You are on page 1of 73

TEST REPORT

IEC 61727
Photovoltaic (PV) systems
Characteristics of the utility interface

Report reference number .............. : PV2208WDG0121-1


Date of issue .......................... ……...: 2022-09-15
Total number of pages ........... ……...: 74

Testing laboratory name ............... : Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch
Address ............................................ : No. 96, Guantai Road (Houjie Section), Houjie Town, Dongguan City,
Guangdong Province, 523942, People’s Republic of China
Accrediation ..................................... :

Applicant's name ........................... : Huawei Technologies Co., Ltd


Address ............................................ : Administration Building, Headquarters of Huawei Technologies Co.,
Ltd., Bantian, Longgang District, Shenzhen, Guangdong, 518129,
China

Test specification
Standard .......................................... : IEC 61727:2004-12

Test Report Form No. ...................... : IEC/EN 61727 VER.2


TRF Originator ................................. : Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch
Master TRF ...................................... : Dated 2020-03-20

Test item description ..................... : SOLAR INVERTER


Trademark ........................................ :

Model / Type .................................... : SUN2000-100KTL-M2, SUN2000-115KTL-M2


This report is governed by, and incorporates by reference, the Conditions of Testing as posted at the date of issuance of this report at http://www.bureauveritas.com/home/about-us/our-
business/cps/about-us/terms-conditions/ and is intended for your exclusive use. Any copying or replication of this report to or for any other person or entity, or use of our name or trademark, is permitted
only with our prior written permission. This report sets forth our findings solely with respect to the test samples identified herein. The results set forth in this report are not indicative or representative of
the quality or characteristics of the lot from which a test sample was taken or any similar or identical product unless specifically and expressly noted. Our report includes all of the tests requested by you
and the results thereof based upon the information that you provided to us. Measurement uncertainty is only provided upon request for accredited tests. Statements of conformity are based on simple
acceptance criteria without taking measurement uncertainty into account, unless otherwise requested in writing. You have 60 days from date of issuance of this report to notify us of any material error or
omission caused by our negligence or if you require measurement uncertainty; provided, however, that such notice shall be in writing and shall specifically address the issue you wish to raise. A failure
to raise such issue within the prescribed time shall constitute your unqualified acceptance of the completeness of this report, the tests conducted and the correctness of the report contents.

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 1 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Ratings ............................................ : SUN2000-100KTL-M2 SUN2000-115KTL-M2


MPP DC voltage range [V] ............... : 200-1000
Maximum Input DC voltage [V] ........ : 1100
Maximum Input DC current [A] ........ : 30,0 x 10 strings
Output AC voltage [V] ...................... : 230/400, 3L/N/PE, 50/60Hz
480, 3L/PE, 50/60Hz
Maximum Output AC current [A] ...... : 160,4(230/400V), 133,7(480) 182,3(230/400V), 151,9(480)
Nominal Output power [kW] ............. : 100 115
Maximum Output power [kVA] ......... : 110 125

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 2 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Testing Location ............................. : Huawei Technologies Co., Ltd


Address ............................................ : Administration Building, Headquarters of Huawei Technologies Co.,
Ltd., Bantian, Longgang District, Shenzhen, Guangdong, 518129,
China

Tested by
(name and signature) ....................... : Ryan He

Approved by
(name and signature) ....................... : Ken Chan

Manufacturer’s name ..................... : Huawei Technologies Co., Ltd


Manufacturer address ...................... : Administration Building, Headquarters of Huawei Technologies Co.,
Ltd., Bantian, Longgang District, Shenzhen, Guangdong, 518129,
China
Factory’s name 1 ............................ : Huawei Machine Co., Ltd.
Factory address 1 ............................. No. 2 New City Avenue, Songshan Lake Sci. & Tech. Industry Park,
523808, Dongguan, People’s Republic of China.
Factory’s name 2 ............................ : Dongguan Yangtian Electron Technologies Co.,Ltd
Factory address 2 ............................. NO.152, LUYUAN RD, SCIENCE CITY, TANGXIA TOWN,
DONGGUAN CITY, GUANGDONG PROVINCE, P.R.CHINA

Document History
Date Internal reference Modification / Change / Status Revision
2022-09-15 Ryan He Initial report was written --
Supplementary information:

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 3 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Test items particulars

Equipment mobility........................... : Permanent connection


Operating condition .......................... : Continuous
Class of equipment .......................... : Class I
Protection against ingress of water.. : IP66 according to EN 60529
Mass of equipment [kg] .................... : Approx. 93,0kg

Test case verdicts


Test case does not apply
to the test object............................... : N/A
Test item does meet
the requirement ................................ : P(ass)
Test item does not meet
the requirement ................................ : F(ail)

Testing
Date of receipt of test item ............... : 2022-08-16
Date(s) of performance of test ......... : 2022-08-16 to 2022-09-13

General remarks:
The test result presented in this report relate only to the object(s) tested.
This report must not be reproduced in part or in full without the written approval of the issuing testing
laboratory.
”(see Annex #)" refers to additional information appended to the report.
"(see appended table)" refers to a table appended to the report.
Throughout this report a comma is used as the decimal separator.

The IEC61727 does not provide any limits of accuracy for the utility voltage and frequency measurement of
the PV-system. Therefore the values for tolerances given in EN 50438, Table 2 are used.
Tolerances on trip values tabel 2 EN50438:
- Voltage: +/- 1% of the nominal voltage;
- Frequency: +/- 0,5% of the nominal frequency
- Clearance time: +/- 10%

This Test Report consists of the following documents:


1. Test Results
2. Annex No. 1 – Pictures of the unit
3. Annex No. 2 – Test equipment list

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 4 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Copy of marking plate

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 5 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Copy of marking plate

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 6 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

General product information:


The Solar converter converts DC voltage into AC voltage.
The DC input of Solar converter can be supplied from PV array.

The input and output are protected by Varistors to Earth. The unit is providing EMC filtering at the output
toward mains. The unit does not provide galvanic separation from input to output (transformerless). The
output is switched off redundant by the high power switching bridge and a two relays. This assures that the
opening of the output circuit will also operate in case of one error.
Description of the electrical circuit: (Figure 1):
The internal control is redundant built. It consists of Microcontroller CPU2 (U101) and CPU1 (U100).
The CPU1 (U100) control the relays by switching signals; measures the PV voltage, PV current, Bus voltage,
grid voltage, frequency, AC current with injected DC and the array insulation resistance to ground. In addition
it tests the current sensors and the RCMU circuit before each start up.
The CPU2 (U101) is measures the grid voltage, grid frequency, DCI and residual current, also can switch off
the relays independently, and communicate with the CPU1 (U100) each other.
The current is measured by a current sensor. The AC current signal and the injected DC current signal are
sent to the CPU1 (U100). The CPU1 (U100) tests and calibrates before each start up all current sensors.
The unit provides two relays in series in all output conductors. When single fault applied to one relay, alarm
an error code in display panel, another redundant relay provides basic insulation maintained between the PV
array and the mains. All the relays are tested before each start up.

Figure 1 – Block diagram

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 7 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Differences of the models:


The model SUN2000-100KTL-M2 and SUN2000-115KTL-M2 have same electric circuits topology design,
same enclosure structure design, same main control circuits and firmware. The output power and current are
limited by software.

The product was tested on:


Hardware: V500R023
Software: V500R023C00SPC010

All tests were performed on SUN2000-115KTL-M2. Tests of the EUT of SUN2000-115KTL-M2 not applicable
for the model SUN2000-100KTL-M2 were performed on the concerned models and a statement is given at
the relevant test.

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 8 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

IEC61727:2004-12
Clause Requirement – Test Result – Remark Verdict
SECTION 4: Utility compatibility
4 General Noticed P
The quality of power provided by the PV system for the
on-site AC loads and for power delivered to the utility is
governed by practices and standards on voltage, flicker,
frequency, harmonics and power factor. Deviation from
these standards represents out-of-bounds conditions
and may require the PV system to sense the deviation
and properly disconnect from the utility system.
All power quality parameters (voltage, flicker, frequency,
harmonics, and power factor) must be measured at the
utility interface/ point of common coupling unless
otherwise specified.
4.1 Voltage, current and frequency Derived from tests P
The PV system AC voltage, current and frequency shall
be compatible with the utility system.
4.2 Normal voltage operating range Derived from tests P
Utility-interconnected PV systems do not normally
regulate voltage; they inject current into the utility.
Therefore, the voltage operating range for PV inverters
is selected as a protection function that responds to
abnormal utility conditions, not as a voltage regulation
function.
4.3 Flicker See table 4.3 P
The operation of the PV system should not cause
voltage flicker in excess of limits stated in the relevant
sections of IEC 61000-3-3 for systems less than 16 A or
IEC 61000-3-5 for systems with current of 16 A and
above.
4.4 DC injection See table 4.4 P
The PV system shall not inject DC current greater than
1 % of the rated inverter output current, into the utility
AC interface under any operating condition.
4.5 Normal frequency operating range See table 4.5 and 5.2.2 P
The PV system shall operate in synchronism with the
utility system, and within the frequency trip limits defined
in 5.2.2.

