INITIAL LATERAL PILE LOAD TEST REPORT

Issued To: -
M/s Balabharti Infrastructure Pvt. Ltd.
Client: -
Hindustan Steel Works Construction Ltd.
(HSCL), Delhi

Project Name: -
“Construction of ROB in Lieu of LC. 407B at KM. 1205/6-8
on Jhansi-Gwalior Section”

Location: -
A1 Side, (Test Pile - 1)

Date of Testing: -
24-01-2024
Date of Report: -
30-01-2024

ULR NO. TC638523335731063


Submitted By: -
M/s ME TESTING LABORATORY JAIPUR.
TABLE OF CONTENTS

1. INTRODUCTION

1.1 Project Description


1.2 Object of Testing

2. USING IS CODE IN PRACTICE

3. DETAILS OF PILE

4. TEST PROCEDURE

5. TEST RESULTS AND INTERPRETATION

6. SUMMARY OF PRINCIPAL FINDINGS

7. CLOSURE

8. LOADING SCHEME

9. EQUIPMENT DETAILS

10. ANNEXURE : A (SITE OBSERVATIONS DATA)

11. ANNEXURE : B (LOAD VS DISPLACEMENT CURVE)

12. ANNEXURE : C (TEST SETUP DRAWING)

13. ANNEXURE : D (TESTING/CALIBRATION CERTIFICATES)


1 Introduction

1.1 PROJECT DESCRIPTION

The Hindustan Steel Works Construction Ltd. (HSCL), Delhi has awarded a work
of Construction of ROB in Lieu of LC. 407B at KM. 1205/6-8 on Jhansi-Gwalior
Section to M/s Balabharti Infrastructure Pvt. Ltd. The work of pile load testing
has been awarded to M/s ME Testing Laboratory Jaipur by M/s Balabharti
Infrastructure Pvt. Ltd.

1.2 OBJECT OF TESTING

The purpose of this study was to have a check on calculation of safe load of pile. To
accomplish this purpose, the study was conducted in the following phases.

2 USING IS CODE IN PRACTICE


 As per IS 2911 (Part 4): 2013, the safe load on pile for Initial Lateral load test
should be the following: -

 Testing one piles, 1200MM dia, 30.0m long to to 2.5 Times the designed
load or failure whichever occurs first.
 Fifty percent of the final load at which the total displacement increases
to 12mm.
 Final load at which the total displacement corresponding to 5mm.
 Preparing the technical report presenting and analysing the load test
result.

3 DETAILS OF PILE

The Initial Lateral Pile Load Test was conducted on Bored cast-in-situ pile with
1200mm diameter.
Following table summarizes the pile details.
PILE DETAILS
Type of Pile Bored cast-in-situ
Pile Diameter 1200 mm
Lenght of Pile 30.0 Meters
Pile Location A1 Side (Test Pile -1)
Date of Casting 01-Nov-2023
Date of Testing 24-Jan-2024
Design Load 10.0 MT
Test Load (2.5 x 10) 25.0 MT
Grade of Concrete M-35

4 TEST PROCEDURE
The procedure of the test was in general accordance with IS 2911 (Part 4): 2013. The
reaction for applying Lateral load on the Pile is taken as per arrangement shown.
The test load was applied on the pile Lateral by means of a Hydraulic jack and a
controlled pressure pump. The load was applied in increments of about 20% of the
design load.

Each stage of loading shall be maintained till the rate of movement of the pile side is
not more than 0.10 mm/30 subjects magnetic base and datum bars. to minimum of
30 min. Displacement were recorded by means of Two dial gauges of 0.01mm least
counts. Dial gauges spaced at 30 cm at a suitable height and the Displacement
interpolated at the load point from Triangle. The maximum load applied 2.5 times of
design load or failure whichever occurred first. Unloading may be carried out, if
possible. A period of 10 minutes may be allowed to elapse between the two
successive stages of load decrement.

5 TEST RESULTS AND INTERPRETATION


The following shows the critical data of test results as obtained from the Initial
Lateral Pile Load Test.
 Design load = 10.0 MT
 Applied Load = 23.73 MT
 Total Displacement = 12.625 mm
 Rebound = 2.825 mm
 Net Displacement = 9.80 mm
IS 2911 (Part 4): 2013 It can also be observed from the load displacement curves
that the total displacement curve is 12.625 mm at final load 23.730 MT which is
less than allowable displacement as per criteria (8.4 - a & b): -
 Criterion (a): 50% of the final load at which the total displacement increases
to 12mm = 50% of 22.2 MT = 11.10 MT
 Criterion (b): Final load at which the total displacement corresponding to
5mm = 8.0 MT
Hence pile of 1200mm dia 30.0m long is safe for its design load 11.10 MT in Lateral.

6 SUMMARY OF PRINCIPAL FINDINGS


M/s ME Testing Laboratory jaipur carried out Initial Lateral load test
Construction of ROB in Lieu of LC. 407B at KM. 1205/6-8 on Jhansi-Gwalior
Section on the behalf of Pile 1200mm dia & 30.0m long is safe for 10.0 MT load in
Lateral.

7 CLOSURE

We appreciate the opportunity to submit this report. Please contact us if you need
any clarification.

