Professional Documents
Culture Documents
I. OBJECTIVE
Studying the operation of a power transmission line in no-load condition (no-load current
Measure the voltage in no-load, as well as the line and face voltage for inductive load.
Draw connection.
II. INTRODUCTION
This experiment involves studying the "transmission line in no load conditions" as given in
its objectives. Also, this will provide a baseline with the measurement taken when the
transmission line is no-load. Moreover, it also aims to measure the line and face voltage for
inductive load.
line) is a set up conductors that enables the efficient transfer of electricity or power from the
source of generations such as power plants to various distribution units that provides electricity
to commercial, residential, and other consumers. Transmission lines are classified based on their
voltage levels, it consists of Low Voltage (LV) as 240V to 600 V, Medium Voltage (MV) as 2.4
KV to 69 KV, High Voltage (HV) as 115 KV to 230KV, Extra-High Voltage (EHV) as 345 KV to
is under no-load condition, the voltage are typically remains closed to its normal voltage and
rated voltage. On the other hand, the current under no-load condition was very low or minimal,
affected by some phenomena such as voltage drop due to inductance, current and voltage caused
by impedance and other factors. Power transmission line requires deep consideration of these
By measuring the voltage and phase voltage under no-load condition, the experiment aims
to provide insights and deep understanding into behavior and performance of a power
transmission line. These measurements can be used to analyze its efficiency and other important
parameters. Also, this will provide valuable information on the relationship between line and
phase voltage which is essential for understanding the baseline performance of a power
transmission line. It ensures the safe and reliable delivery of electric power to consumers,
needed.
2. Connect jumpers as shown in the drawing /illustration and measure the line voltages of
the circuit breaker and the three-phase transformer with no-load. Record the measured
3. Turn off the supply and connect the three-phase trans former to the Inductive Load
4. Record the measured line and phare voltages of inductive load after turning on the supply
5. Repeat procedure 4, but now for the inductive load with Delta connection.
6. Record the obtained measurements in Table 1.2 and Table 1.3, respectively.
• Three-phase Transformer
-Is an electrical device that is used to transfer electrical energy between three-phase power
system.
-Are used to connect various electrical components in a system. Particularly when dealing
• Multimeter
• Inductive Load
• Circuit Breaker
-Is a safety device that automatically interrupts the flow of electrical current in a circuit when
Determine the voltage and current in the transmission line with increased capacitance.
Compare the results of the transmission line with and without increased capacitance.
Determine the existing relationship between the transmission line and the effect of
capacitance.
II. INTRODUCTION
This experiment involves studying the transmission line with increased capacitance under
no – load condition. The primary objective of the experiment is to determine the value of the
voltage and the current during no – load operation. This will provide a baseline for comparison
with the measurements taken when transmission line is loaded. Also, the experiment aims to
know the existing relationship between the line and effects of the capacitance.
Capacitance in a transmission line is defined as the inherent ability of the line to store
electrical energy in the form of electrical field between its conductors. It is easier to store energy
when capacitance increases and typically it is measured in farads. Due to electric material
between the conductors and physical geometry of a transmission line, the capacitance arises.
When the transmission line is operating in no load, there is “no current (0 ampere) flowing
through the line. At the same time, when capacitance increases the voltage “rises” as a result. The
voltage at the receiving end of the line was higher than the voltage at the sending end. In
When transmission line is connected on an increased capacitive load it can have several
effects on the performance of the system. It may affect the reactive power flow that is useful for
power factor that is efficient in transmission line. Overall connecting an increased capacitive
load under no load condition has both positive and negative effects on the performance of
transmission line.