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 9 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

IEC61727:2004-12
Clause Requirement – Test Result – Remark Verdict
SECTION 4: Utility compatibility
4.6 Harmonics and waveform distortion See tables 4.6 (1) and P
Low levels of current and voltage harmonics are 4.6 (2)
desirable; the higher harmonic levels increase the
potential for adverse effects on connected equipment.
Acceptable levels of harmonic voltage and current
depend upon distribution system characteristics, type of
service, connected loads/apparatus, and established
utility practice.
The PV system output should have low current-
distortion levels to ensure that no adverse effects are
caused to other equipment connected to the utility
system.
Total harmonic current distortion shall be less than 5 %
at rated inverter output. Each individual harmonic shall
be limited to the percentages listed in Table 1.
Even harmonics in these ranges shall be less than
25 % of the lower odd harmonic limits listed. (see
Clause 4.6 Table 1 – Current distortion limits)
4.7 Power factor See table 4.7 P
The PV system shall have a lagging power factor
greater than 0,9 when the output is greater
than 50 % of the rated inverter output power.

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 10 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

IEC61727:2004-12
Clause Requirement – Test Result – Remark Verdict
SECTION 5: Personnel safety and equipment protection
5 General Noticed P
This Clause provides information and considerations for
the safe and proper operation of the utility-connected
PV systems.
5.1 Loss of utility voltage The loss of utility voltage P
To prevent islanding, a utility connected PV system shall test report for IEC61727
cease to energize the utility system from a de-energized according to IEC62116 is
distribution line irrespective of connected loads or other stored in archive at Bureau
generators within specified time limits. Veritas, Project Nr.
A utility distribution line can become de-energized for PV2207WDG0058-2
several reasons. For example, a substation breaker
opening due to fault conditions or the distribution line
switched out during maintenance.
If inverters (single or multiple) have DC SELV input and
have accumulated power below 1 kW then no
mechanical disconnect (relay) is required.
5.2 Over/under voltage and frequency See table 5.2.1 and 5.2.2 P
Abnormal conditions can arise on the utility system that
requires a response from the connected photovoltaic
system. This response is to ensure the safety of utility
maintenance personnel and the general public, as well
as to avoid damage to connected equipment, including
the photovoltaic system. The abnormal utility conditions
of concern are voltage and frequency excursions above
or below the values stated in this Clause, and the
complete disconnection of the utility, presenting the
potential for a distributed resource island.
5.2.1 Over/under voltage See table 5.2.1 P
When the interface voltage deviates outside the
conditions specified in Table 2, the photovoltaic system
shall cease to energize the utility distribution system.
This applies to any phase of a multiphase system.
All discussions regarding system voltage refer to the
local nominal voltage. The system shall sense abnormal
voltage and respond. The following conditions should be
met, with voltages in RMS and measured at the point of
utility connection.
(see clause 5.2.1 Table 2 – Response to abnormal
voltages)
The purpose of the allowed time delay is to ride through
short-term disturbances to avoid excessive nuisance
tripping. The unit does not have to cease to energize if
the voltage returns to the normal utility continuous
operation condition within the specified trip time.

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 11 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

IEC61727:2004-12
Clause Requirement – Test Result – Remark Verdict
SECTION 5: Personnel safety and equipment protection
5.2.2 Over/under frequency See table 5.2.2 P
When the utility frequency deviates outside the specified
conditions the photovoltaic system shall cease to
energize the utility line. The unit does not have to cease
to energize if the frequency returns to the normal utility
continuous operation condition within the specified trip
time.
When the utility frequency is outside the range of
±1 Hz, the system shall cease to energize the utility line
within 0,2 s. The purpose of the allowed range and time
delay is to allow continued operation for short-term
disturbances and to avoid excessive nuisance tripping in
weak-utility system conditions.
5.3 Islanding protection The loss of utility voltage P
The PV system must cease to energize the utility line test report for IEC61727
within 2 s of loss of utility. according to IEC62116 is
stored in archive at Bureau
Veritas, Project Nr.
PV2207WDG0058-2
5.4 Response to utility recovery See table 5.2 (1) and P
Following an out-of-range utility condition that has 5.2 (2)
caused the photovoltaic system to cease energizing, the
photovoltaic system shall not energize the utility line for
20 s to 5 min after the utility service voltage and
frequency have recovered to within the specified
ranges.
5.5 Earthing Stated in the manual. P
The utility interface equipment shall be
earthed/grounded in accordance with
IEC 60364-7-712.
5.6 Short circuit protection Stated in the manual. P
The photovoltaic system shall have short-circuit
protection in accordance with IEC 60364-7-712.
5.7 Isolation and switching Stated in the manual. P
A method of isolation and switching shall be provided in
accordance with IEC 60364-7-712.

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 12 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Test overview:

IEC 61727:2004-12

Clause Test Result

4 Type test:

4.3 Voltage Fluctuations and Flicker P

4.4 Monitoring of DC-Injection P

4.5 Normal frequency operating range (see 5.2.2 below) P

4.6 Harmonics and waveform distortion P

4.7 Power factor P

5.2.1 Voltage monitoring P

5.2.2 Frequency monitoring P

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 13 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Test Results

4.3 Voltage fluctuation and flicker P

Inverter >16A

Limit dc% = 3.3 Pst=1.0 Plt=0.65


Test model: SUN2000-100KTL-M2(230Va.c., 50Hz)
Test value: L1 phase 2,09 0,14 0,14
Test value: L2 phase 2,11 0,17 0,16
Test value: L3 phase 1,45 0,17 0,17
Test model: SUN2000-100KTL-M2(230Va.c., 60Hz)
Test value: L1 phase 1,52 0,12 0,12
Test value: L2 phase 1,43 0,13 0,12
Test value: L3 phase 1,36 0,12 0,12
Test model: SUN2000-100KTL-M2(480Va.c., 50Hz)
Test value: L1 phase 0,77 0,23 0,20
Test value: L2 phase 1,27 0,23 0,21
Test value: L3 phase 0,75 0,22 0,18
Test model: SUN2000-100KTL-M2(480Va.c., 60Hz)
Test value: L1 phase 0,67 0,11 0,10
Test value: L2 phase 0,65 0,12 0,11
Test value: L3 phase 0,70 0,15 0,13
Test model: SUN2000-115KTL-M2(230Va.c., 50Hz)
Test value: L1 phase 2,20 0,25 0,22
Test value: L2 phase 1,80 0,25 0,23
Test value: L3 phase 1,73 0,26 0,23
Test model: SUN2000-115KTL-M2(230Va.c., 60Hz)
Test value: L1 phase 1,63 0,23 0,22
Test value: L2 phase 2,23 0,23 0,22
Test value: L3 phase 1,46 0,24 0,23
Test model: SUN2000-115KTL-M2(480Va.c., 50Hz)
Test value: L1 phase 0,72 0,11 0,10
Test value: L2 phase 0,66 0,14 0,13
Test value: L3 phase 0,81 0,16 0,13
Test model: SUN2000-115KTL-M2(480Va.c., 60Hz)
Test value: L1 phase 0,76 0,12 0,12
Test value: L2 phase 0,75 0,10 0,10

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 14 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Test value: L3 phase 0,82 0,13 0,11


Note:
*The stationary deviance of dc% is more relevant than the dynamic deviance of dmax at starting and stopping.

Mains Impedance according EN61000-3-11: Rmax = 0.24Ω; jXmax= 0.15Ω @50Hz (|Zmax| = 0.283/0.4717Ω)
for single phase inverter use also Rn = 0.16Ω; jXn= 0.1Ω

Calculation of the maximum permissible grid impedance at the point of common coupling based on dc:
Zmax = Zref * 3,3% / dc(Pn)

The tests should be based on the limits of the EN 61000-3-11 for more than 16A.

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 15 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

4.4 Monitoring of Permanent DC-Injection P

Test model: SUN2000-100KTL-M2 (230Va.c., 50Hz)


IEC61727 Limit: 1% of Inom ( 1449,3 mA)
Output power: 25% 50% 100%
Abs. Max. Test Value:L1 130,0 130,0 140,0
Abs. Ave. Test Value:L1 35,7 25,6 18,9
Abs. Max. Test Value:L2 160,0 150,0 240,0
Abs. Ave. Test Value:L2 56,6 48,7 66,0
Abs. Max. Test Value:L3 140,0 140,0 190,0
Abs. Ave. Test Value:L3 49,5 42,6 46,3

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 16 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Test model: SUN2000-100KTL-M2 (230Va.c., 60Hz)


IEC61727 Limit: 1% of Inom ( 1449,3 mA)
Output power: 25% 50% 100%
Abs. Max. Test Value:L1 140,0 170,0 130,0
Abs. Ave. Test Value:L1 61,4 59,5 43,8
Abs. Max. Test Value:L2 170,0 170,0 250,0
Abs. Ave. Test Value:L2 79,8 75,1 93,9
Abs. Max. Test Value:L3 140,0 160,0 240,0
Abs. Ave. Test Value:L3 47,6 56,1 56,8

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 17 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Test model: SUN2000-100KTL-M2 (480Va.c., 50Hz)


IEC61727 Limit: 1% of Inom ( 1200,0 mA)
Output power: 25% 50% 100%
Abs. Max. Test Value:L1 90,0 90,0 80,0
Abs. Ave. Test Value:L1 40,2 48,3 39,5
Abs. Max. Test Value:L2 120,0 140,0 130,0
Abs. Ave. Test Value:L2 68,8 62,8 53,4
Abs. Max. Test Value:L3 120,0 140,0 140,0
Abs. Ave. Test Value:L3 64,7 61,6 61,7

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 18 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Test model: SUN2000-100KTL-M2 (480Va.c., 60Hz)