Tested by

For M/s ME Testing Laboratory

AUTH. SIGNATORY
8 LOADING SCHEME
 Design Pile Load = 10.0 MT
 Test Load (2.5 x 10) = 25.0 MT
 Effective Bore Dia of Hydraulic Jack = 120 mm
 Effective Bore Area of Hydraulic Jack = 113.112 cm2 ...(A)
 Least Count of Pressure Gauge = 10 kg/cm2 ...(P)
 Each Small Division on Pressure Gauge = P x A = (kg/cm 2 x cm2)
= 10 x 113.112 = 113.112 kg Say = 113.112/1000 = 1.13 MT
 Required Each Increment of Final Test Load Approximate 20% of 10 is = 2 MT
 Applied Each Increment which is (1.13 x 2.0) = 2.26 MT
S. Required Applied Pressure Applied load Displacement
Description
No load in MT in kg/cm2 in MT in MM
0 Increment 0 0 0 0
1 Loading 2.0 20.0 2.26 0.025
2 cycle 4.0 40.0 4.52 0.080
3 6.0 60.0 6.78 0.185
4 8.0 80.0 9.04 0.275
5 10.0 100.0 11.30 0.740
6 12.0 120.0 13.56 1.525
7 14.0 140.0 15.82 2.880
8 16.0 160.0 18.08 5.065
9 18.0 180.0 20.34 7.990
10 20.0 200.0 22.60 11.335
11 22.0 210.0 23.73 12.625
12 20.0 200.0 22.60 12.660
13 16.0 160.0 18.08 12.505
14 12.0 120.0 13.56 12.255
(Rebound)
15 8.0 80.0 9.04 11.740
16 4.0 40.0 4.52 10.990
17 0 0 0 9.800
9 EQUIPMENT DETAILS
 Total Nos. of Hydraulic Jack - 1 nos
 Capacity of Hydraulic Jack each - 50.0 MT
 Total Nos of Dial Gauges - 2 Nos
 Least Count od Dial Gauge - 0.01 mm
 Magnet Base - 2 nos
 Hydraulic Hand Pump - 1 nos
 Hose Pipe - 1 nos
 Pressure Gauge Range - 0-600 kg/cm2
 Datum bar - 1 Nos
 Auto Level, Sprite Level etc.
ANNEXURE : A (SITE OBSERVATIONS DATA)
INITIAL LATERAL PILE LOAD TEST
PROJECT Construction of ROB in Lieu of LC. 407B at KM. 1205/6-8 on Jhansi-Gwalior Section
PILE TYPE BORED CAST IN SITU DESIGN SAFE LOAD 10.0 METRIC TON
PILE DIA 1200 MM DATE OF CAST 1/11/2023
PILE LENGTH 30.0 M DATE OF TEST 24/1/2024
RAM DIA. 120 MM 1 DIV. OF PG 10 KG/SQ CM
RAM AREA 113.112 CM² LOAD ON 1 DIV. 1.13 MT
DATE TIME Pressure LOAD READING, mm AVG SETTLEMENT
DIAL
IN HRS in kg/cm² IN MT DIAL GAUGE I mm
GAUGE II
24/01/2024 10:30 AM 0 0 0.00 0.00 0.0
" 10:30 20.0 2.26 0.02 0.03 0.025
" 11:00 " " 0.02 0.03 0.025
" 11:00 40.0 4.52 0.06 0.08 0.070
" 11:30 " " 0.07 0.09 0.080
" 11:30 60.0 6.78 0.16 0.19 0.175
" 12:00 PM " " 0.17 0.20 0.185
" 12:00 80.0 9.04 0.23 0.27 0.250
" 12:30 " " 0.25 0.30 0.275
" 12:30 100.0 11.30 0.66 0.75 0.705
" 1:00 " " 0.69 0.79 0.740
" 1:00 120.0 13.56 1.40 1.56 1.480
" 1:30 " " 1.44 1.61 1.525
" 1:30 140.0 15.82 2.69 2.94 2.815
" 2:00 " " 2.75 3.01 2.880
" 2:00 160.0 18.08 4.76 5.22 4.990
" 2:30 " " 4.83 5.30 5.065
" 2:30 180.0 20.34 7.61 8.20 7.905
" 3:00 " " 7.69 8.29 7.990
" 3:00 200.0 22.60 10.84 11.64 11.240
" 3:30 " " 10.93 11.74 11.335
" 3:30 210.0 23.73 12.08 12.93 12.505
" 4:00 " " 12.19 13.06 12.625
LOAD REBOUND (RELEASE)
24/01/2024 4:00 PM 200.00 22.60 12.23 13.11 12.670
" 4:15 " " 12.22 13.10 12.660
" 4:15 160.00 18.08 12.11 12.97 12.540
" 4:30 " " 12.08 12.93 12.505
" 4:30 120.00 13.56 11.89 12.71 12.300
" 4:45 " " 11.85 12.66 12.255
" 4:45 80.00 9.04 11.44 12.19 11.815
" 5:00 " " 11.37 12.11 11.740
" 5:00 40.00 4.52 10.76 11.46 11.110
" 5:15 " " 10.65 11.33 10.990
" 5:15 0 0 9.82 10.30 10.060
" 5:30 " " 9.58 10.02 9.800
ANNEXURE : B (LOAD VS DISPLACEMENT CURVE)

 Total Displacement at the 12.625 final load mm at 2.5 times of design load.
 After Reboun of Test load Net Displacement is 9.80 mm.
Pile Location A1 Side (Test Pile -1)
Pile Dia 1200 MM
Pile Lenght 30.0 Meters
Design Load 10.0 MT
Applied Load 23.73 MT
Date of Cast 01-Nov-2023
Date of Test 24-Jan-2024
ANNEXURE : C (TEST SETUP DRAWING)
ANNEXURE : D (CALIBRATION CERTIFICATES)