temperature control type[ C-MD] is set to PID control.
(K)
Timer
(M)
OUT1 SSR drive output type Tacho/
S ※Displayed only when OUT1 control output of model Speed/ Pulse
O!SR STND CYCL PHAS is SSR drive output of SSRP function.
meter
(N)
Display
OUT1 current output range unit
S ※Displayed only when OUT1 control output of model is current output
O!MA 4-20 0-20 and is set to CURR in OUT1 mode. (O)
Sensor
controller
(Q)
OUT2 current output range Stepper
S motor&
※Displayed only when OUT2 control output of model is current output
O@MA 4-20 0-20 and is set to CURR in OUT2 mode.
Driver&Controller
(R)
Graphic/
Logic
Heating control time panel
S
H-T 02)0 (S)
Field
Set range: 000.1 to 120.0 sec. network
device
※Displayed only when temperature control method[ C-MD] is set to PID control.
Cooling control time ※Not Displayed when output method is set to CYCL, PHAS.
S (T)
C-T 02)0 Software
(U)
※OUT1, OUT2 output: Other
In case that OUT1,OUT2 output is relay output type , OUT1, O!SR, O!MA, OUT2, O@SR, O@MA parameter are not displayed.
In case that OUT1,OUT2 output is current + SSR drive output type, when OUT1,OUT2 output is set to SSR.
- Output method of O!SR, O@SR is held in STND and parameter is not displayed.
In case that OUT1, output is SSR drive output model of SSRP function and OUT2 output is current + SSR drive output
- OUT1, O!MA are not displayed.
- O!SR can set to STND, CYCL, PHAS
- When O@SR is set to SSR it is held in STND and parameter is not displayed.
H-31
TK Series
Parameter 4 group
※1: S : Press any key among , ,
※After entering setting mode, press key anytime for 3 sec. to return to Run mode.
※After entering setting mode, press key anytime for 1.5 sec. to go to the concerned group name.
※If you press the key after changing the setting value of the parameter the setting value will be stored.
※ Shaded parameters are for standard-level users, the others are for high-level users.
(You can set the user level in parameter 5 group)
※ This parameter might not be displayed depending on other parameter settings.
H-32
High Accuracy Standard PID Control
(A)
Photo
Alarm output3 operation mode electric
sensor
S
( ) AL-3 OFF DVCC HBA (B)
Fiber
optic
sensor
(G)
Alarm 3 ON delay time Connector/
S Set range Socket
( ) A#ON 0000 : 0000 to 3600 sec. ※Displayed only if alarm output 3's
(H)
operating mode[AL-3] is not set to Temp.
OFF. controller
Alarm 3 OFF delay time
S Set range
( ) A#OF 0000 : 0000 to 3600 sec.
(I)
SSR/
Power
controller
(O)
C-MV H-MV C-MV H-MV Sensor
controller
Trans. output 1 low-limit value
PV trans. output low-limit (P)
S
S
( ) FsL1 -200 Set range: F.S.
FS-L -200 Set range: F.S.
Switching
mode power
supply
(Q)
Stepper
Trans. output 1 high-limit value PV trans. output high-limit motor&
S S Driver&Controller
( ) FsH1 1350 Set range: F.S. FS-H 1350 Set range: F.S.
(R)
Graphic/
Logic
Analog trans. output 2 mode panel
S
( ) AoM2 PV SV (S)
Field
network
device
H-33
TK Series
Comm. address
S
ADRS 01 Set range: 01 to 99
Comm. speed
S
BPS 96 192 48
Comm. write
S
COMW EnA DIsA
Parameter 5 group
※1: S : Press any key among , ,
※After entering setting mode, press key anytime for 3 sec. to return to Run mode.
※After entering setting mode, press key anytime for 1.5 sec. to go to the concerned group name.
※If you press the key after changing the setting value of the parameter the setting value will be stored.
※ Shaded parameters are for standard-level users, the others are for high-level users.
(You can set the user level in parameter 5 group)
※ This parameter might not be displayed depending on other parameter settings.
Parameter 5 group Parameter 1 group Parameter 2 group
Multi SV
S
MtSV 1 2 4
Sensor error, MV
S Set range: 000.0 to 100.0% (standard control),
ErMV 00)0 -100.0 to 100.0% (heating & cooling control)
Control stop, MV
S
StMV 00)0
H-34
High Accuracy Standard PID Control
(A)
Photo
Control stop, alarm output electric
S sensor
StAL CONT OFF
(B)
Fiber
optic
sensor
User level
S
USER STND HIGH (C)
Door/Area
sensor
(E)
Pressure
Parameter 1 group lock sensor
S
LcP1 OFF ON
(F)
Rotary
encoder
Parameter 2 group lock
S
LcP2 OFF ON (G)
Connector/
Socket
(I)
SSR/
Power
Parameter 4 group lock controller
S
LcP4 OFF ON
(J)
Counter
Parameter Initialization
(N)
Display
unit
(Q)
Stepper
motor&
Driver&Controller
(R)
Graphic/
Logic
panel
(S)
Field
network
device
(T)
Software
(U)
Other
H-35
TK Series
H-36
High Accuracy Standard PID Control
SV 0 PASS 0001
(C)
Door/Area
sensor
Parameter 1 group [ PAR1]
(D)
Parameter Factory default Parameter Factory default Parameter Factory default Parameter Factory default Proximity
sensor
R-S RUN AL!H 1550 AL#H 1550 SV-3 0000
SV-N SV-0 AL@L 1550 SV-0 0000 (E)
Pressure
CT-A )0 AL@H 1550 SV-1 0000 sensor
H-37
TK Series
Alarm
Alarm operation
Mode Name Alarm operation Description
OFF H ON OFF H ON
Deviation If deviation between PV and SV as high-
DVCC high-limit SV PV PV SV limit is higher than set value of deviation
alarm 100℃ 110℃ 90℃ 100℃ temperature, the alarm output will be ON.