IEC61727 Limit: 1% of Inom ( 1200,0 mA)
Output power: 25% 50% 100%
Abs. Max. Test Value:L1 80,0 110,0 120,0
Abs. Ave. Test Value:L1 45,9 42,4 42,3
Abs. Max. Test Value:L2 170,0 150,0 140,0
Abs. Ave. Test Value:L2 77,8 70,0 51,9
Abs. Max. Test Value:L3 100,0 150,0 160,0
Abs. Ave. Test Value:L3 47,7 46,0 55,0

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 19 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Test model: SUN2000-115KTL-M2 (230Va.c., 50Hz)


IEC61727 Limit: 1% of Inom ( 1666,7 mA)
Output power: 25% 50% 100%
Abs. Max. Test Value:L1 140,0 310,0 70,0
Abs. Ave. Test Value:L1 53,0 162,4 39,3
Abs. Max. Test Value:L2 220,0 350,0 150,0
Abs. Ave. Test Value:L2 92,3 196,7 77,6
Abs. Max. Test Value:L3 180,0 310,0 220,0
Abs. Ave. Test Value:L3 52,7 128,5 156,0

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 20 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Test model: SUN2000-115KTL-M2 (230Va.c., 60Hz)


IEC61727 Limit: 1% of Inom (1666,7 mA)
Output power: 25% 50% 100%
Abs. Max. Test Value:L1 176,0 70,0 120,0
Abs. Ave. Test Value:L1 129,7 8,1 24,8
Abs. Max. Test Value:L2 220,0 170,0 140,0
Abs. Ave. Test Value:L2 20,0 25,1 29,8
Abs. Max. Test Value:L3 397,0 100,0 210,0
Abs. Ave. Test Value:L3 24,8 27,3 82,9

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 21 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Test model: SUN2000-115KTL-M2 (480Va.c., 50Hz)


IEC61727 Limit: 1% of Inom (1383,9 mA)
Output power: 25% 50% 100%
Abs. Max. Test Value:L1 294,0 50,0 60,0
Abs. Ave. Test Value:L1 18,9 15,3 20,6
Abs. Max. Test Value:L2 274,0 60,0 70,0
Abs. Ave. Test Value:L2 12,0 12,6 18,2
Abs. Max. Test Value:L3 570,0 50,0 80,0
Abs. Ave. Test Value:L3 14,5 11,9 35,2

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 22 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Test model: SUN2000-115KTL-M2 (480Va.c., 60Hz)


IEC61727 Limit: 1% of Inom (1383,9 mA)
Output power: 25% 50% 100%
Abs. Max. Test Value:L1 78,0 80,0 80,0
Abs. Ave. Test Value:L1 16,6 16,1 14,0
Abs. Max. Test Value:L2 64,0 90,0 60,0
Abs. Ave. Test Value:L2 12,0 16,0 12,5
Abs. Max. Test Value:L3 73,0 80,0 120,0
Abs. Ave. Test Value:L3 14,3 14,4 25,4

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 23 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

4.6 Harmonic Current Limit Test P

Test result: SUN2000-100KTL-M2 (230Va.c./50Hz)


Watts [kW] 33,46 33,43 33,27
Vrms [V] 230,77 230,57 230,71
Arms [A] 145,03 145,02 144,25
Frequency [Hz] 50,00 50,00 50,00
THD50 (100% output power) 0,816 0,887 0,697

Current Magnitude [A] at Harmonic


Harmonic % of Fundamental
100% rated output power Phase Current
order n
Limits [%]
L1 L2 L3 L1 L2 L3
1st 145,004 145,006 144,224 100,053 100,054 99,515 Three phase --
2nd 0,087 0,150 0,119 0,060 0,104 0,082 Three phase 1
3rd 0,370 0,349 0,233 0,255 0,241 0,161 Three phase 4
4th 0,076 0,140 0,076 0,052 0,097 0,052 Three phase 1
5th 0,116 0,045 0,109 0,080 0,031 0,075 Three phase 4
6th 0,088 0,096 0,039 0,060 0,067 0,027 Three phase 1
7th 0,170 0,176 0,161 0,118 0,121 0,111 Three phase 4
8th 0,049 0,081 0,084 0,034 0,056 0,058 Three phase 1
9th 0,075 0,165 0,105 0,052 0,114 0,073 Three phase 4
10th 0,066 0,051 0,054 0,045 0,035 0,037 Three phase 0,5
11th 0,169 0,086 0,149 0,117 0,059 0,103 Three phase 2
12th 0,057 0,050 0,061 0,039 0,035 0,042 Three phase 0,5
13th 0,047 0,185 0,178 0,033 0,128 0,123 Three phase 2
14th 0,036 0,041 0,038 0,025 0,028 0,026 Three phase 0,5
15th 0,079 0,180 0,111 0,055 0,124 0,077 Three phase 2
16th 0,042 0,041 0,040 0,029 0,029 0,028 Three phase 0,5
17th 0,293 0,221 0,205 0,202 0,152 0,141 Three phase 1,5
18th 0,041 0,047 0,044 0,028 0,032 0,031 Three phase 0,5
19th 0,296 0,433 0,310 0,204 0,299 0,214 Three phase 1,5
20th 0,047 0,042 0,049 0,032 0,029 0,034 Three phase 0,5
21th 0,090 0,117 0,060 0,062 0,081 0,042 Three phase 1,5
22th 0,043 0,043 0,043 0,030 0,030 0,030 Three phase 0,5
23th 0,245 0,274 0,209 0,169 0,189 0,144 Three phase 0,6
24th 0,046 0,054 0,050 0,032 0,037 0,035 Three phase 0,5
25th 0,346 0,455 0,267 0,238 0,314 0,184 Three phase 0,6
26th 0,046 0,056 0,050 0,032 0,038 0,034 Three phase 0,5
27th 0,109 0,071 0,057 0,075 0,049 0,040 Three phase 0,6
28th 0,054 0,053 0,051 0,037 0,036 0,035 Three phase 0,5
29th 0,207 0,222 0,212 0,143 0,153 0,146 Three phase 0,6
30th 0,053 0,062 0,058 0,037 0,043 0,040 Three phase 0,5
31th 0,392 0,445 0,276 0,270 0,307 0,190 Three phase 0,6
32th 0,059 0,058 0,058 0,040 0,040 0,040 Three phase 0,5
33th 0,099 0,123 0,075 0,068 0,085 0,052 Three phase 0,6
34th 0,065 0,059 0,062 0,045 0,041 0,042 Three phase --
35th 0,215 0,233 0,197 0,148 0,161 0,136 Three phase --
36th 0,070 0,069 0,067 0,048 0,047 0,046 Three phase --
37th 0,399 0,381 0,276 0,275 0,263 0,191 Three phase --
38th 0,073 0,072 0,072 0,050 0,050 0,050 Three phase --
39th 0,097 0,148 0,103 0,067 0,102 0,071 Three phase --
40th 0,080 0,076 0,078 0,055 0,053 0,054 Three phase --
41th 0,172 0,194 0,155 0,119 0,134 0,107 Three phase --
42th 0,078 0,081 0,074 0,054 0,056 0,051 Three phase --
No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 24 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

43th 0,370 0,312 0,304 0,255 0,215 0,210 Three phase --


44th 0,072 0,074 0,075 0,050 0,051 0,051 Three phase --
45th 0,099 0,136 0,130 0,068 0,094 0,090 Three phase --
46th 0,072 0,071 0,068 0,050 0,049 0,047 Three phase --
47th 0,127 0,123 0,117 0,088 0,085 0,080 Three phase --
48th 0,065 0,060 0,062 0,045 0,042 0,043 Three phase --
49th 0,307 0,276 0,302 0,212 0,191 0,208 Three phase --
50th 0,055 0,056 0,053 0,038 0,039 0,036 Three phase --
Note:

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 25 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

4.6 Harmonic Current Limit Test P

Test result: SUN2000-100KTL-M2 (230Va.c./60Hz)


Watts [kW] 33,56 33,53 33,38
Vrms [V] 230,74 230,54 230,67
Arms [A] 145,48 145,47 144,74
Frequency [Hz] 60,00 60,00 60,00
THD50 (100% output power) 0,829 0,943 0,782