By measuring the voltage and current under no load condition, the experiment provide
insights and deep understanding into the behavior of the transmission line and its performance
analyzed the efficiency of the transmission line with increased capacitance, its power factor and
other key components/parameters that affect its performance. Additionally, the experiment can
provide valuable information on the relationship between the voltage and current, which is
10. Pre – arrange the simulator as in figure 2.1 and connect the capacitor of the module
11. The reference electric diagram is still that shown in the figure 2.1, whereas the
12. Measure the line voltage and current of the three – phase transformer with no load
13. Turn off supply and connect the three – phase transformer to the capacitive load of 3.5uf
(model CL2/EV)
14. Turn on the supply and measure the line voltage and current of it.
15. Repeat the procedure 6 now with an increased capacitive load of 7uF
16. Record the obtained measurements for voltage and current in 3.5uF, 7uF and 14uF in
• Three-phase Transformer
• Multimeter
• Capacitive load
• Circuit Breaker
• Ground
V. DRAWING/ILLUSTRATION
VI.
VII. DATA TABLE:
VIII. OBSERVATION AND ANALYSIS
IX. CONCLUSION
Experiment No. 3
Determine the voltage and current in the transmission line with increased resistance.
Compare the results of the transmission line with and without increased resistance.
Determine the existing relationship between the transmission line and the effect of
resistance.
II. INTRODUCTION
This experiment involves studying the transmission line with increased resistance under no
– load condition. The primary objective of the experiment is to determine the value of the voltage
and the current during no – load operation. This will provide a baseline for comparison with the
measurements taken when transmission line is loaded. Also, the experiment aims to know the
The current and voltage on a three – phase transmission line can vary the load conditions.
When the transmission line is operating in no load, there is “no current (0 ampere) flowing
through the line. At the same time, when capacitance increases the voltage “rises” as a result. The
voltage at the receiving end of the line was higher than the voltage at the sending end. In
When transmission line is connected on an increased capacitive load it can have several
effects on the performance of the system. It may affect the reactive power flow that is useful for
power factor that is efficient in transmission line. Overall connecting an increased capacitive
load under no load condition has both positive and negative effects on the performance of
transmission line.
By measuring the voltage and current under no load condition, the experiment provide
insights and deep understanding into the behavior of the transmission line and its performance
analyzed the efficiency of the transmission line with increased resistance, its power factor and
other key components/parameters that affect its performance. Additionally, the experiment can
provide valuable information on the relationship between the voltage and current, which is
III. PROCEDURE
IV. MATERIALS/EQUIPMENT
V. DRAWING/ILLUSTRATION
VI.
VII. DATA TABLE:
VIII. OBSERVATION AND ANALYSIS
IX. CONCLUSION
Experiment No. 4
Determine the voltage and current in the transmission line with increased inductance.
Compare the results of the transmission line with and without increased inductance.
Determine the existing relationship between the transmission line and the effect of
inductance.
II. INTRODUCTION
III. PROCEDURE
IV. MATERIALS/EQUIPMENT
V. DRAWING/ILLUSTRATION
VI.
VII. DATA TABLE:
VIII. OBSERVATION AND ANALYSIS
IX. CONCLUSION
Experiment No. 5
IV. PROCEDURE
Turn OFF the breakers at the origin and line 2.
Measurement instruments should be connected to the left busway and
terminals at the start and end of line 2.
To simulate active conductor capacitance, connect the jumpers to line
2's left capacitors. Perform the delta connection to boost capacitive
currents. Choose 0.1 u.F for CL.
To simulate the capacitance between the active conductors and the
ground, connect the jumpers to the set of right capacitors in line 2 and
the jumper that grounds the capacitors star centers.
Since each line conductor provides a capacitance to ground, only the
star connection may be made. Also choose o.1 u.F For CE. set
selection Resistance line 2. to 8.9 ohms and inductance to 0.034 H.
V. DRAWING/ILLUSTRATION
VI. DATA/TABLE
VII. OBSERVATION AND ANALYSIS
VIII. CONCLUSION
Experiment No. 6
Compute for the power loss from sending end to receiving end of the line.
Calculate the total performance of the transmission line with capacitive load.