High deviation: Set as 10℃ High deviation: Set as -10℃
ON H OFF ON H OFF
Deviation If deviation between PV and SV as low-
]]DV low-limit PV SV SV PV limit is higher than set value of deviation
alarm 90℃ 100℃ 100℃ 110℃ temperature, the alarm output will be ON.
Lower deviation: Set as 10℃ Lower deviation: Set as -10℃
ON H OFF H ON
Deviation If deviation between PV and SV as high/
]DV[ high/low-limit PV SV PV low-limit is higher than set value of deviation
alarm 90℃ 100℃ 120℃ temperature, the alarm output will be ON.
Lower deviation: Set as 10℃, High deviation: Set as 20℃
OFF H ON H OFF
Deviation If deviation between PV and SV as high/
CDV] high/low-limit PV SV PV low-limit is higher than set value of deviation
reserve alarm 90℃ 100℃ 120℃ temperature, the alarm output will be OFF.
Lower deviation: Set as 10℃, High deviation: Set as 20℃
OFF H ON OFF H ON
Absolute
PV SV SV PV If PV is higher than the absolute value,
PVCC value high
90℃ 100℃ 100℃ 110℃ the output will be ON.
limit alarm
Absolute-value Alarm: Absolute-value Alarm:
Set as 90℃ Set as 110℃
ON H OFF ON H OFF
Absolute
PV SV SV PV If PV is lower than the absolute value,
]]PV value low
90℃ 100℃ 100℃ 110℃ the output will be ON.
limit alarm
Absolute-value Alarm: Absolute-value Alarm:
Set as 90℃ Set as 110℃
LBA Loop break Alarm - It will be ON when it detects loop break.
It will be ON when it detects sensor
SBA Sensor break Alarm -
disconnection.
HBA Heater break alarm - It will be ON when CT detects heater break.
※ H: Alarm output hysteresis [ A .HY]
Alarm option
Mode Name Description
AL-A Standard alarm If it is an alarm condition, alarm output is ON. If it is a clear alarm condition, alarm output is OFF.
AL-B Alarm latch If it is an alarm condition, alarm output is ON and maintains ON status.
First alarm condition is ignored and from second alarm condition, standard alarm operates.
AL-C Standby sequence1 When power is supplied and it is an alarm condition, this first alarm condition is ignored and from the
second alarm condition, standard alarm operates.
If it is an alarm condition, it operates both alarm latch and standby sequence. When power is supplied
Alarm latch and
AL-D and it is an alarm condition, this first alarm condition is ignored and from the second alarm condition,
standby sequence1
alarm latch operates.
First alarm condition is ignored and from second alarm condition, standard alarm operates.
AL-E Standby sequence2 When re-applied standby sequence and if it is alarm condition, alarm output does not turn ON.
After clearing alarm condition, standard alarm operates.
Basic operation is same as alarm latch and standby sequence1. It operates not only by power ON/OFF,
Alarm latch and but also alarm setting value, or alarm option changing. When re-applied standby sequence and if it is
AL-F standby sequence2 alarm condition, alarm output does not turn ON.
After clearing alarm condition, alarm latch operates.
※Condition of re-applied standby sequence for standby sequence 1, alarm latch and standby sequence 1: Power ON
Condition of re-applied standby sequence for standby sequence 2, alarm latch and standby sequence 2: Power ON, changing set
temperature, alarm temperature[ AL1, AL2] or alarm operation[ AL-1, AL-2], switching STOP mode to RUN mode.