Current Magnitude [A] at Harmonic


Harmonic % of Fundamental
100% rated output power Phase Current
order n
Limits [%]
L1 L2 L3 L1 L2 L3
1st 145,070 145,000 144,290 100,098 100,050 99,560 Three phase --
2nd 0,140 0,160 0,120 0,097 0,110 0,083 Three phase 1
3rd 0,420 0,460 0,400 0,290 0,317 0,276 Three phase 4
4th 0,020 0,090 0,080 0,014 0,062 0,055 Three phase 1
5th 0,130 0,040 0,150 0,090 0,028 0,104 Three phase 4
6th 0,050 0,030 0,080 0,035 0,021 0,055 Three phase 1
7th 0,210 0,200 0,110 0,145 0,138 0,076 Three phase 4
8th 0,010 0,090 0,080 0,007 0,062 0,055 Three phase 1
9th 0,080 0,150 0,060 0,055 0,104 0,041 Three phase 4
10th 0,120 0,060 0,080 0,083 0,041 0,055 Three phase 0,5
11th 0,140 0,100 0,050 0,097 0,069 0,035 Three phase 2
12th 0,100 0,060 0,070 0,069 0,041 0,048 Three phase 0,5
13th 0,100 0,130 0,030 0,069 0,090 0,021 Three phase 2
14th 0,090 0,070 0,090 0,062 0,048 0,062 Three phase 0,5
15th 0,090 0,240 0,180 0,062 0,166 0,124 Three phase 2
16th 0,030 0,050 0,060 0,021 0,035 0,041 Three phase 0,5
17th 0,290 0,160 0,240 0,200 0,110 0,166 Three phase 1,5
18th 0,070 0,050 0,040 0,048 0,035 0,028 Three phase 0,5
19th 0,360 0,490 0,330 0,248 0,338 0,228 Three phase 1,5
20th 0,050 0,050 0,060 0,035 0,035 0,041 Three phase 0,5
21th 0,090 0,120 0,150 0,062 0,083 0,104 Three phase 1,5
22th 0,030 0,100 0,060 0,021 0,069 0,041 Three phase 0,5
23th 0,210 0,230 0,210 0,145 0,159 0,145 Three phase 0,6
24th 0,040 0,060 0,040 0,028 0,041 0,028 Three phase 0,5
25th 0,440 0,550 0,330 0,304 0,380 0,228 Three phase 0,6
26th 0,050 0,070 0,040 0,035 0,048 0,028 Three phase 0,5
27th 0,050 0,150 0,110 0,035 0,104 0,076 Three phase 0,6
28th 0,070 0,040 0,070 0,048 0,028 0,048 Three phase 0,5
29th 0,230 0,290 0,120 0,159 0,200 0,083 Three phase 0,6
30th 0,030 0,110 0,090 0,021 0,076 0,062 Three phase 0,5
31th 0,450 0,390 0,480 0,311 0,269 0,331 Three phase 0,6
32th 0,090 0,090 0,070 0,062 0,062 0,048 Three phase 0,5
33th 0,010 0,240 0,160 0,007 0,166 0,110 Three phase 0,6
34th 0,070 0,070 0,060 0,048 0,048 0,041 Three phase --
35th 0,110 0,320 0,260 0,076 0,221 0,179 Three phase --
36th 0,040 0,130 0,080 0,028 0,090 0,055 Three phase --
37th 0,330 0,280 0,330 0,228 0,193 0,228 Three phase --
38th 0,080 0,070 0,050 0,055 0,048 0,035 Three phase --
39th 0,100 0,160 0,130 0,069 0,110 0,090 Three phase --
40th 0,020 0,040 0,010 0,014 0,028 0,007 Three phase --
41th 0,140 0,200 0,100 0,097 0,138 0,069 Three phase --
42th 0,040 0,110 0,080 0,028 0,076 0,055 Three phase --
No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 26 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

43th 0,290 0,260 0,230 0,200 0,179 0,159 Three phase --


44th 0,170 0,140 0,020 0,117 0,097 0,014 Three phase --
45th 0,100 0,110 0,140 0,069 0,076 0,097 Three phase --
46th 0,030 0,030 0,030 0,021 0,021 0,021 Three phase --
47th 0,150 0,150 0,160 0,104 0,104 0,110 Three phase --
48th 0,040 0,050 0,030 0,028 0,035 0,021 Three phase --
49th 0,200 0,170 0,110 0,138 0,117 0,076 Three phase --
50th 0,100 0,110 0,060 0,069 0,076 0,041 Three phase --
Note:

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 27 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

4.6 Harmonic Current Limit Test P

Test result: SUN2000-100KTL-M2 (480Va.c./50Hz)


Watts [kW] 33,59 33,58 33,38
Vrms [V] 277,78 277,55 277,75
Arms [A] 120,95 121,03 120,20
Frequency [Hz] 50,00 50,00 50,00
THD50 (100% output power) 1,002 0,935 0,886

Current Magnitude [A] at Harmonic


Harmonic % of Fundamental
100% rated output power Phase Current
order n
Limits [%]
L1 L2 L3 L1 L2 L3
1st 120,909 121,001 120,174 100,524 100,601 99,913 Three phase --
2nd 0,297 0,206 0,261 0,247 0,171 0,217 Three phase 1
3rd 0,322 0,239 0,175 0,268 0,199 0,146 Three phase 4
4th 0,043 0,073 0,100 0,036 0,061 0,083 Three phase 1
5th 0,206 0,113 0,115 0,171 0,094 0,095 Three phase 4
6th 0,097 0,133 0,049 0,080 0,111 0,041 Three phase 1
7th 0,152 0,172 0,042 0,126 0,143 0,035 Three phase 4
8th 0,071 0,060 0,093 0,059 0,050 0,077 Three phase 1
9th 0,105 0,107 0,113 0,087 0,089 0,094 Three phase 4
10th 0,088 0,092 0,069 0,073 0,077 0,057 Three phase 0,5
11th 0,147 0,097 0,093 0,122 0,081 0,077 Three phase 2
12th 0,063 0,073 0,070 0,053 0,061 0,058 Three phase 0,5
13th 0,056 0,091 0,112 0,046 0,076 0,093 Three phase 2
14th 0,037 0,045 0,034 0,031 0,038 0,029 Three phase 0,5
15th 0,040 0,060 0,035 0,033 0,050 0,029 Three phase 2
16th 0,035 0,043 0,041 0,029 0,036 0,034 Three phase 0,5
17th 0,190 0,197 0,173 0,158 0,164 0,144 Three phase 1,5
18th 0,047 0,045 0,045 0,039 0,037 0,037 Three phase 0,5
19th 0,413 0,336 0,341 0,343 0,279 0,284 Three phase 1,5
20th 0,041 0,044 0,037 0,034 0,037 0,031 Three phase 0,5
21th 0,065 0,101 0,069 0,054 0,084 0,057 Three phase 1,5
22th 0,045 0,050 0,040 0,038 0,041 0,033 Three phase 0,5
23th 0,138 0,204 0,194 0,114 0,170 0,161 Three phase 0,6
24th 0,048 0,047 0,040 0,040 0,039 0,033 Three phase 0,5
25th 0,364 0,283 0,297 0,303 0,235 0,247 Three phase 0,6
26th 0,053 0,054 0,049 0,044 0,045 0,041 Three phase 0,5
27th 0,132 0,156 0,109 0,110 0,129 0,090 Three phase 0,6
28th 0,057 0,054 0,048 0,047 0,045 0,040 Three phase 0,5
29th 0,276 0,270 0,261 0,229 0,225 0,217 Three phase 0,6
30th 0,074 0,062 0,074 0,062 0,051 0,061 Three phase 0,5
31th 0,316 0,260 0,284 0,263 0,216 0,236 Three phase 0,6
32th 0,065 0,055 0,070 0,054 0,045 0,058 Three phase 0,5
33th 0,156 0,140 0,124 0,130 0,117 0,103 Three phase 0,6
34th 0,062 0,061 0,053 0,052 0,051 0,044 Three phase --
35th 0,309 0,308 0,284 0,257 0,256 0,236 Three phase --
36th 0,082 0,065 0,095 0,068 0,054 0,079 Three phase --
37th 0,303 0,287 0,271 0,252 0,238 0,225 Three phase --
38th 0,078 0,066 0,070 0,065 0,055 0,058 Three phase --
39th 0,126 0,167 0,087 0,104 0,139 0,073 Three phase --
40th 0,070 0,061 0,065 0,058 0,051 0,054 Three phase --
41th 0,245 0,275 0,208 0,203 0,229 0,173 Three phase --
42th 0,076 0,064 0,077 0,063 0,053 0,064 Three phase --
No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 28 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

43th 0,313 0,325 0,330 0,260 0,270 0,274 Three phase --


44th 0,068 0,053 0,058 0,056 0,044 0,048 Three phase --
45th 0,105 0,175 0,079 0,088 0,145 0,066 Three phase --
46th 0,071 0,051 0,054 0,059 0,042 0,045 Three phase --
47th 0,187 0,153 0,127 0,156 0,127 0,106 Three phase --
48th 0,063 0,054 0,062 0,053 0,045 0,051 Three phase --
49th 0,266 0,293 0,320 0,221 0,243 0,266 Three phase --
50th 0,056 0,048 0,042 0,047 0,040 0,035 Three phase --
Note:

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 29 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

4.6 Harmonic Current Limit Test P

Test result: SUN2000-100KTL-M2 (480Va.c./60Hz)


Watts [kW] 33,80 33,76 33,57
Vrms [V] 277,78 277,48 277,68
Arms [A] 121,72 121,70 120,92
Frequency [Hz] 60,00 60,00 60,00
THD50 (100% output power) 1,154 1,264 1,105

