You are on page 1of 5

ELECTRICAL POWER SYSTEM WORK

PROJECT TITEL : PARAGON 1 - NEW CAPITAL


Date : Dec, 2022

IFT Ref. Item Description Qty Unit Rate Amount

16 Electrical System

General Notes

The following items should be included in the price.


A Contactor shall obtain authorities approvals during construction stage, preparing all official
submissions
B Contactor shall review all drawings, preparing shopdrawings, MEP composite, as built drawings
and all official submissions.
C All related civil and mechanical works which are necessary for complete the installation are the
responsibility of the contractor.
D
The drawings’ details are for guidance only; the contractor is responsible for all sizing,
calculations, coordination with other trades,. ..etc., and all necessary ancillary works and
accessories required for complete installation as per drawings and specs.
E All decorative lighting fixtures will be supplied by owner and installing as per ID
recommendations and selection by Electrical contractor.
F Lighting and Power systems calculations (LUX, V.D, S.C, Selectivity, Cable tray filing ratio,
Earthing, Lightning…..) should be submitted and approved by consultant engineer.
G
Contactor shall review and check KNX actuators channel size and ampere rating in distribution
boards, Sensors and touchscreens options to meet recommendation of equipments supplier
and consultant.
H Panels busbar rating should be larger than circuit breaker rating after derating factors as per
supplier derating table and loads.
I The contractor is required to supply all materials and equipment necessary to finalize the work
whether mentioned or not mentioned in the bill of quantities.
J
The work mentioned here shall include supply, erection, termination, installation, routing cable
tray, cable trench completing with necessary accessories, testing and commissioning of all the
items according to the applicable specifications, code, Electrical authority requirements,
telecom authority requirements, environmental limitation and as shown on the project
drawings.
ELECTRICAL POWER SYSTEM WORK

PROJECT TITEL : PARAGON 1 - NEW CAPITAL


Date : Dec, 2022

IFT Ref. Item Description Qty Unit Rate Amount

To Collection LE 0

1.1 LIGHTING INSTALLATION


1.1.1 LIGHTING OUTLETS

Supply, install, connect, test and put into operation lighting outlets complete with all
conduits, conduit fittings, terminations, fittings, to control modules, cables to other
socket to lighting switches or back to the panelboard, junction boxes, pull boxes, cap
connectors, components, accessories and all related ancillary works as shown on
drawings and specified in specifications.
32 1.1.1.1
1,120 846 947,520
Lighting outlets by copper wire 3(1x3) sqmm in 20 mm medium gauge pvc conduit Nr.
32 1.1.1.2
300 874 262,200
Lighting outlets by copper wire 3(1x3) sqmm in 20 mm heavy gauge pvc conduit Nr.
32 1.1.1.3 Lighting outlets by copper wire (4(1x3) sqmm) in 20 mm fire resistance pvc conduit for
EXIT SIGN/Backup battery lighting fixtures 630 1,028 647,640
Nr.
32 1.1.1.4
Lighting outlets by copper wire 3(1x3) sqmm in 20 mm EMT conduit 60 2,282 136,920
Nr.
32 1.1.1.5
Lighting outlets by copper wire 4(1x3) sqmm in 20 mm EMT conduit for Backup battery 20 2,435 48,700
lighting fixtures Nr.
33 1.1.1.6
Lighting outlets by thermoplastic copper cable (3x3) sqmm in 20 mm heavy gauge 100 HOLD
upvc conduit for Façade Nr.
33 1.1.1.7
Lighting outlets by thermoplastic copper cable (3x4) sqmm in 25 mm heavy gauge 150 2,700 405,000
upvc conduit for landscape Nr.

1.2 SMALL POWER SYSTEMS


1.2.1 Electrical Outlets:

Supply, install, connect and test and put into operation electrical outlet, complete with
all outlet boxes, conduits, conduit fittings, terminations, cables to other socket,
isolating switch, electrical outlet or back to panelboard, junction boxes, pullboxes, cap
connectors, accessories and all related ancillary works as shown on drawings and
specified in specifications.

35 1.2.1.1
Single Phase single/duplex outlet by copper wires 3(1x3) mm2 in 20 mm medium 919 156,230
gauge pvc conduit. 170 Nr.
35 1.2.1.2
Single Phase single/duplex outlet by copper wires 3(1x3) mm2 in 20 mm heavy gauge 952 75,208
pvc conduit. 79 Nr.
38 1.2.1.3
Single Phase Electrical Power single outlet 20 AMP by copper wires 3(1x4) mm2 in 20 4,886 112,378
mm heavy gauge pvc conduit 23 Nr.
38 1.2.1.4
Single Phase Electrical Power single outlet 20 AMP by copper wires 3(1x4) mm2 in 20 4,742 241,842
mm medium gauge pvc conduit 51 Nr.
37 1.2.1.5
Three Phase Electrical Power outlet 20 AMP by copper wires 5(1x4) mm2 in 25 mm 5 Nr. 8,832 44,160
heavy gauge pvc conduit
0
1.3 Lighting Switches: 0