H-38
High Accuracy Standard PID Control
※Ex)The above is masking auto tuning[ AT], cooling Setting value Descriptions (F)
proportional band[ C-P], cooling integral time[ C-1], Rotary
OFF Auto tuning end encoder
cooling derivative time[ C-D] parameters in parameter
ON Auto tuning run
2group. (G)
Connector/
Before applying mask PAR2 AT H-P C-P Setting group Parameter Set range Factory default Unit Socket
※This function is for new model. ※Auto-tuning continues to run even if the temperature controller
For more information, refer to the DAQMaster user manual. ●●Heating control and cooling control are mutually Tacho/
Speed/ Pulse
opposing operations with inverse outputs. meter
Visit our website (www.autonics.com) to download the
DAQMaster program and the user manual. ●●The PID time constant varies based on the controlled (N)
Display
objects during PID control. unit
Ex)The above is setting user parameter group in the
DAQMaster with alarm output 1 low-limit value [ AL1. Control output (O)
(MV)
L], alarm output 1 high-limit value [ AL1.H], SV-0 100%
Sensor
controller
set value [ SV-0] parameter of parameter 1 group,
heating hysteresis[ hHYS], cooling hysteresis [ cHYS] (P)
Switching
parameters of parameter 2 group, input correction[ IN- Heating control mode power
(Heating) supply
B] parameter of parameter 3 group, alarm output 1
(Q)
hysteresis [ A1.HY], alarm output 2 hysteresis [ A@HY] 0% PV Stepper
parameters of parameter 4 group. Heating control(Reverse operation)
motor&
Driver&Controller
Control output
RUN (MV) (R)
Graphic/
100% Logic
panel
PARU PAR1 PAR5 (S)
Colling control Field
network
(Cooling) device
AL!L AL!HH SV-0 hHYS cHYS
0% PV
(T)
Cooling control(Normal operation) Software
IN-B A!HY A@HY
Setting group Parameter Set range Factory default Unit
※This function is for new model.
(U)
Standard model Other
HEAT -
HEAT/ COOL
PAR3 O-FT
Heating & Cooling
model H-C -
HEAT/ COOL/ H-C
H-39
TK Series
Heating control [ HEAT] Proper usage
Heating control mode: the output will be provided in order
to supply power to the load (heater) if PV (Present Value) Simple "Error" diagnosis
falls below SV (Setting Value). ● When the load (Heater etc) is not operated
Please check operation of the OUT indicator located in
Cooling control [ COOL] front panel of the unit.
Cooling control mode: the output will be provided in order If the OUT indicator does not operate, please check the
to supply power to the load (cooler) if PV (Present Value) parameter of all programmed mode.
rises above SV (Setting Value). If OUT indicator is operating, please check the
output(Relay, SSR drive voltage) after separating output
Heating and cooling control[ H-SC] line from the unit.
Heating and cooling control mode: heating and cooling with ● When it displays OPEN during operation
a single temperature controller when it is difficult to control
subject temperature with only heating or cooling. This is a warning that external sensor is open.
Please turn off the power and check the wire state of the
Heating and cooling control mode controls the object using
sensor. If sensor is not open disconnect sensor line from
different PID time constants for each heating and cooling.
the unit and short the input +, - terminal. Turn on the
It is also possible to set heating and cooling control in both power of the unit and check the controller displays room
PID control or ON/OFF control mode. temperature.
Heating/cooling output can be selected among Relay output, If this unit cannot display room temperature, this unit is
SSR drive output and current output depending on model broken. Please remove this unit and contact our service
types chosen according to your application environment. center. (When the input mode is thermocouple, it is
(Note that only standard SSR control is available for SSR available to display room temperature.)
drive output in OUT2.)
● In case of indicating "Error" in display
Cooling control output
Cooling load This Error message is indicated in case of damaging
Temperature Cooling
inner chip program data by outer strong noise.
drop Temperature control
Temperature sensor
contr oller Heating
In this case, please send the unit to our after service
Input(feedback)
Temperature control center after removing the unit from system.
rise
Heating control output Noise protection is designed in this unit, but it does not
Heating load
stand up strong noise continuously. If bigger noise than
※For heating and cooling control, OUT1 control output is specified(Max. 2kV) flows in the unit, it can be damaged.
dedicated to heating control and OUT2 control output to
cooling control. Caution for using
Control output (OUT1/OUT2) selection ●●Please use separated line from high voltage line or power
line in order to avoid inductive noise.
[ OUT1/ OUT2]
●●Please install power switch or circuit-breaker in order to
●●In case of selecting the Models with current control output, cut power supply off.
both current and SSR drive outputs are available. You
●●The switch or circuit-breaker should be installed near by
can therefore choose the right output type depending on
users.
application environments.
●●This unit is designed for temperature controlling only. Do
- OUT1: Selects OUT1 control output.
not apply this unit as a voltage meter or a current meter.
- OUT2: Selects OUT2 control output.
●●In case of using RTD sensor, 3-wire type must be used.
Setting group Parameter Set range Factory default Unit
If you need to extend the line, 3-wires must be used
OUT1 with the same thickness as the line. It might cause
PAR3 SSR/ CURR SSR -
OUT2 temperature difference if the resistance of line is different.
●●In case of making power line and input signal line close,
line filter for noise protection should be installed at power
For more information, refer to the user manual. line and input signal line should be shielded.
●●Keep away from the high frequency instruments.(High
frequency welding machine & sewing machine, big
capacitive SCR controller)
●●Installation environment
It shall be used indoor.
Altitude Max. 2000m.
Pollution Degree 2
Installation Category Ⅱ.