II. INTRODUCTION
The operation of a transmission line with a capacitive load revolves around understanding
the intricate interplay of electrical signals as they traverse the transmission medium. A
transmission line serves as a conduit for the transfer of electrical energy, embodying properties
like capacitance, inductance, resistance, and conductance. When dealing with a capacitive load,
where the load impedance is predominantly capacitive due to connected capacitors, certain
characteristic behaviors emerge. Notably, capacitive loads induce a leading power factor,
signifying that the current leads the voltage in phase. This capacitive nature results in a
phenomenon known as line charging, where the transmission line accumulates energy in its
The voltage distribution along the transmission line is influenced, with higher voltages near
the sending end tapering towards the receiving end. The presence of capacitive loads can
contribute to reflections, leading to standing waves on the transmission line. Efficient operation
involves compensating for these effects, employing techniques such as series or parallel reactors
or capacitors to optimize electrical characteristics and minimize signal distortions. Managing the
impact of capacitance is crucial for ensuring effective power transfer and maintaining the
III. PROCEDURE
1) Equipment Preparation:
Begin by preparing all the necessary equipment required for the experiment.
2) Connection of Capacitive Load:
Connect the capacitive load to the transmission line trainer, ensuring a secure and
proper connection.
3) Energize Transmission Line Trainer:
Power up the transmission line trainer and measure the line supply voltage to
establish the baseline.
4) Data Collection under Capacitive Load:
Conduct measurements for line voltage, current, and power while the transmission
line is under a capacitive load.
5) Calculation of Parameters:
Utilize the collected data to calculate essential parameters:
Determine the voltage drop along the transmission line.
Calculate the power loss incurred in the system.
Assess the efficiency of the transmission line under the given conditions.
IV. MATERIALS/EQUIPMENT
Compute for the power loss from sending end to receiving end of the line.
Calculate the total performance of the transmission line with inductive load.
II. INTRODUCTION
with the essential parameters that define these conduits. Transmission lines come in various
forms, such as Coaxial cables, twisted pairs, and optical fibers. The key. parameters of interest
include line length, cross-sectional area, and the resistance, inductance, and capacitance per unit
length. These parameters provide the foundational knowledge required for our analysis.
Transmission lines are the vital arteries of our electrical infrastructure, playing a pivotal
role in the seamless distribution of electricity across vast distances, from power generation plants
to end consumers, However, their efficiency and reliability can be faced with significant hurdles
when confronted with inductive loads a common occurrence resulting from devices like electric
Inductive loads pose challenges to transmission lines primarily due to their propensity to
draw reactive power. When these loads are connected to the grid, they augment the current
this translates to reduced voltage levels experienced at the load's end, disrupting the uniformity
Voltage Regulation Challenges: the presence of inductive loads can undermine voltage
regulation, causing irregular voltage drops along the transmission lines, ultimately
Power Factor Correction: Inductive loads typically exhibits a lagging power factor,
consuming more reactive power in comparison to real power. To address this, utilities
Increased Losses: The heightened current flow prompt by inductive loads leads to
escalated losses, specifically I 2 R losses (whore "I'"denotes current and "R" signifies
potentially
transmission line performance under inductive load conditions. Utilities and engineers deploy
various strategies, including power factor corrector in techniques, meticulous line designs, and
inductive loads, maintaining the reliability, efficiency and stability of electrical grid.
technology to navigate the complexities introduced by inductive loads and ensure the robustness
electrical infrastructure.
III. PROCEDURE
1. Prepare the necessary equipment to be used in conducting the experiment.
3. Energize the transmission line trainer and measure the line supply voltage.
4. Obtain the line voltage, current and the power under inductive load.
5. Calculate the voltage drop, power loss and efficiency of the line using the data.
IV. MATERIALS/EQUIPMENT
Wattmeter
Connecting wires
alligator clip
apparatus
2/EV)
V. DRAWING/ILLUSTRATION
VI. DATA TABLE
VII. OBSERVATION AND ANALYSIS
VIII. CONCLUSION
Experiment No. 8
ELECTRICAL SUBSTATION
II. INTRODUCTION