Supply, install, connect, test and put into operation lighting switch complete with the 0
switch fixture and all outlet boxes, conduits, conduit fittings, terminations, cables to
nearest lighting fixture, junction boxes, pull boxes, cap connectors, accessories and all
related ancillary works as shown on drawings and specified in specifications.
58 1.3.1 One way, one gang switch 10A, 250v 50 Nr. 557 HOLD
59 1.3.3 One way, two gang switch 10A, 250V 6 Nr. 710 HOLD
0
1.4 FIRE ALARM OUTLETS 0

Supply, install, connect, test and put into operation alarm outlets complete with hot
dip galvanized steel conduits 20 mm dia. for exposed installation, medium gauge fire
retandant pvc conduits 20 mm dia. for embedded installation, conduit fittings, back 0
boxes, junction box, shielding 105C degree 2x1.5sqmm copper conductor fire
resistance wiring, components, accessories and all related ancillary works as shown on
drawings and specified in specifications.
176 1.4.1 Addressable fire alarm detector outlet 396 Nr. 2,262 895,752
181 1.4.2 Addressable fire alarm call point outlet 69 Nr. 2,262 156,078
182 1.4.3 Fire alarm siren with strop light outlet 79 Nr. 2,262 178,698
179 1.4.4 Control module outlet 6 Nr. 2,262 13,572
180 1.4.5 Monitor module outlet 33 Nr. 2,262 74,646
DC outlet with 2x2.5sqmm copper conductor fire resistance wiring inside 25 mm dia.
1.4.8
hot dip galvanized steel conduits 118 Nr. 4,874 575,132
0
1.5 IP TELEPHONE AND DATA SYSTEM OUTLETS 0

Supply, Install, connect, test and put into operation Tel/Data outlets including Cat6 0
cables, conduits, conduit fittings, cable ducts, boxes and all necessary accessories and
ancillary works and materials required for complete installations starting from outlet
up till its data rack as specified and as indicated on the drawings.
188 1.5.1 Outlet using CAT-06 Cable inside 20mm medium gauge pvc conduit Nr. 2,841 230,121
81
ELECTRICAL POWER SYSTEM WORK

PROJECT TITEL : PARAGON 1 - NEW CAPITAL


Date : Dec, 2022

IFT Ref. Item Description Qty Unit Rate Amount

To Collection LE
ELECTRICAL POWER SYSTEM WORK

PROJECT TITEL : PARAGON 1 - NEW CAPITAL


Date : Dec, 2022

IFT Ref. Item Description Qty Unit Rate Amount

189 1.5.2 Outlet using CAT-06 Cable inside 20mm medium gauge pvc conduit for ACP 8 Nr. 2,841 22,728
188 1.5.3 Outlet using CAT-06 Cable inside 20mm heavy gauge pvc conduit 28 Nr. 2,870 80,360
189 1.5.4 Outlet using CAT-06 Cable inside 20mm heavy gauge pvc conduit for ACP 7 Nr. 2,870 20,090
0
1.6 OVER IP CCTV OUTLETS 0

Supplying, installing, connecting, testing and put into operation POE CCTV outlets 0
including Cat6 cables, conduits, conduit fittings, cable ducts, boxes and all necessary
accessories and ancillary works and materials required for complete installations
starting from outlet up till its data rack as specified and as indicated on the drawings.
190 1.6.1 IP-CAM outlet using CAT-06 Cable inside 20mm medium gauge pvc conduit 52 Nr. 2,841 147,732
190 1.6.2 IP-CAM outlet using CAT-06 Cable inside 20mm heavy gauge pvc conduit 50 Nr. 2,870 143,500
0
1.7 PUBLIC ADDRESS OUTLETS 0

Supply, install, connect, test and put into operation public address outlets complete
with all conduits, conduit fittings, terminations, fittings, cabling, to volume controls, 0
junction boxes, pull boxes, components, accessories and all related ancillary works as
shown on drawings and specified in specifications.
205 Ceiling/wall loud speaker outlet by copper wires (2x1.5) mm2 shielded sound cable in
1.7.1
20 mm fire retardant medium gauge pvc conduit. 100 Nr. 1,429 142,900
0
1.8 ACCESS CONTROL SYSTEM OUTLETS 0

Supplying, installing, connecting, testing and put into operation access control outlets
including Cat6A cables, conduits, conduit fittings, cable ducts, boxes and all necessary 0
accessories and ancillary works and materials required for complete installations as
specified and as indicated on the drawings.
201 1.8.1 Outlet using CAT-06 Cable inside 20mm medium gauge pvc conduit. 41 Nr. 2,841 116,481
201 1.8.2 Outlet using CAT-06 Cable inside 20mm heavy gauge pvc conduit. 46 Nr. 2,870 132,020

To Collection LE 0
ELECTRICAL POWER SYSTEM WORK

PROJECT TITEL : PARAGON 1 - NEW CAPITAL


Date : Dec, 2022

IFT Ref. Item Description Qty Unit Rate Amount

Total - Electrical System LE 6,007,608