Current Magnitude [A] at Harmonic


Harmonic % of Fundamental
100% rated output power Phase Current
order n
Limits [%]
L1 L2 L3 L1 L2 L3
1st 121,662 121,688 120,875 101,151 101,173 100,496 Three phase --
2nd 0,050 0,097 0,093 0,042 0,081 0,078 Three phase 1
3rd 0,415 0,383 0,239 0,345 0,318 0,198 Three phase 4
4th 0,049 0,115 0,101 0,041 0,096 0,084 Three phase 1
5th 0,104 0,050 0,098 0,086 0,041 0,081 Three phase 4
6th 0,078 0,115 0,076 0,065 0,096 0,063 Three phase 1
7th 0,163 0,246 0,112 0,136 0,205 0,093 Three phase 4
8th 0,069 0,119 0,135 0,058 0,099 0,112 Three phase 1
9th 0,087 0,162 0,086 0,073 0,135 0,072 Three phase 4
10th 0,047 0,069 0,069 0,039 0,057 0,057 Three phase 0,5
11th 0,183 0,061 0,140 0,152 0,050 0,116 Three phase 2
12th 0,059 0,048 0,047 0,049 0,040 0,039 Three phase 0,5
13th 0,072 0,252 0,202 0,060 0,210 0,168 Three phase 2
14th 0,092 0,090 0,088 0,076 0,075 0,073 Three phase 0,5
15th 0,201 0,173 0,127 0,167 0,144 0,106 Three phase 2
16th 0,109 0,101 0,105 0,090 0,084 0,087 Three phase 0,5
17th 0,353 0,309 0,282 0,293 0,257 0,234 Three phase 1,5
18th 0,064 0,059 0,073 0,054 0,049 0,061 Three phase 0,5
19th 0,461 0,589 0,437 0,384 0,490 0,363 Three phase 1,5
20th 0,074 0,064 0,099 0,062 0,053 0,083 Three phase 0,5
21th 0,115 0,093 0,115 0,095 0,077 0,096 Three phase 1,5
22th 0,086 0,082 0,067 0,072 0,068 0,056 Three phase 0,5
23th 0,190 0,327 0,349 0,158 0,272 0,290 Three phase 0,6
24th 0,072 0,072 0,083 0,060 0,060 0,069 Three phase 0,5
25th 0,395 0,462 0,341 0,328 0,384 0,283 Three phase 0,6
26th 0,071 0,068 0,069 0,059 0,057 0,057 Three phase 0,5
27th 0,078 0,062 0,122 0,065 0,052 0,101 Three phase 0,6
28th 0,096 0,104 0,090 0,080 0,087 0,075 Three phase 0,5
29th 0,255 0,300 0,359 0,212 0,249 0,299 Three phase 0,6
30th 0,096 0,069 0,119 0,080 0,057 0,099 Three phase 0,5
31th 0,376 0,454 0,316 0,312 0,378 0,262 Three phase 0,6
32th 0,085 0,072 0,097 0,071 0,060 0,080 Three phase 0,5
33th 0,163 0,117 0,146 0,135 0,097 0,121 Three phase 0,6
34th 0,114 0,107 0,128 0,095 0,089 0,107 Three phase --
35th 0,307 0,256 0,299 0,255 0,213 0,248 Three phase --
36th 0,104 0,078 0,168 0,087 0,065 0,140 Three phase --
37th 0,402 0,437 0,332 0,334 0,363 0,276 Three phase --
38th 0,077 0,089 0,109 0,064 0,074 0,091 Three phase --
39th 0,180 0,129 0,106 0,150 0,107 0,088 Three phase --
40th 0,101 0,087 0,114 0,084 0,072 0,095 Three phase --
41th 0,221 0,187 0,207 0,183 0,155 0,172 Three phase --
42th 0,095 0,095 0,156 0,079 0,079 0,130 Three phase --
No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 30 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

43th 0,442 0,474 0,376 0,368 0,394 0,312 Three phase --


44th 0,069 0,074 0,088 0,058 0,062 0,074 Three phase --
45th 0,152 0,165 0,110 0,126 0,137 0,092 Three phase --
46th 0,062 0,076 0,084 0,051 0,063 0,070 Three phase --
47th 0,152 0,124 0,138 0,126 0,103 0,115 Three phase --
48th 0,061 0,065 0,114 0,051 0,054 0,095 Three phase --
49th 0,329 0,364 0,361 0,274 0,303 0,300 Three phase --
50th 0,074 0,094 0,088 0,062 0,078 0,074 Three phase --
Note:

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 31 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

4.6 Harmonic Current Limit Test P

Test result: SUN2000-115KTL-M2 (230Va.c./50Hz)


Watts [kW] 38,40 38,41 38,25
Vrms [V] 230,86 230,63 230,78
Arms [A] 166,35 166,54 165,76
Frequency [Hz] 50,00 50,00 50,00
THD50 (100% output power) 0,650 0,738 0,600

Current Magnitude [A] at Harmonic


Harmonic % of Fundamental
100% rated output power Phase Current
order n
Limits [%]
L1 L2 L3 L1 L2 L3
1st 166,283 166,498 165,722 99,770 99,899 99,433 Three phase --
2nd 0,200 0,233 0,307 0,120 0,140 0,184 Three phase 1
3rd 0,480 0,681 0,415 0,288 0,409 0,249 Three phase 4
4th 0,112 0,070 0,139 0,067 0,042 0,083 Three phase 1
5th 0,108 0,110 0,117 0,065 0,066 0,070 Three phase 4
6th 0,066 0,053 0,065 0,040 0,032 0,039 Three phase 1
7th 0,216 0,158 0,155 0,130 0,095 0,093 Three phase 4
8th 0,046 0,049 0,055 0,027 0,029 0,033 Three phase 1
9th 0,121 0,069 0,146 0,072 0,041 0,087 Three phase 4
10th 0,066 0,051 0,049 0,039 0,031 0,030 Three phase 0,5
11th 0,129 0,129 0,077 0,077 0,077 0,046 Three phase 2
12th 0,053 0,061 0,058 0,032 0,037 0,035 Three phase 0,5
13th 0,109 0,127 0,094 0,065 0,076 0,056 Three phase 2
14th 0,050 0,046 0,044 0,030 0,028 0,026 Three phase 0,5
15th 0,063 0,090 0,105 0,038 0,054 0,063 Three phase 2
16th 0,041 0,051 0,044 0,024 0,031 0,026 Three phase 0,5
17th 0,248 0,199 0,169 0,149 0,119 0,102 Three phase 1,5
18th 0,040 0,049 0,046 0,024 0,029 0,027 Three phase 0,5
19th 0,192 0,291 0,215 0,115 0,175 0,129 Three phase 1,5
20th 0,042 0,050 0,049 0,025 0,030 0,029 Three phase 0,5
21th 0,085 0,092 0,047 0,051 0,055 0,028 Three phase 1,5
22th 0,046 0,053 0,044 0,028 0,032 0,027 Three phase 0,5
23th 0,226 0,189 0,152 0,136 0,114 0,091 Three phase 0,6
24th 0,046 0,045 0,045 0,027 0,027 0,027 Three phase 0,5
25th 0,229 0,328 0,153 0,137 0,197 0,092 Three phase 0,6
26th 0,048 0,053 0,051 0,029 0,032 0,030 Three phase 0,5
27th 0,084 0,098 0,079 0,050 0,059 0,047 Three phase 0,6
28th 0,057 0,049 0,051 0,034 0,029 0,030 Three phase 0,5
29th 0,252 0,206 0,223 0,151 0,124 0,134 Three phase 0,6
30th 0,056 0,050 0,050 0,033 0,030 0,030 Three phase 0,5
31th 0,248 0,359 0,239 0,149 0,216 0,143 Three phase 0,6
32th 0,061 0,063 0,061 0,037 0,038 0,037 Three phase 0,5
33th 0,100 0,087 0,142 0,060 0,052 0,085 Three phase 0,6
34th 0,069 0,057 0,062 0,042 0,034 0,037 Three phase --
35th 0,243 0,226 0,232 0,146 0,135 0,139 Three phase --
36th 0,065 0,060 0,058 0,039 0,036 0,035 Three phase --
37th 0,262 0,315 0,257 0,157 0,189 0,154 Three phase --
38th 0,064 0,065 0,064 0,038 0,039 0,038 Three phase --
39th 0,126 0,095 0,144 0,075 0,057 0,087 Three phase --
40th 0,075 0,069 0,072 0,045 0,041 0,043 Three phase --
41th 0,217 0,204 0,179 0,130 0,122 0,107 Three phase --
42th 0,075 0,071 0,073 0,045 0,043 0,044 Three phase --
No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 32 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

43th 0,247 0,263 0,222 0,148 0,158 0,133 Three phase --


44th 0,076 0,073 0,074 0,045 0,044 0,045 Three phase --
45th 0,092 0,088 0,150 0,055 0,053 0,090 Three phase --
46th 0,078 0,068 0,077 0,047 0,041 0,046 Three phase --
47th 0,220 0,210 0,150 0,132 0,126 0,090 Three phase --
48th 0,068 0,062 0,065 0,041 0,037 0,039 Three phase --
49th 0,208 0,208 0,166 0,125 0,125 0,100 Three phase --
50th 0,060 0,056 0,059 0,036 0,033 0,036 Three phase --
Note:

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 33 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

4.6 Harmonic Current Limit Test P

Test result: SUN2000-115KTL-M2 (230Va.c./60Hz)


Watts [kW] 38,49 38,49 38,34
Vrms [V] 230,84 230,61 230,74
Arms [A] 166,78 166,91 166,20
Frequency [Hz] 60,00 60,00 60,00
THD50 (100% output power) 0,729 0,825 0,703

