EQUIPMENT SCHEDULE - 27/05/2021

SMOKE CONTROL AIR VOLUME S.P POWER POWER SUPPLY EMERGENCY


ITEM QUANTITY (EA) SERVICE LOCATION INVERTER REMARK
SYSTEM (Ph/Volt/Hz) POWER
NORMAL (CMH) EMERGENCY (CMH) NORMAL (mmAq) EMERGENCY (mmAq) NORMAL (kW) EMERGENCY (kW)

EAF-B2-01 & 02 SMOKE PURGING DUTY :1 B2F LOADING AREA B1F. LOADING TO INPUT BY MEP 66,000 20 TBA 7.5 30 1/230/50 - 0 - INCLUDE ALL ACCESSORY INCLUDING NRD AND SILENCERS. ^
STANDBY :1 AREA

FAF-B2-01 & 02 SMOKE PURGING DUTY :1 B2F LOADING AREA B1F. LOADING TO INPUT BY MEP 66,000 20 TBA 7.5 30 3/400/50 - 0 - INCLUDE ALL ACCESSORY INCLUDING NRD AND SILENCERS. ^
STANDBY :1 AREA

EAF-B1-01 & 02 DUCTLESS JETFAN DUTY: 2 B1F CAR PARK ZONE 1 B1F CAR PARK TO INPUT BY MEP 22,500 30 TBA 5 11 1/230/50 - 0 - INCLUDE ALL ACCESSORY INCLUDING NRD AND SILENCERS. ^

FAF-B1-03 & 04 DUCTLESS JETFAN DUTY: 2 B1F CAR PARK ZONE 2 B1F CAR PARK TO INPUT BY MEP 36,000 30 TBA 5 11 3/400/50 - 0 - INCLUDE ALL ACCESSORY INCLUDING NRD AND SILENCERS. ^

EAF-B1-03 & 04 DUCTLESS JETFAN DUTY: 2 B1F CAR PARK ZONE 2 B1F CAR PARK TO INPUT BY MEP 36,000 30 TBA 7.5 11 3/400/50 - 0 - INCLUDE ALL ACCESSORY INCLUDING NRD AND SILENCERS. ^

EAF-L6-01 to 03 SMOKE PURGING DUTY :1 6F ASSEMBLED 6F. FAN ROOM TO INPUT BY MEP 65,000 40 TBA 11 30 3/400/50 - 0 - INCLUDE ALL ACCESSORY INCLUDING NRD AND SILENCERS. ^
STANDBY :1 CAR STORAGE ZONE 1

EAF-L6-04 & 05 SMOKE PURGING DUTY :1 6F ASSEMBLED 6F. CAR STORAGE TO INPUT BY MEP 35,000 20 TBA 3.7 11 3/400/50 - 0 - INCLUDE ALL ACCESSORY INCLUDING NRD AND SILENCERS. ^
STANDBY :1 CAR STORAGE ZONE 2

EAF-L7-01 to 03 SMOKE PURGING DUTY :1 7F ASSEMBLED 7F. FAN ROOM TO INPUT BY MEP 75,000 40 TBA 11 30 3/400/50 - 0 - INCLUDE ALL ACCESSORY INCLUDING NRD AND SILENCERS. ^
STANDBY :1 CAR STORAGE ZONE 1

EAF-L7-04 & 05 SMOKE PURGING DUTY :1 7F ASSEMBLED 7F. CAR STORAGE TO INPUT BY MEP 38,000 20 TBA 3.7 11 3/400/50 - 0 - INCLUDE ALL ACCESSORY INCLUDING NRD AND SILENCERS. ^
STANDBY :1 CAR STORAGE ZONE 2

SEF-L2-01 to 10 ENGINEERED DUTY :9 1F 2F CEILING - 80,000 - TBA - 35 3/400/50 - 0 - INCLUDE ALL ACCESSORY INCLUDING NRD AND SILENCERS. ^
SMOKE CONTROL STANDBY :1 PRODUCTION AREA

SEF-L2-11 to 13 ENGINEERED DUTY :2 1F 2F CEILING - 90,000 - TBA - 35 1/230/50 - 0 - INCLUDE ALL ACCESSORY INCLUDING NRD AND SILENCERS. ^
SMOKE CONTROL STANDBY :1 LOBBY & GALLERY

SEF-L4-01 to 10 ENGINEERED DUTY :9 3F 4F CEILING - 80,000 - TBA - 35 1/230/50 - 0 - INCLUDE ALL ACCESSORY INCLUDING NRD AND SILENCERS. ^
SMOKE CONTROL STANDBY :1 PRODUCTION AREA
^ Note: It is recommended (market practise) to provide silencer to reduce the noise level due to minimum dBA requirement for alarm bell and Emergency Voice Communication System