1 - Overview
While this report covers many areas, it is not fully comprehensive and does NOT replace the need for those involved with the hotel project, to read,
understand and utilize the IHG Engineering Standards. The IHG Engineering Standards provide the details necessary for a proper and compliant installation.
IMPORTANT :-
– For all new build hotel projects, compliance with all points listed must be attained prior to hotel opening.
– For re-branding and conversion hotel projects, priority and completion targets will be noted by the inspection engineer.
These priority and completion targets will be broken down into 2 Phases as follows:-
PHASE 1 Works – Essential Fire Life Safety and Brand Standards Compliance.
Phase 1 works must be completed prior to hotel opening (or re-branding as the case may be).
In all cases, the final inspection prior to hotel opening will be arranged only after the assigned IHG Engineer gives the approval to do so. This
approval will be based on the successful completion of the “Approval for Final Inspection” form found in Section 4 of this document.
Proposed Date for Inspection: (Note this needs to be confirmed with the person conducting the final inspection)
Signature:
Pass/Fail
Date of Inspection Conducted By Comments
(Yes/No)
English.
263148
Provide a minimum sound level of
65dBA in Places of Assembly.
Include an alarm. 263149
The evacuation system is capable of
10
single zone or multi zone paging.
The evacuation system will automatically
12
switch off any BGM or AV system.
Strobe lights and warning bells are
15
installed in FOH & BOH areas.
The detection & evacuation systems
16 wiring is "Class A" (To allow for line
monitoring).
A mimic/ repeater panel (where required)
meets the following requirement:
installed in the Telephone Operator
room or an area where it is manned
by Hotel Personnel 24/7.
Panel Includes both an audible and
visual alarm.
Panel indicates the overall status of
18
the system.
Panel indicates the specific zone
which initiated the alarm (public
areas) and specific room (guestroom).
Panel includes a general alarm feature
(break glass).
Procedure/ mechanism for alarm
delay (while investigating).
23 All initiating devices (Ie. smoke detectors,
flow switches etc) sound an alarm at the
5.5 MANUAL CALL STATIONS ARE INSTALLED IN ALL AREAS AND AT DESIGNATED EXITS IN:
Date
Issue Comments & Actions required to achieve IHG/
# OBSM YES PAR NO N/A
International Standard
Priority Comments/Progress Completed
TIAL
Manual call points are provided in all 26313
0
FOH & BOH areas. Including:
At or close to the front desk
Each ground floor exit 26313
Each Stair Access point 1
1
26313
2
26313
3
26312
9
The maximum travel distance between
manual call points must not exceed 37620
10 7
60m. (For new Properties. Existing
properties on a case-by-case basis).
requirements:
56047
At least 2 separate exits for 50 to 500
people.
At least 3 separate exits for 501 to 56048
1000 people.
More than 1001 people, minimum of 56049
four separate exits, to be validated
by a Qualified Person.
Exit Doors Remote from each other 56050
56448
27806
0
Swimming pool depth markings must be 56449
7
clearly displayed.
Safety features for Swimming Pool and
Hot Tub are provided accordingly:
Minimum of two drains are required. 58204
9
Anti-entrapment drain covers are
required in all Pools and Hot Tub 58205
with a single drain. 0
Minimum of 1.5m of clear deck
8 space must be provided around the
perimeter of all Swimming Pools. 56485
Swimming Pool deck must be slip
resistant.
Ladders, steps and/ or ramps with 56438
handrails must be provided at
opposite ends of the Swimming Pool.
56441