Current Magnitude [A] at Harmonic


Harmonic % of Fundamental
100% rated output power Phase Current
order n
Limits [%]
L1 L2 L3 L1 L2 L3
1st 166,755 166,901 166,180 100,053 100,141 99,708 Three phase --
2nd 0,118 0,064 0,119 0,071 0,038 0,072 Three phase 1
3rd 0,457 0,703 0,535 0,274 0,422 0,321 Three phase 4
4th 0,052 0,063 0,051 0,031 0,038 0,031 Three phase 1
5th 0,087 0,091 0,153 0,052 0,055 0,092 Three phase 4
6th 0,124 0,145 0,072 0,075 0,087 0,043 Three phase 1
7th 0,196 0,183 0,109 0,117 0,110 0,065 Three phase 4
8th 0,074 0,111 0,096 0,044 0,067 0,057 Three phase 1
9th 0,099 0,109 0,143 0,060 0,066 0,086 Three phase 4
10th 0,054 0,058 0,051 0,032 0,035 0,031 Three phase 0,5
11th 0,116 0,093 0,061 0,069 0,056 0,037 Three phase 2
12th 0,054 0,060 0,065 0,032 0,036 0,039 Three phase 0,5
13th 0,080 0,106 0,104 0,048 0,064 0,062 Three phase 2
14th 0,079 0,105 0,089 0,048 0,063 0,053 Three phase 0,5
15th 0,104 0,119 0,141 0,062 0,072 0,084 Three phase 2
16th 0,095 0,087 0,098 0,057 0,052 0,059 Three phase 0,5
17th 0,296 0,227 0,225 0,178 0,136 0,135 Three phase 1,5
18th 0,067 0,095 0,061 0,040 0,057 0,037 Three phase 0,5
19th 0,277 0,357 0,338 0,166 0,214 0,203 Three phase 1,5
20th 0,073 0,075 0,050 0,044 0,045 0,030 Three phase 0,5
21th 0,107 0,104 0,081 0,064 0,062 0,048 Three phase 1,5
22th 0,078 0,057 0,082 0,047 0,034 0,049 Three phase 0,5
23th 0,307 0,315 0,242 0,184 0,189 0,145 Three phase 0,6
24th 0,069 0,076 0,061 0,041 0,046 0,036 Three phase 0,5
25th 0,309 0,401 0,275 0,185 0,241 0,165 Three phase 0,6
26th 0,098 0,068 0,064 0,059 0,041 0,039 Three phase 0,5
27th 0,101 0,120 0,070 0,061 0,072 0,042 Three phase 0,6
28th 0,074 0,080 0,070 0,044 0,048 0,042 Three phase 0,5
29th 0,329 0,330 0,285 0,197 0,198 0,171 Three phase 0,6
30th 0,081 0,072 0,078 0,049 0,043 0,047 Three phase 0,5
31th 0,337 0,387 0,317 0,202 0,232 0,190 Three phase 0,6
32th 0,111 0,082 0,080 0,066 0,049 0,048 Three phase 0,5
33th 0,098 0,126 0,091 0,059 0,075 0,055 Three phase 0,6
34th 0,103 0,089 0,096 0,062 0,053 0,057 Three phase --
35th 0,276 0,280 0,255 0,165 0,168 0,153 Three phase --
36th 0,098 0,090 0,086 0,059 0,054 0,051 Three phase --
37th 0,302 0,309 0,273 0,181 0,185 0,164 Three phase --
38th 0,103 0,087 0,097 0,062 0,052 0,058 Three phase --
39th 0,104 0,114 0,102 0,063 0,069 0,061 Three phase --
40th 0,097 0,091 0,097 0,058 0,055 0,058 Three phase --
41th 0,229 0,218 0,209 0,137 0,131 0,125 Three phase --
42th 0,080 0,077 0,078 0,048 0,046 0,047 Three phase --
No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 34 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

43th 0,261 0,277 0,260 0,156 0,166 0,156 Three phase --


44th 0,073 0,072 0,080 0,044 0,043 0,048 Three phase --
45th 0,097 0,089 0,105 0,058 0,053 0,063 Three phase --
46th 0,067 0,067 0,068 0,040 0,040 0,041 Three phase --
47th 0,187 0,176 0,156 0,112 0,105 0,094 Three phase --
48th 0,051 0,045 0,056 0,031 0,027 0,033 Three phase --
49th 0,242 0,227 0,216 0,145 0,136 0,130 Three phase --
50th 0,044 0,052 0,053 0,026 0,031 0,032 Three phase --
Note:

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 35 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

4.6 Harmonic Current Limit Test P

Test result: SUN2000-115KTL-M2 (480Va.c./50Hz)


Watts [kW] 38,53 38,54 38,34
Vrms [V] 277,86 277,61 277,81
Arms [A] 138,71 138,84 138,03
Frequency [Hz] 50,00 50,00 50,00
THD50 (100% output power) 0,753 0,765 0,743

Current Magnitude [A] at Harmonic


Harmonic % of Fundamental
100% rated output power Phase Current
order n
Limits [%]
L1 L2 L3 L1 L2 L3
1st 138,683 138,818 138,009 100,263 100,361 99,775 Three phase --
2nd 0,289 0,179 0,197 0,209 0,129 0,142 Three phase 1
3rd 0,376 0,331 0,209 0,272 0,239 0,151 Three phase 4
4th 0,039 0,074 0,095 0,028 0,054 0,069 Three phase 1
5th 0,169 0,087 0,120 0,122 0,063 0,087 Three phase 4
6th 0,088 0,112 0,050 0,064 0,081 0,036 Three phase 1
7th 0,122 0,152 0,062 0,088 0,110 0,045 Three phase 4
8th 0,070 0,103 0,086 0,051 0,075 0,062 Three phase 1
9th 0,090 0,133 0,071 0,065 0,096 0,052 Three phase 4
10th 0,095 0,066 0,082 0,069 0,048 0,059 Three phase 0,5
11th 0,108 0,073 0,140 0,078 0,053 0,101 Three phase 2
12th 0,064 0,068 0,064 0,046 0,049 0,046 Three phase 0,5
13th 0,065 0,100 0,123 0,047 0,072 0,089 Three phase 2
14th 0,041 0,054 0,075 0,030 0,039 0,054 Three phase 0,5
15th 0,144 0,155 0,117 0,104 0,112 0,084 Three phase 2
16th 0,039 0,043 0,037 0,028 0,031 0,027 Three phase 0,5
17th 0,235 0,228 0,243 0,170 0,165 0,176 Three phase 1,5
18th 0,044 0,036 0,040 0,032 0,026 0,029 Three phase 0,5
19th 0,248 0,301 0,310 0,179 0,218 0,224 Three phase 1,5
20th 0,044 0,045 0,049 0,032 0,033 0,035 Three phase 0,5
21th 0,143 0,098 0,108 0,104 0,071 0,078 Three phase 1,5
22th 0,049 0,041 0,043 0,035 0,029 0,031 Three phase 0,5
23th 0,177 0,249 0,266 0,128 0,180 0,192 Three phase 0,6
24th 0,040 0,042 0,042 0,029 0,030 0,030 Three phase 0,5
25th 0,198 0,284 0,263 0,143 0,205 0,190 Three phase 0,6
26th 0,048 0,055 0,051 0,034 0,040 0,037 Three phase 0,5
27th 0,132 0,066 0,111 0,095 0,047 0,080 Three phase 0,6
28th 0,048 0,055 0,049 0,035 0,040 0,036 Three phase 0,5
29th 0,257 0,327 0,313 0,186 0,237 0,226 Three phase 0,6
30th 0,061 0,070 0,057 0,044 0,051 0,041 Three phase 0,5
31th 0,195 0,208 0,254 0,141 0,151 0,184 Three phase 0,6
32th 0,064 0,061 0,056 0,046 0,044 0,041 Three phase 0,5
33th 0,130 0,120 0,095 0,094 0,087 0,069 Three phase 0,6
34th 0,059 0,054 0,060 0,043 0,039 0,043 Three phase --
35th 0,290 0,279 0,301 0,210 0,202 0,218 Three phase --
36th 0,060 0,072 0,059 0,044 0,052 0,043 Three phase --
37th 0,235 0,234 0,184 0,170 0,169 0,133 Three phase --
38th 0,076 0,067 0,063 0,055 0,048 0,046 Three phase --
39th 0,119 0,136 0,140 0,086 0,098 0,101 Three phase --
40th 0,067 0,062 0,070 0,049 0,045 0,050 Three phase --
41th 0,209 0,203 0,240 0,151 0,147 0,174 Three phase --
42th 0,062 0,059 0,063 0,045 0,042 0,045 Three phase --
No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 36 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

43th 0,265 0,238 0,178 0,192 0,172 0,128 Three phase --


44th 0,058 0,061 0,060 0,042 0,044 0,043 Three phase --
45th 0,088 0,057 0,099 0,063 0,041 0,071 Three phase --
46th 0,062 0,059 0,059 0,045 0,043 0,043 Three phase --
47th 0,108 0,147 0,169 0,078 0,107 0,122 Three phase --
48th 0,053 0,049 0,046 0,038 0,035 0,033 Three phase --
49th 0,230 0,237 0,230 0,166 0,171 0,166 Three phase --
50th 0,048 0,039 0,038 0,034 0,028 0,028 Three phase --
Note:

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 37 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

4.6 Harmonic Current Limit Test P

Test result: SUN2000-115KTL-M2 (480Va.c./60Hz)


Watts [kW] 38,45 38,45 38,25
Vrms [V] 277,77 277,54 277,73
Arms [A] 138,44 138,55 137,74
Frequency [Hz] 60,00 60,00 60,00
THD50 (100% output power) 0,863 0,801 0,758

