Refresher Module – Structural Engineering (Combined Footings)


SITUATION:
A combined rectangular footing supports an exterior column (450mm
square) and an interior column of (500mm square) placed at a distance
center to center equal to 3.6m. The exterior column having its face along
the property line carries a DL = 535kN and LL = 446kN. The interior
column having a DL = 892kN and LL = 668kN. The bottom of the footing is
to be 1.8m below the grade. Allowable soil bearing capacity is 240kPa.
Weight of soil is 15.74kN/m3 and that of concrete is 23.5kN/m3. Take fc’
= 20.7MPa, fy = 415MPa. Assume footing thickness of 650mm. Use
75mm as steel covering.
1. Determine the dimension of the rectangular combined footing.
A. 5.21x1.61x0.65 B. 4.87x2.53x0.65
C. 2.21x4.68x0.65 D. 5.92x1.13x0.65
2. Determine the maximum moment of the footing along the longitudinal
section.
A. -547.11 B. -957.87 C. -845.81 D. -618.94
3. Determine the ultimate punching shear force on the exterior column.
A. 1141.19 B. 1257.84 C. 797 D. 1811.42
4. Determine the ultimate punching shear force on the interior column.
A. 1141.19 B. 1257.84 C. 797 D. 1811.42
5. Determine the ultimate wide beam shear force on the interior column.
A. 1141.19 B. 1257.84 C. 797 D. 1811.42
6. Determine the required longitudinal reinforcement.
A. 15-18 B. 8-28mm C. 9-32 D. 7-22
7. Determine the required transverse reinforcement for the side of the
interior column.
A. 4-28mm B. 5-22mm C. 10-16mm D. 3-28mm
8. Determine the required transverse reinforcement for the side of the
exterior column.
A. 6-28 B. 10-16mm C. 3-28mm D. 5-22