DEAD LOAD
2 On Roof :
Wt. of sheeting, fixtures etc. - 7 kg/m2
Wt. of purlins - 14 kg/m2
Total : 21 kg/m2 @ 5.50m = 115.5 kg/m 1.16 kN/m
@ 2.75m = 57.75 kg/m 0.58 kN/m
3 Cladding :
Wt. of cladding - 30 kg/m2 @ 5.50m = 165 kg/m 1.65 kN/m
@ 2.75m = 82.5 kg/m 0.83 kN/m
@ 6.50m = 195 kg/m 1.95 kN/m
@ 3.25m = 97.5 kg/m 0.98 kN/m
Vb = 39 m/s
k1 = 1.07 k3 = 1.0 k2 = 1.05 (Cat. 2) k4 = 1.00
Kd= 0.9 Ka = 0.9 (For all the manabers in building structure frame the Tributary area is more than 25 m2, but less than 100 m2)
For referance load case the force on the mamber are determined by multiplying pd with the tributary area of the mambers.
The effect of (Cpe-Cpi) X Kc will be taken care of in Actual wind load cases.
C D E
A B
A B
F
A B C D E F
5.50m 5.34 5.34 5.34 5.34 kN/m
2.75m 2.67 2.67 2.67 2.67 kN/m
6.50m 6.31 6.31 kN/m
3.25m 3.15 3.15 kN/m
0.60p 0.60p
0.80p 0.80p h= 9.1 m
wind l= 22 m
w= 13 m
90deg +/- 0.5p 9.1 m
h/w = 0.70
l/w = 1.69 0.590909
0.10p 13 m
0.70p
F 0.18p
A B C D E F
near 5.50m 4.80 4.80 6.24 6.24 kN/m
far 5.28 5.28 kN/m
near 2.75m 2.40 2.40 3.12 3.12 kN/m
far 2.64 2.64 kN/m
6.50m 3.40 1.13 kN/m
3.25m 1.70 0.57 kN/m
F 1.20p
A B C D E F
near 5.50m 0.00 0.00 1.60 1.60 kN/m
far 0.53 0.53 kN/m
near 2.75m 0.00 0.00 0.80 0.80 kN/m
far 0.27 0.27 kN/m
6.50m -2.52 7.57 kN/m
3.25m -1.26 3.78 kN/m
Seismic Loading
Parameters considered