Current Magnitude [A] at Harmonic


Harmonic % of Fundamental
100% rated output power Phase Current
order n
Limits [%]
L1 L2 L3 L1 L2 L3
1st 138,395 138,505 137,711 100,055 100,134 99,560 Three phase --
2nd 0,136 0,073 0,083 0,098 0,053 0,060 Three phase 1
3rd 0,486 0,461 0,309 0,351 0,333 0,223 Three phase 4
4th 0,158 0,065 0,168 0,114 0,047 0,121 Three phase 1
5th 0,101 0,053 0,121 0,073 0,038 0,087 Three phase 4
6th 0,077 0,099 0,059 0,056 0,071 0,043 Three phase 1
7th 0,200 0,185 0,070 0,145 0,134 0,050 Three phase 4
8th 0,061 0,073 0,044 0,044 0,053 0,032 Three phase 1
9th 0,073 0,084 0,068 0,053 0,061 0,049 Three phase 4
10th 0,062 0,044 0,082 0,045 0,031 0,059 Three phase 0,5
11th 0,161 0,056 0,132 0,116 0,040 0,096 Three phase 2
12th 0,062 0,040 0,068 0,045 0,029 0,049 Three phase 0,5
13th 0,065 0,110 0,117 0,047 0,080 0,085 Three phase 2
14th 0,062 0,060 0,068 0,045 0,044 0,049 Three phase 0,5
15th 0,081 0,103 0,098 0,058 0,074 0,071 Three phase 2
16th 0,081 0,071 0,058 0,058 0,052 0,042 Three phase 0,5
17th 0,261 0,212 0,189 0,188 0,153 0,137 Three phase 1,5
18th 0,045 0,065 0,061 0,033 0,047 0,044 Three phase 0,5
19th 0,338 0,358 0,308 0,244 0,259 0,223 Three phase 1,5
20th 0,049 0,045 0,051 0,035 0,033 0,037 Three phase 0,5
21th 0,101 0,054 0,072 0,073 0,039 0,052 Three phase 1,5
22th 0,059 0,076 0,074 0,043 0,055 0,054 Three phase 0,5
23th 0,200 0,211 0,278 0,144 0,152 0,201 Three phase 0,6
24th 0,070 0,064 0,066 0,050 0,046 0,048 Three phase 0,5
25th 0,281 0,347 0,260 0,203 0,251 0,188 Three phase 0,6
26th 0,071 0,066 0,074 0,051 0,048 0,053 Three phase 0,5
27th 0,107 0,065 0,079 0,077 0,047 0,057 Three phase 0,6
28th 0,066 0,071 0,080 0,048 0,051 0,058 Three phase 0,5
29th 0,290 0,245 0,315 0,209 0,177 0,227 Three phase 0,6
30th 0,099 0,097 0,113 0,072 0,070 0,081 Three phase 0,5
31th 0,268 0,288 0,234 0,194 0,208 0,169 Three phase 0,6
32th 0,110 0,110 0,109 0,079 0,080 0,079 Three phase 0,5
33th 0,134 0,111 0,153 0,097 0,080 0,110 Three phase 0,6
34th 0,077 0,077 0,092 0,055 0,056 0,067 Three phase --
35th 0,363 0,221 0,249 0,262 0,160 0,180 Three phase --
36th 0,073 0,070 0,074 0,053 0,051 0,054 Three phase --
37th 0,243 0,238 0,221 0,175 0,172 0,159 Three phase --
38th 0,071 0,068 0,096 0,051 0,049 0,069 Three phase --
39th 0,079 0,066 0,114 0,057 0,048 0,082 Three phase --
40th 0,068 0,054 0,073 0,049 0,039 0,053 Three phase --
41th 0,280 0,201 0,180 0,202 0,146 0,130 Three phase --
42th 0,060 0,059 0,065 0,044 0,043 0,047 Three phase --
No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 38 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

43th 0,256 0,265 0,231 0,185 0,192 0,167 Three phase --


44th 0,059 0,055 0,071 0,042 0,040 0,051 Three phase --
45th 0,041 0,043 0,085 0,029 0,031 0,062 Three phase --
46th 0,047 0,045 0,052 0,034 0,033 0,038 Three phase --
47th 0,187 0,162 0,163 0,136 0,117 0,118 Three phase --
48th 0,033 0,046 0,045 0,024 0,033 0,033 Three phase --
49th 0,273 0,289 0,275 0,197 0,209 0,199 Three phase --
50th 0,036 0,037 0,033 0,026 0,027 0,024 Three phase --
Note:

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 39 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

4.7 Power factor P

Test conditions: Test model: SUN2000-100KTL-M2

Output power [kW] ~10% ~25% ~50% ~75% ~100%


10,92 kW 25,63 kW 50,44 kW 75,74 kW 100,65 kW
Test AC voltage [V]

230Va.c., 50Hz 0,9998c 1,0000 1,0000 1,0000 1,0000

Test conditions: Test model: SUN2000-100KTL-M2

Output power [kW] ~10% ~25% ~50% ~75% ~100%


10,91 kW 25,61 kW 50,31 kW 75,55 kW 100,59 kW
Test AC voltage [V]

230Va.c., 60Hz 0,9998c 1,0000 1,0000 1,0000 1,0000

Test conditions: Test model: SUN2000-100KTL-M2

Output power [kW] ~10% ~25% ~50% ~75% ~100%


10,78 kW 25,44 kW 50,24 kW 75,55 kW 100,70 kW
Test AC voltage [V]

480Va.c., 50Hz 0,9998c 1,0000 1,0000 1,0000 1,0000

Test conditions: Test model: SUN2000-100KTL-M2

Output power [kW] ~10% ~25% ~50% ~75% ~100%


10,78 kW 25,43 kW 50,22 kW 75,52 kW 100,64 kW
Test AC voltage [V]

480Va.c., 60Hz 0,9997c 1,0000 1,0000 1,0000 1,0000

Test conditions: Test model: SUN2000-115KTL-M2

Output power [kW] ~10% ~25% ~50% ~75% ~100%


11,49 kW 29,11 kW 58,54 kW 86,46 kW 115,46 kW
Test AC voltage [V]

230Va.c., 50Hz 0,9999c 1,0000 1,0000 1,0000 1,0000

Test conditions: Test model: SUN2000-115KTL-M2

Output power [kW] ~10% ~25% ~50% ~75% ~100%


11,49 kW 29,10 kW 58,66 kW 86,43 kW 115,43 kW
Test AC voltage [V]
No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 40 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

230Va.c., 60Hz 0,9999c 1,0000 1,0000 1,0000 1,0000

Test conditions: Test model: SUN2000-115KTL-M2

Output power [kW] ~10% ~25% ~50% ~75% ~100%


11,36 kW 28,90 kW 58,47 kW 86,51 kW 115,67 kW
Test AC voltage [V]

480Va.c., 50Hz 0,9998c 1,0000 1,0000 1,0000 1,0000

Test conditions: Test model: SUN2000-115KTL-M2

Output power [kW] ~10% ~25% ~50% ~75% ~100%


11,35 kW 28,67 kW 58,46 kW 86,48 kW 115,59 kW
Test AC voltage [V]

480Va.c., 60Hz 0,9998c 1,0000 1,0000 1,0000 1,0000

Note:
*The PV system shall have a lagging power factor greater than 0,9 when the output is greater than 50% of
the rated inverter output power.

The letter “i” is short for “inductive” and indicates inductive power factor. In case of capacitive power factor
the letter “c” is used instead.

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 41 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

5.2.1 Voltage monitoring P

IEC 61727: First Level


Test Output power: 115kW
conditions: Output voltage: 230V
Frequency: 50Hz
L1 phase
Under Voltage Over Voltage
Parameter Voltage Time Voltage Time
Limit 195,5V 253,0V
<= 2,0s <= 2,0s
Trip value 194,6V 253,8V
Disconnection 230V to 230V to
1,963 1,974 1,982 1,983 1,978 1,968
time [ms] 191V 258V
L2 phase
Under Voltage Over Voltage
Parameter Voltage Time Voltage Time
Limit 195,5V 253,0V
<= 2,0s <= 2,0s
Trip value 194,7V 253,5V
Disconnection 230V to 230V to
1,960 1,966 1,968 1,971 1,986 1,961
time [ms] 191V 258V
L3 phase
Under Voltage Over Voltage
Parameter Voltage Time Voltage Time
Limit 195,5V 253,0V
<= 2,0s <= 2,0s
Trip value 194,7V 253,7V
Disconnection 230V to 230V to
1,978 1,978 1,981 1,976 1,973 1,962
time [ms] 191V 258V
Reconnection
20s<t<300s 86,8 s 20s<t<300s 84,6 s
time [s]

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 42 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

IEC 61727: Second Level


Test Output power: 115kW
conditions: Output voltage: 230V
Frequency: 50Hz
L1 phase
Under Voltage Over Voltage
Parameter Voltage Time Voltage Time
Limit 115,0V 310,5V
<= 100ms <= 50ms
Trip value 114,1V 311,2V
Disconnection 230V to 230V to
74,0 76,0 70,0 48,0 44,0 46,0
time [ms] 110V 312V
L2 phase
Under Voltage Over Voltage
Parameter Voltage Time Voltage Time
Limit 115,0V 310,5V
<= 100ms <= 50ms
Trip value 114,6V 310,4V
Disconnection 230V to 230V to
74,0 70,0 74,0 42,0 46,0 42,0
time [ms] 110V 312V
L3 phase
Under Voltage Over Voltage
Parameter Voltage Time Voltage Time
Limit 115,0V 310,5V
<= 100ms <= 50ms
Trip value 114,1V 310,2V
Disconnection 230V to 230V to
68,0 70,0 72,0 38,0 40,0 38,0
time [ms] 110V 312V
Reconnection
20s<t<300s 72,9 s 20s<t<300s 73,1 s
time [s]
Note:
The tests had been performed on the SUN2000-115KTL-M2 are valid for the SUN2000-100KTL-M2 since it
is almost same as in hardware and just power derated by software.

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 43 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Under Voltage First Level, L1 phase

Over voltage First Level, L1 phase

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 44 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Under Voltage First Level, L2 phase

Over voltage First Level, L2 phase

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 45 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Under Voltage First Level, L3 phase

Over voltage First Level, L3 phase

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 46 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Reconnection time: Under Voltage First Level

Reconnection time:Over voltage First Level

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 47 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Under Voltage Second Level, L1 phase

Over voltage Second Level, L1 phase

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 48 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Under Voltage Second Level, L2 phase

Over voltage Second Level, L2 phase

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 49 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Under Voltage Second Level, L3 phase

Over voltage Second Level, L3 phase

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 50 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Reconnection time: Under Voltage Second Level

Reconnection time:Over voltage Second Level

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 51 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

5.2.1 Voltage monitoring P

IEC 61727: First Level


Test Output power: 115kW
conditions: Output voltage: 480V
Frequency: 50Hz
L1 phase
Under Voltage Over Voltage
Parameter Voltage Time Voltage Time
Limit 408,0V 528,0V
<= 2,0s <= 2,0s
Trip value 408,4V 529,4V
Disconnection 480V to 480V to
1,984 1,976 1,984 1,980 1,978 1,980
time [ms] 398V 539V
L2 phase
Under Voltage Over Voltage
Parameter Voltage Time Voltage Time
Limit 408,0V 528,0V
<= 2,0s <= 2,0s
Trip value 408,1V 529,3V
Disconnection 480V to 480V to
1,976 1,984 1,980 1,984 1,980 1,988
time [ms] 398V 539V
L3 phase
Under Voltage Over Voltage
Parameter Voltage Time Voltage Time
Limit 408,0V 528,0V
<= 2,0s <= 2,0s
Trip value 408,5V 529,6V
Disconnection 480V to 480V to
1,982 1,990 1,978 1,980 1,972 1,980
time [ms] 398V 539V
Reconnection
20s<t<300s 95,6 s 20s<t<300s 100,8 s
time [s]

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 52 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

IEC 61727: Second Level


Test Output power: 115kW
conditions: Output voltage: 480V
Frequency: 50Hz
L1 phase
Under Voltage Over Voltage
Parameter Voltage Time Voltage Time
Limit 240,0V 648,0V
<= 100ms <= 50ms
Trip value 239,8V 649,1V
Disconnection 480V to 480V to
93,0 92,0 91,0 33,0 35,0 37,0
time [ms] 230V 658V
L2 phase
Under Voltage Over Voltage
Parameter Voltage Time Voltage Time
Limit 240,0V 648,0V
<= 100ms <= 50ms
Trip value 239,7V 648,1V
Disconnection 480V to 480V to
92,0 94,0 92,0 40,0 34,0 32,0
time [ms] 230V 658V
L3 phase
Under Voltage Over Voltage
Parameter Voltage Time Voltage Time
Limit 240,0V 648,0V
<= 100ms <= 50ms
Trip value 239,8V 648,6
Disconnection 480V to 480V to
88,0 94,0 96,0 36,0 35,0 39,0
time [ms] 230V 658V
Reconnection
20s<t<300s 95,0 s 20s<t<300s 120,4 s
time [s]
Note:
The tests had been performed on the SUN2000-115KTL-M2 are valid for the SUN2000-100KTL-M2 since it
is almost same as in hardware and just power derated by software.

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 53 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Under Voltage First Level, L1 phase

Over voltage First Level, L1 phase

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 54 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Under Voltage First Level, L2 phase

Over voltage First Level, L2 phase

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 55 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Under Voltage First Level, L3 phase

Over voltage First Level, L3 phase

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 56 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Reconnection time: Under Voltage First Level

Reconnection time:Over voltage First Level

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 57 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Under Voltage Second Level, L1 phase

Over voltage Second Level, L1 phase

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 58 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Under Voltage Second Level, L2 phase

Over voltage Second Level, L2 phase

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 59 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Under Voltage Second Level, L3 phase

Over voltage Second Level, L3 phase

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 60 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Reconnection time: Under Voltage Second Level

Reconnection time:Over voltage Second Level

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 61 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

5.2.2 Frequency monitoring (50Hz) P

IEC 61727
Any output power level
Test
Output voltage: 480V
conditions:
Output frequency: 50Hz
Under frequency Over frequency
Frequency Frequency
Parameter Time [ms] Time [ms]
[Hz] [Hz]
Output Voltage 85%UN UN 110%UN 85%UN UN 110%UN

Limit 49.00Hz 200ms 200ms 200ms 51.00Hz 200ms 200ms 200ms

Trip value 48,99Hz 48,99Hz 48,99Hz 51,00Hz 51,00Hz 51,00Hz


Disconnection 49,01Hz to 50,99Hz to
185,0 185,0 180,0 177,0 189,0 182,0
time 48,99Hz 51,01Hz
Reconnection
20s<t<300s 85,8 s 20s<t<300s 85,4 s
time
Note:
The tests had been performed on the SUN2000-115KTL-M2 are valid for SUN2000-100KTL-M2 since it is
almost same as in hardware and just power derated by software.

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 62 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Under Frequency:

Over Frequency:

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 63 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Reconnection time: Under Frequency:

Reconnection time: Over Frequency:

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 64 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

5.2.2 Frequency monitoring (60Hz) P

IEC 61727
Any output power level
Test
Output voltage: 480V
conditions:
Output frequency: 60Hz
Under frequency Over frequency
Frequency Frequency
Parameter Time [ms] Time [ms]
[Hz] [Hz]
Output Voltage 85%UN UN 110%UN 85%UN UN 110%UN

Limit 59,00Hz 200ms 200ms 200ms 61,00Hz 200ms 200ms 200ms

Trip value 59,00Hz 59,00Hz 59,00Hz 61,00Hz 61,00Hz 61,00Hz


Disconnection 59,01Hz to 60,99Hz to
178,4 176,0 172,4 175,6 178,8 179,6
time 58,99Hz 61,01Hz
Reconnection
20s<t<300s 86,0 s 20s<t<300s 85,2 s
time
Note:
The tests had been performed on the SUN2000-115KTL-M2 are valid for SUN2000-100KTL-M2 since it is
almost same as in hardware and just power derated by software.

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 65 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Under Frequency:

Over Frequency:

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 66 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Reconnection time: Under Frequency:

Reconnection time: Over Frequency:

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 67 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Annex No. 1
Pictures of the unit

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 68 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Enclosure front view

Enclosure side view

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 69 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Enclosure side view

Enclosure top view

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 70 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

DC terminal

AC terminal

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 71 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Annex 2
Test equipment list

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 73 of 74 TEST REPORT IEC/EN 61727 VER.2
Report No.: PV2208WDG0121-1

Test location: Huawei Technologies Co., Ltd


Dates of performance test: 2022-08-16 to 2022-09-13

Equipment Internal no.: Manufacturer: Type: Serial no.: Next


calibration
Power Analyzer A160918200 HIOKI PW6001-06 160713398 Aug. 04, 2023
Power Analyzer 36090900139 YOKOGAWA WT3000 91J902079 Aug. 05, 2023
AC Source A161015843 KEYSIGHT N8957APV DE16391766
AC Source A161217057 KEYSIGHT N8957APV DE16391781
AC Source A161217054 KEYSIGHT N8957APV DE16411817
AC Source A161217051 KEYSIGHT N8957APV DE16431824
AC Source A161217048 KEYSIGHT N8957APV DE16431827
AC Source A161149925 KEYSIGHT N8957APV DE16431830
AC Source A161149924 KEYSIGHT N8957APV DE16431833
Monitored by
AC Source A160211548 KEYSIGHT N8957APV DE15401242
Power
AC Source A161008708 KEYSIGHT N8957APV DE16341675 Analyzer
AC Source A161008705 KEYSIGHT N8957APV DE16341669
AC Source A161008717 KEYSIGHT N8957APV DE16321631
AC Source A160814354 KEYSIGHT N8957APV DE16231520
DC Simulation
A181218502 AMETEK RS90 1623A00088
Power Supply
DC Simulation
A161221087 AMETEK RS90 1623A00067
Power Supply
RLC Load A7150027DG Qunling ACLT-3803H 93VOO2869
Oscilloscope A160514132 Tektronix DPO7054C C200858 Jul. 28, 2023

Current transducer A120717856 HIOKI CT6865 120118225 Jun. 19, 2023


Current transducer A170420332 HIOKI CT6863-05 170333301 Dec. 19, 2022
Current transducer A170613866 HIOKI CT6862-05 170342413 Dec. 19, 2022
Voltage transducer A150708925 Tektronix P5205A C023640 Apr. 30, 2023
Temp. & Humi.
140904974 CENTER CENTER 313 140904974 May 25, 2023
Recorder

--End of test report--

No. 96, Guantai Road (Houjie Section), Houjie Tel: +86 769 8593 5656
Bureau Veritas Shenzhen Co., Ltd.
Town, Dongguan City, Guangdong Province, Fax: +86 769 8599 1080
Dongguan Branch
523942, People’s Republic of China Email: customerservice.dg@cn.bureauveritas.com
Page 74 of 74 TEST REPORT IEC/EN 61727 VER.2

You might also like